Relays & Sockets RH

RH Series Compact Power Relays

Switches & Pilot Lights


Key features
• SPDT through 4PDT, 10A contacts
• Compact power type relays
• Miniature power relays with a large capacity
• 10A contact capacity
• Compact size saves space

Signaling Lights
Part Number Selection
Part Number
Blade Coil Voltage Code
Contact Model PCB Terminal
Terminal (Standard Stock in bold)

Relays & Sockets


Standard RH1B-U 0 RH1V2-U 0
SPDT With Indicator RH1B-UL 0 —
AC6V, AC12V, AC24V, AC110V, AC120V,
With Check Button RH1B-UC 0 — AC220V, AC240V DC6V, DC12V, DC24V,
DC48V, DC110V
With Indicator and Check Button RH1B-ULC 0 —
Top Bracket Mounting RH1B-UT 0 —
With Diode (DC coil only) RH1B-UD 0 RH1V2-UD 0 DC6V, DC12V, DC24V, DC48V, DC110V
With Indicator and Diode (DC coil only) RH1B-ULD 0 — DC12V, DC24V, DC48V, DC110V
Standard RH2B-U 0 RH2V2-U 0
DPDT
With Indicator RH2B-UL 0 RH2V2-UL 0

Timers
AC6V, AC12V, AC24V, AC110-120V,
With Check Button RH2B-UC 0 — AC220-240V
DC6V, DC12V, DC24V, DC48V, DC100-110V
With Indicator and Check Button RH2B-ULC 0 —
Top Bracket Mounting RH2B-UT 0 —
With Diode (DC coil only) RH2B-UD 0 RH2V2-UD 0
DC6V, DC12V, DC24V, DC48V, DC100-110V
With Indicator and Diode (DC coil only) RH2B-ULD 0 RH2V2-ULD 0
Standard RH3B-U 0 RH3V2-U 0
3PDT

Contactors
With Indicator RH3B-UL 0 RH3V2-UL 0
AC6V, AC12V, AC24V, AC110V, AC120V,
With Check Button RH3B-UC 0 — AC220V, AC240V DC6V, DC12V, DC24V,
DC48V, DC110V
With Indicator and Check Button RH3B-ULC 0 —
Top Bracket Mounting RH3B-UT 0 —
With Diode (DC coil only) RH3B-UD 0 —
DC6V, DC12V, DC24V, DC48V, DC110V
With Indicator and Diode (DC coil only) RH3B-ULD 0 —
Standard RH4B-U 0 RH4V2-U 0

Terminal Blocks
4PDT
With Indicator RH4B-UL 0 RH4V2-UL 0
AC6V, AC12V, AC24V, AC110V, AC120V,
With Check Button RH4B-UC 0 — AC220V, AC240V DC6V, DC12V, DC24V, DC48V,
DC110V
With Indicator and Check Button RH4B-ULC 0 —
Top Bracket Mounting RH4B-UT 0 —
With Diode (DC coil only) RH4B-UD 0 RH4V2-UD 0
DC6V, DC12V, DC24V, DC48V, DC110V
With Indicator and Diode (DC coil only) RH4B-ULD 0 —
Circuit Breakers

PCB terminal relays are designed to mount directly to a circuit board without any socket.
Ordering Information
When ordering, specify the Part No. and coil voltage code:
(example) RH3B-U AC120V
Part No. Coil Voltage Code

1705151135
800-262-IDEC (4332) • USA & Canada 873
RH Relays & Sockets

Sockets (for Blade Terminal Models)


Switches & Pilot Lights

Relays Standard DIN Rail Mount 1 Finger-safe DIN Rail Mount 1 Through Panel Mount PCB Mount
RH1B SH1B-05 SH1B-O5C SH1B-51 SH1B-62
RH2B SH2B-05 SH2B-05C SH2B-51 SH2B-62 1. DIN Rail mount
socket comes with
RH3B SH3B-05 SH3B-05C SH3B-51 SH3B-62 two horseshoe
clips. Do not use
RH4B SH4B-05 SH4B-05C SH4B-51 SH4B-62 unless you plan to
insert pullover wire
spring. Replacement
horseshoe clip part
number is Y778-011.
Signaling Lights

