This document provides guidelines for fire safety in industrial occupancies such as factories and workshops. It classifies industrial occupancies based on hazard levels and provides requirements for fire detection and suppression systems. Special-purpose industrial occupancies with low hazards and general industrial occupancies with low or ordinary hazards must comply with provisions for unoccupied attic and concealed spaces, fire alarms, portable extinguishers, standpipes, and fire hoses. Additional requirements apply for taller or larger buildings.
This document provides guidelines for fire safety in industrial occupancies such as factories and workshops. It classifies industrial occupancies based on hazard levels and provides requirements for fire detection and suppression systems. Special-purpose industrial occupancies with low hazards and general industrial occupancies with low or ordinary hazards must comply with provisions for unoccupied attic and concealed spaces, fire alarms, portable extinguishers, standpipes, and fire hoses. Additional requirements apply for taller or larger buildings.
This document provides guidelines for fire safety in industrial occupancies such as factories and workshops. It classifies industrial occupancies based on hazard levels and provides requirements for fire detection and suppression systems. Special-purpose industrial occupancies with low hazards and general industrial occupancies with low or ordinary hazards must comply with provisions for unoccupied attic and concealed spaces, fire alarms, portable extinguishers, standpipes, and fire hoses. Additional requirements apply for taller or larger buildings.
GENERAL DIRECTORATE OF CIVIL DEFENCE MINISTRY OF INTERIOR, STATE OF QATAR BUILDING PLAN - FIRE SAFETY GUIDE
I APPLICATIONS INDUSTRIAL OCCUPANCIES - FACTORY AND WORKSHOPS
DRY CLEANING PLANTS / FACTORIES OF ALL KINDS / FOOD PROCESSING PLANTS / GAS PLANTS / AN OCCUPANCY IN WHICH PRODUCTS ARE MANUFACTURED OR IN WHICH PROCESSING, ASSEMBLING, HANGARS (FOR SERVICING/MAINTENANCE) / LAUNDRIES/ POWER PLANTS / PUMPING STATIONS / MIXING, PACKAGING, FINISHING, DECORATING, OR REPAIR OPERATIONS ARE CONDUCTED REFINERIES / SAWMILLS / TELEPHONE EXCHANGES II OCCUPANCY CLASSIFICATION* BUILDING AREA AND HEIGHT REQUIREMENTS A SPECIAL-PURPOSE INDUSTIAL OCCUPANCY LOW AND ORDINARY HAZARD CLASSIFICATION IN ACCORDANCE WITH NFPA 5000 CHAPTER 7 TABLE 7.4.1 FOR THE ALLOWABLE BUILDING HEIGHT AND B GENERAL INDUSTRIAL OCCUPANCY LOW AND ORDINARY HAZARD CLASSIFICATION AREA REQUIREMENTS C HIGH HAZARD INDUSTRIAL OCCUPANCY - D INDUSTRIAL USE CONSIDERED AS LOW HAZARDS: BEVERAGES (NON ALCOHOLIC) / BRICKS & MASONRY / CERAMIC / FOUNDRIES / GLASS PRODUCTS / GYPSUM / ICE / METAL PRODUCTS (FABRICATION & ASSEMBLY / TELECOMMUNICATION SIGNAL PROCESSING / TELEPHONE EXCHANGES
FIRE SAFETY PROVISIONS MINIMUM REQUIREMENTS HIGH HAZARD INDUSTRIAL LOW HAZARD ORDINARY LOW HAZARD ORDINARY UNOCCUPIED ATTIC SPACES DRAFSTOP INTO AREAS NOT EXCEEDING 280M² REQUIRED REQUIRED REQUIRED CONCEALED SPACES (CEILINGS & FLOORS) DRAFSTOP INTO AREAS NOT EXCEEDING 93M² REQUIRED REQUIRED REQUIRED CONCEALED SPACES (FLOORS & ROOFS) DRAFSTOP INTO AREAS NOT EXCEEDING 280M² REQUIRED REQUIRED REQUIRED VII FIRE PROTECTION NR-NOT REQUIRED / R-REQUIRED A DETECTION ALARM AND COMMUNICATION SYSTEMS 1 FIRE ALARM SYSTEM COMPLYING WITH NFPA 72 REQUIRED REQUIRED REQUIRED B EXTINGUISHING REQUIREMENTS 1 PORTABLE FIRE EXTINGUISHERS TYPE AND RATING IN ACCORDANCE WITH NFPA 10 REQUIRED REQUIRED REQUIRED 2 FIRE BLANKETS IN KITCHEN OR PANTRY REQUIRED REQUIRED REQUIRED 3 STANDPIPE SYSTEM COMPLYING WITH NFPA 14 REQUIRED REQUIRED REQUIRED 4 FIRE HOSE REELS 25MM DIAMETER HOSE REQUIRED REQUIRED REQUIRED 3 OR MORE STOREYS IN HEIGHT NR R NR R REQUIRED FIRE AREA EXCEEDING 1115M² NR R NR R REQUIRED 5 AUTOMATIC SPRINKLER SYSTEM TOTAL AREA OF ALL FLOORS EXCEEDS 2230M² NR R NR R REQUIRED WOODWORKING OPERATIONS EXCEEDING 232M² REQUIRED REQUIRED REQUIRED POWER GENERATION BUILDING REQUIRED REQUIRED REQUIRED INDUSTRIAL OCCUPANCY – FACTORY/WORKSHOP – Revisions_2015 Page 13 of 17