Hold Down Springs & Clips


For DIN For Through Panel &
Appearance Item Relay
Mount Socket PCB Mount Socket
RH1B SY2S-02F1 2 2. Must use horseshoe clip when
mounting in DIN mount socket.
RH2B SY4S-02F1 2
Replacement horseshoe clip
Pullover Wire Spring SY4S-51F1 part number is Y778-011.
RH3B SH3B-05F1 2
Relays & Sockets

3. Two required per relay.


RH4B SH4B-02F1 2

Leaf Spring (side latch) RH1B, RH2B, RH3B, RH4B SFA-202 3 SFA-302 3

Leaf Spring (top latch) RH1B, RH2B, RH3B, RH4B SFA-101 3 SFA-301 3

AC Coil Ratings
Rated Current (mA) ±15% at 20°C Coil Resistance (Ω) Operation Characteristics
Timers

Voltage AC 50Hz AC 60Hz ±10% at 20°C (against rated values at 20ºC)


(V)
Max. Continuous Pickup Dropout
SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT
Applied Voltage Voltage Voltage
6 170 240 330 387 150 200 280 330 18.8 9.4 6.4 5.4
12 86 121 165 196 75 100 140 165 76.8 39.3 25.3 21.2
24 42 60.5 81 98 37 50 70 83 300 153 103 84.5
110 9.6 — 18.1 21.6 8.4 — 15.5 18.2 6,950 — 2,200 1,800
Contactors

9.4- 80% 30%


110-120 — — — — 8.0-9.2 — — — — — — 110%
10.8 maximum minimum
120 8.6 — 16.4 19.5 7.5 — 14.2 16.5 8,100 — 10,800 7,360
220 4.7 — 8.8 10.7 4.1 — 7.7 9.1 25,892 — 10,800 7,360
220-240 — 4.7-5.4 — — — 4.0-4.6 — — 18,820 — —
240 4.9 — 8.2 9.8 4.3 — 7.1 8.3 26,710 — 12,100 9,120

DC Coil Ratings
Terminal Blocks

Coil Resistance (Ω) Operation Characteristics


Rated Current (mA) ±15% at 20°C
Voltage ±10% at 20°C (against rated values at 20ºC)
(V) Max. Continuous Pickup Dropout
SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT
Applied Voltage Voltage Voltage
6 128 150 240 250 47 40 25 24
12 64 75 120 125 188 160 100 96
24 32 36.9 60 62 750 650 400 388 Standard coil
80% 10%
110% voltages are in
48 18 18.5 30 31 2,660 2,600 1,600 1,550 maximum minimum
Circuit Breakers

BOLD.
100-110 — 8.2-9.0 — — — 12,250 — —
110 8 — 12.8 15 13,800 — 8,600 7,340

874 www.IDEC.com 1705151135


Relays & Sockets RH

Contact Ratings UL Ratings

Switches & Pilot Lights


Maximum Contact Capacity Resistive General Use Horsepower Rating
Allowable Contact Power Rated Load Voltage RH1 RH1 RH1
Continuous RH3 RH4 RH3 RH4 RH3 RH4
Model RH2 RH2 RH2
Current Resistive Inductive Voltage Res. Ind.
Load Load (V) Load Load 240V AC 10A 7.5A 7.5A 7A 6.5A 5A 1/3 HP 1/3 HP —
110 AC 10A 7A 120V AC — 10A 10A — 7.5A 7.5A 1/6 HP 1/6 HP —
1540VA 990VA
SPDT 10A 220 AC 7A 4.5A 30V DC 10A 10A — 7A — — — — —
300W 210W
30 DC 10A 7A 28V DC — — 10A — — — — — —
110 AC 10A 7.5A
DPDT CSA Ratings

Signaling Lights
1650VA 1100VA
3PDT 10A 220 AC 7.5A 5A
300W 225W Horse-
4PDT
30 DC 10A 7.5A Resistive General Use power
Note: Inductive load for the rated load — cos ø = 0.3, L/R = 7 ms Voltage Rating
RH1 RH2 RH3 RH4 RH1 RH2 RH3 RH4 RH1, 2, 3
240V AC 10A 10A — 7.5A 7A 7A 7A 5A 1/3 HP
TÜV Ratings 120V AC 10A 10A 10A 10A 7.5A 7.5A — 7.5A 1/6 HP
Voltage RH1 RH2 RH3 RH4 30V DC 10A 10A 10A 10A 7A 7.5A — — —

Relays & Sockets


240V AC 10A 10A 7.5A 7.5A
30V DC 10A 10A 10A 10A

AC: cos ø = 1.0, DC: L/R = 0 ms

Socket Specifications
Sockets Terminal Electrical Rating Wire Size Torque
(Coil) M3 screws 5.5 - 9 in•lbs
SH1B-05 250V, 10A Maximum up to 2–#12AWG
DIN Rail (contact) M3.5 screws with captive wire clamp 9 - 11.5 in•lbs

Timers
Mount SH2B-05
Sockets SH3B-05 M3.5 screws with captive wire clamp 300V, 10A Maximum up to 2–#12AWG 9 - 11.5 in•lbs
SH4B-05
(coil) M3 screws 5.5 - 9 in•lbs
SH1B-05C 250V, 10A Maximum up to 2–#12AWG
Finger-safe (contact) M3.5 screws with captive wire clamp, fingersafe 9 - 11.5 in•lbs
DIN Rail SH2B-05C
Mount SH3B-05C M3.5 screws with captive wire clamp, fingersafe 300V, 10A Maximum up to 2–#12AWG 9 - 11.5 in•lbs
SH4B-05C
Through SH1B-51

Contactors
Panel SH2B-51
Solder 300V, 10A — —
Mount SH3B-51
Socket SH4B-51
SH1B-62 PCB mount 250V, 10A — —
PCB Mount SH2B-62
Socket SH3B-62 PCB mount 300V, 10A — —
SH4B-62

Accessories Terminal Blocks


Item Appearance Use with Part No. Remarks
The BNDN1000 is designed to accommodate DIN mount sockets.
Aluminum
Made of durable extruded aluminum, the BNDN1000 measures 0.413
DIN Rail All DIN rail sockets BNDN1000
(10.5mm) in height and 1.37 (35mm) in width (DIN standard). Standard
(1 meter length)
length is 39” (1,000mm).

DIN Rail End


Circuit Breakers

DIN rail BNL5 9.1 mm wide.


Stop

Replacement
DIN mount sockets and hold For use on DIN rail mount socket when using pullover wire hold down
Hold-Down Y778-011
down springs. spring. 2 pieces included with each socket.
Spring Anchor

1705151135
800-262-IDEC (4332) • USA & Canada 875
RH Relays & Sockets

Specifications
Switches & Pilot Lights

Contact Material Silver cadmium oxide


Contact Resistance 1 50mΩ maximum
Minimum Applicable Load 24V DC, 30 mA; 5V DC, 100 mA (reference value)
SPDT
20ms maximum
DPDT
Operating Time 2
3PDT
25ms maximum
4PDT
SPDT
20ms maximum
DPDT
Signaling Lights

Release Time 2
3PDT
25ms maximum
4PDT
SPDT AC: 1.1VA (50Hz), 1VA (60Hz) DC: 0.8W
Power Consumption DPDT AC: 1.4VA (50Hz), 1.2VA (60Hz) DC: 0.9W
(approx.) 3PDT AC: 2VA (50Hz), 1.7VA (60Hz) DC: 1.5W
4PDT AC: 2.5VA (50Hz), 2VA (60Hz) DC: 1.5W
Insulation Resistance 100MΩ minimum (500V DC megger)
Relays & Sockets

Between live and dead parts: 2,000V AC, 1 minute


SPDT Between contact and coil: 2,000V AC, 1 minute
Between contacts of the same pole: 1,000V AC, 1 minute
Dielectric Strength 3
Between live and dead parts: 2,000V AC, 1 minute
DPDT
Between contact and coil: 2,000V AC, 1 minute
3PDT
Between contacts of different poles: 2,000V AC, 1 minute
4PDT
Between contacts of the same pole: 1,000V AC, 1 minute
Electrical: 1,800 operations/hour maximum
Operating Frequency
Mechanical: 18,000 operations/hour maximum
Damage limits: 10 to 55Hz, amplitude 0.5 mm
Vibration Resistance
Operating extremes: 10 to 55Hz, amplitude 0.5 mm
Timers

Damage limits: 1,000m/s2 (100G)


Shock Resistance Operating extremes: 200m/s2 (20G - SPDT, DPDT)
100m/s2 (10G - 3PDT, 4PDT)
Mechanical Life 50,000,000 operations minimum
DPDT 500,000 operations minimum (120V AC, 10A)

Electrical Life SPDT


3PDT 200,000 operations minimum (120V AC, 10A)
4PDT
Contactors

SPDT
Operating DPDT
–25 to +70°C (no freezing)
Temperature 4 3PDT
4PDT
Operating Humidity 45 to 85% RH (no condensation)
Weight (approx.) SPDT: 24g, DPDT: 37g, 3PDT: 50g, 4PDT: 74g

Note: Above values are initial values.


1. Measured using 5V DC, 1A voltage drop method
Terminal Blocks

2. Measured at the rated voltage (at 20°C), excluding contact bouncing


Release time of relays with diode: 40 ms maximum
3. Relays with indicator or diode: 1000V AC, 1 minute
4. For use under different temperature conditions, refer to Continuous Load Current vs. Operating Temperature Curve. The operating
temperature range of relays with indicator or diode is –25 to +40°C.
Circuit Breakers

876 www.IDEC.com 1705151135


Relays & Sockets RH

Characteristics (Reference Data)

Switches & Pilot Lights


Electrical Life Curves
AC Load DC Load
1000 1000

(RH1) 120V AC resistive (RH1)


500 500

Life (X 10,000 operations)


Life (x 10,000 operations)

30V DC resistive
100

Signaling Lights
100

50 50
100V DC resistive

30V DC inductive
20 20
240V AC inductive 240V AC resistive
120V AC inductive 100V DC inductive

10 10
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
Load Current (A) Load Current (A)

(RH2) 1000 (RH2) 1000


120V AC resistive

Relays & Sockets


30V DC resistive
500 500

Life (X 10,000 operations)


Life (x 10,000 operations)

100 100

50 50 100V DC resistive 30V DC


inductive
240V AC inductive 240V AC resistive
120V AC inductive 100V DC inductive

20 20

Timers
10 10
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
Load Current (A) Load Current (A)

(RH3/RH4) 1000 (RH3/RH4) 1000

120V AC resistive
30V DC resistive
500 500
Life (X 10,000 operations)

30V DC inductive
Life (x 10,000 operations)

Contactors
100 100

50 50

20 20 100V DC resistive
240V AC inductive
240V AC resistive 100V DC inductive
120V AC inductive
10
10 1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
Load Current (A) Load Current (A)

Maximum Switching Capacity


Terminal Blocks
(RH1) (RH2/RH3/RH4)
10.0 10.0
AC resistive AC resistive

5.0 5.0 AC inductive


AC inductive
Load Current (A)

DC resistive
Load Current (A)

DC resistive
1.0 1.0
DC inductive

0.5 DC inductive 0.5


Circuit Breakers

0.1 0.1
1 5 10 50 100 200 300 1 5 10 50 100 200 300
Load Voltage (V) Load Voltage (V)

1705151135
800-262-IDEC (4332) • USA & Canada 877
RH Relays & Sockets

Continuous Load Current vs. Operating Temperature Curve (Basic Type, With Check Button, and Top Bracket Mounting Type)
Switches & Pilot Lights

(RH1) Note: The rated voltage is (RH2) Note: The rated voltage is (RH3/RH4) Note: The rated voltage is
applied to the coil. applied to the coil. applied to the coil.
100 100 100
90 90 90
80 80
Operating Temperature (˚C)

80

Operating Temperature (˚C)


Operating Temperature (˚C)
DC Coil
70 70 DC Coil 70
60 60 60
50 AC Coil 50 50 AC/DC Coil
40 AC Coil
40 40
30 30 30
20 20 20
Signaling Lights

10 10 10
0 0 0
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
Load Current (A) Load Current (A) Load Current (A)
Internal Connection (View from Bottom)
Basic Type
SPDT DPDT 3PDT 4PDT With Check Button

Front
1 2 3 4 Pushbutton
Relays & Sockets

5 6 7 8
9 10 11 12
Contacts can be operated by pressing the
13 (–) (+) 14 check button.

With Indicator (-L type)


SPDT 3PDT 4PDT DPDT

1 1 2 4 1 2 3 4 1 4
5 5 6 8 When the relay is energized,
5 6 7 8 5 8
Below 9 9 10 12
Below 9 12 the indicator goes on.
9 10 11 12
100V 13 14 13 ( – ) ( + )14
24V AC/ • Relay coils less than
(–) (+) 13( – ) ( + )14 13( – ) ( + )14
AC/DC DC 100V DC do not contain a
Timers

protection diode (except


DPDT).
• Relay coils below 100V
1 1 2 4 1 4
use LED indicator, coils
1 2 3 4
5 5 8 above 100V use neon lamp
100V 5 6 8 5 6 7 8 24V AC/
9 9 12 indicator.
AC/DC 9 10 12 9 10 11 12 DC and
13 14 13 (–) (+) 14 • LED color of DPDT model
and over (–) (+) 13 (–) (+) 14 over
is green
13( – ) ( + )14
Contactors

With Diode (-D type)


SPDT DPDT 3PDT 4PDT
Contains a diode to absorb the back emf
1 1 4 1 2 4 1 2 3 4 generated when the coil is de-energized. The
5 5 8 5 6 8 5 6 7 8 release time is slightly longer. Available for DC
9 9 12 9 10 12 9 10 11 12 coil only.
13
(–)
14
(+)
13 (–) (+) 14
13 (–) (+) 14 13 (–) (+) 14 • Diode Characteristics
Reverse withstand voltage: 1,000V
Forward current: 1A
Terminal Blocks
Circuit Breakers

878 www.IDEC.com 1705151135


Relays & Sockets RH

With Indicator LED & Diode (-LD type)

Switches & Pilot Lights


SPDT 3PDT 4PDT DPDT

1
1 4
5
5 8
9 Below
Below 9 12
13 14 24V AC/
100V DC (–) (+) 13( – ) ( + )14
DC
Contains an LED indicator and
a surge absorber, and has the
same height as the basic type.

Signaling Lights
1
1 4
LED color of DPDT model is
5
5 8 green.
9 24V AC/
100V DC 9 12
13 ( – ) 14( + ) DC and
and over
over
13 14
(–) (+)

Dimensions (mm)
RH1B-U/RH1B-UL/RH1B-UD/RH1B-ULD RH2B-U/RH2B-UL/RH2B-UD/RH2B-ULD RH3B-U/RH3B-UL/RH3B-UD/RH3B-ULD

Relays & Sockets


Total length from panel surface including relay socket
Total length from panel surface including relay socket Total length from panel surface including relay socket
SH1B-05: 61.5 (63.5) max., SH1B-51: 39.6 (41.6) max.
SH2B-05: 61.5 (63.5) max., SH2B-51: 39.6 (41.6) max. SH3B-05: 61.5 (63.5) max., SH3B-51: 39.6 (41.6) max.
Dimensions in the ( )
include a hold-down spring. Dimensions in the ( ) Dimensions in the ( )
include a hold-down spring. include a hold-down spring.
4.7

ø2.6 hole
ø2.6 hole
4.7

1
ø2.6 hole

4.7
5
1 4
9
27.5

5 8
0.5

0.5

27.5
13 14 9 12

13 14 1 2 4
5 6 8
5.4 14

27.5
0.5
9 10 11

35.6 max. 6.4 21

Timers
35.6 max. 6.4 13 14

35.6 max. 6.4 31

RH4B-U/RH4B-UL/RH4B-UD/RH4B-ULD RH1B-UT RH2B-UT


Total length from panel surface including relay socket
SH4B-05: 61.5 (63.5) max., SH4B-51: 39.6 (41.6) max.
4.7

Dimensions in the ( )

10
include a hold-down spring.
ø2.6 hole
0.5
4.7

ø2.6 hole

Contactors
4.7

4.7
0.5
1
5
1 4
5.9
43.2

27.5

9
38

5 8

5.9
43.2

27.5
38

13 14
9 12

ø2.6 hole 13 14
6.6

7.25
3.5 2 5.4
4.7

14.5 35.6 max. 6.4 3.5 2


1 2 3 4
5 6 7 8 21.5 35.6 max. 6.4
27.5

9 10 11 12
0.5

13 14

35.6 max. 6.4 41

Terminal Blocks
RH3B-UT RH4B-UT
10

10
4.7
10

10
10

3.5 ø2.6 hole


4.7

2 3.5
0.5
4.7

ø2.6 hole
0.5
4.7

Circuit Breakers

1 2 4
1 2 3 4
5.9

5 6 8
43.2
38

28

5.9

5 6 7 8
9 10 12
28
38
44

13 14 9 10 11 12
13 14
7.25
7.25

21.5 2 35.6 max. 6.4 28


31.5 35.6 max. 6.4 42 max. 41.5

1705151135
800-262-IDEC (4332) • USA & Canada 879
RH Relays & Sockets

Dimensions con’t (mm)


Switches & Pilot Lights

RH1V2-U/RH1V2-UD RH2V2-U/RH2V2-UL/RH2V2-UD
8-ø2.4 holes
0.5

4.7
3-ø2.4 holes
2-ø2 holes

7.25
0.5
1.5

4.7
0.5

2
7.15

0.5
1

13.15
5

7.8
1 4

27.5
9

12.5
0.5

5 8

27.5
6.6
13 14
9 12
13 14

5
35.6 max. 4.6 14 10

2
Signaling Lights

35.6 max. 4.6 21


4.4 14.2

RH3V2-U/RH3V2-UL/RH3V2-D RH4V2-U/RH4V2-UL/RH4V2-UD

30
11-ø2.4 holes 10 10

4.7
14-ø2.4 holes 10

4.7
2

13.15
1 2 4

13.15
7.8

5 6 8

7.8
1 2 3 4
27.5
Relays & Sockets

9 10 11 5 6 7 8
0.5

27.5
9 10 11 12

0.5
13 14
13 14
7.25

7.25
0.5 31
0.5 41
35.6 max. 4.6
35.6 max. 4.6

Standard DIN Rail Mount Sockets


SH1B-05 SH2B-05
17 31.5 22 31.5
8 18 DIN Rail Terminal Arrangement 8 M3.5 Terminal 18 DIN Rail
M3.5 Terminal Terminal Arrangement
(BNDN) (BNDN)
Screw 2-ø4.2 Mounting Holes
Screw
5
2-ø4.2 Mounting Holes 8 5
(or M4 Tapped Holes) (or M4 Tapped Holes)
Timers

1
4.2

4 1
4.2

16
67

47

26
67

47

M3 Terminal 5.5 min. 4.8 min. 14 13 4.4 max. 5.5 min. 14 13


Screw 9
4.4 max. 4 max. 12 9
(Top View)
16 14.5 14.5 (Top View)
ø3.6 min. ø3.2 min. 26 7.9 max.
20 25
2.5

2.5

30 25 ø3.6 min.
7.9 max. 5.9 max.

(For terminals 1, 5, and 9) (For terminals 13 and 14)


Contactors

SH3B-05 SH4B-05
31.5 31.5
32 42
8 18 DIN Rail 8 18 DIN Rail
M3.5 Terminal Terminal Arrangement M3.5 Terminal Terminal Arrangement
(BNDN) (BNDN)
Screw Screw
2-ø4.2 Mounting Holes 2-ø4.2 Mounting Holes
8 6 5 8 7 6 5
(or M4 Tapped Holes) (or M4 Tapped Holes)
4.2

4 3 2 1
4.2

4 2 1

46
67

47
67

47

36

4.4 max. 5.5 min. 14 13


4.4 max. 5.5 min. 14 13
12 11 10 9
Terminal Blocks

12 10 9
(Top View)
(Top View) 46 14.5
36 14.5 7.9 max.
7.9 max. 50 25 ø3.6 min.
2.5
2.5

40 25 ø3.6 min.
Circuit Breakers

880 www.IDEC.com 1705151135


Relays & Sockets RH

Dimensions con’t (mm)

Switches & Pilot Lights


Finger-safe DIN Rail Mount Sockets
SH1B-05C SH2B-05C
22 36
30 35.5
6 M3 Terminal DIN Rail 7 M3.5 Terminal 25 DIN Rail
25 Screw
Screw (BNDN) Terminal Arrangement (BNDN) Terminal Arrangement

18 2-ø4.2 Mounting Holes 8 7 6 5


ø5 2-ø4.2 Mounting Holes 8 5
ø5.5
(or M4 Tapped Holes) 4 3 2 1 (or M4 Tapped Holes) 4 1

4.2
4.2

49
69
26
46
64

26
14 13
14 13

Signaling Lights
12 9
12 11 10 9
Ring terminals (Top View) 18.7 Ring terminals (Top View)
26
cannot be used. cannot be used.

1.7
26 18.2 30 29.5
1.6

29
2

SH3B-05C SH4B-05C
32 When using
M3.5 Terminal 36 42 BAA/BAP: 33
7 Screw DIN Rail
25 Terminal Arrangement 7 25
(BNDN)
DIN Rail
8 6 5 (BAA/BAP) Terminal Arrangement
ø5 2-ø4.2 Mounting Holes
4 2 1
(or M4 Tapped Holes) ø5 2-ø4.2 Mounting Holes 8 7 6 5
4.2

Relays & Sockets


(or M4 Tapped Holes) 4 3 2 1

4.2
49
69

36

49
69
14 13 46
12 10 9
14 13

Ring terminals (Top View) 12 11 10 9

36 18.7
cannot be used. Ring type crimping (Top View)
1.7

40 29.5 1.7 46 18.7 terminals cannot be used.


50 29.5

Through Panel Mount Socket


SH1B-51 SH2B-51

Timers
Contactors
SH3B-51 SH4B-51

Terminal Blocks
Circuit Breakers

1705151135
800-262-IDEC (4332) • USA & Canada 881
RH Relays & Sockets

Dimensions con’t (mm)


Switches & Pilot Lights

PCB Mount Sockets


SH1B-62 SH2B-62
Terminal Arrangement 3-ø2.4 holes 6.8 18 min. Terminal Arrangement 2.85 21.5 min.
1 4 15.5

6.95
1 4.4

5.65
5 5 8 10

25.4
4.7
25.4

29

4.7
9 12
31

9
13 14 13 14

11.85

0.3
21.2 3 (Bottom View)
0.3

18

12.5
3 (Bottom View)
11

5.95
11

31 min.*

6.6
2-ø2 holes

29 min.*
15 8-ø2.4 holes
15
Signaling Lights

2
1.5 (Tolerance ±0.1) 2
* 36 min. when using * 34 min. when using (Tolerance 0.1)
12.2 hold-down springs hold-down springs

SH3B-62 SH4B-62
Terminal Arrangement 36 min. Terminal Arrangement 6.85 45 min.
7.35 21.3 1 2 3 4 31.3
1 2 4

6.65
5 6 8 10 10 5 6 7 8 10 10 10

25.4

4.7
31
25.4

4.7

9 10 11 12
31

9 10 12
13 14
13 14

0.3
45 3 (Bottom View)
0.3

36 3 (Bottom View)
6.65
12.5

12.5
Relays & Sockets

11
11
15
6.6

6.6
31 min.*
31 min.*

15 14-ø2.4 holes
11-ø2.4 holes
2
2 39.2 * 36 min. when using
hold-down springs (Tolerance 0.1)
30.2 * 36 min. when using (Tolerance 0.1)
hold-down springs
Timers
Contactors
Terminal Blocks
Circuit Breakers

882 www.IDEC.com 1705151135


Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

IDEC:
RH2B-ULD-DC24V RH1B-ULD-DC24V RH3B-UDC24V RH1B-UAC24V RH1B-UCDC24V RH3B-ULCDC110V
RH4B-ULCAC12V RH2B-UAC220-240V RH1B-ULCAC240V RH1B-UTDC24V RH1B-UTAC12V RH2B-ULAC220-
240V RH3B-UTAC240V RH2B-UAC110-120V RH4B-UAC6V RH2V2-ULAC110-120V RH2B-ULDC48V RH1V2-
UDC6V RH4B-ULAC24V RH1V2-UAC24V RH2B-UAC24V RH3V2-UAC120V RH2V2-UAC110-120V RH3B-
ULDC24V RH1V2-UDC24V RH3V2-UAC12V RH4B-UTAC24V RH2B-UTAC110-120V RH3B-UCDC24V RH1B-
UTAC120V RH3B-ULDC6V RH4B-UDC12V RH4V2-UAC220V RH2B-UTDC100-110V RH1B-UAC6V RH4B-
ULCDC12V RH4B-UAC24V SH2B-05C RH2B-UDC6V RH3B-UDC6V RH2B-ULCDC24V RH3B-ULCDC12V RH3B-
ULAC24V RH3V2-UDC110V RH2B-UTDC24V RH3B-ULDC110V RH2V2-UAC6V RH4V2-UAC6V RH3B-
ULCAC240V RH4V2-ULDC12V RH1B-UCDC6V RH3V2-UDC24V RH1B-ULCAC120V RH4V2-ULAC24V RH4B-
UDC24V RH1B-ULAC24V RH1B-UAC110V RH3V2-UAC24V RH1B-UTAC24V RH3B-UTDC12V RH1B-ULAC110V
RH3B-UTAC120V RH2V2-UAC220-240V RH4B-UCDC6V RH4B-ULCAC24V RH4B-UTAC120V RH3B-UDC12V
RH2V2-UDC48V RH2B-UCDC48V RH2V2-ULAC220-240V RH2B-ULCDC48V RH4V2-UDC12V RH3V2-UDC6V
RH4B-UTDC6V RH1B-ULDC24V RH4B-UCAC12V RH2B-UCDC6V RH3B-UCAC240V SH1B-62 RH3B-UCAC120V
RH2V2-ULDC12V RH3B-UCDC110V RH1B-UDC24V RH1V2-UAC120V RH4V2-UDC48V RH1B-UAC220V
RH2V2-UDC24V RH2B-UCAC220-240V SH2B-51 RH3B-UAC110V RH3B-ULAC220V RH2B-UTAC6V RH2B-
ULCAC12V RH3V2-UAC6V RH4B-ULAC120V RH1B-ULDC48V RH1B-ULCAC12V RH2B-UCAC110-120V RH1V2-
UDC110V RH2B-ULCDC6V

You might also like