You are on page 1of 3

INTERNAL FIRE SAFETY AUDIT PRELIMINARY REPORT

LOCATION FINDINGS/OBSERVATION RECOMENDATION


SMOKING AREA BUCKET MIXED WITH VARIOUS TO PROVIDE BUCKET WITH SAND FOR
COMBUSTIBLE MATERIALS EXTINGUISH THE CIGERETTE BUDS
NO SIGN BOARDS PROVIDED TO PROVIDE SIGN BOARDS LIKE
PLEASE EXTINGUISH THE BUDS AFTER
YOU SMOKE, DO NOT PUT CIGERETTE
PACKET INSIDE THE BUCKET ETC...
FIRE EXTINGUISHER NOT PROVIDED PROVIDE FIRE EXTINGUISHER IN
SMOKING AREA, FOR ADDITIONAL
PRECAUTION PROVIDE FIRE BLANKET
ON THE SMOKING SHELTER AND
MAINTAIN AREA CLEAR FROM
COMBUSTIBLE OR FLAMMABLE
MATERIALS.
TOILET FIRE EXTINGUISHER PROVIDED, BUT CHANGE THE FIRE EXTINGUISHER
DOUBT FUL WORKING CONDITION. AND PROVIDE NEW ONE.
NO SMOKE DETECTOR PROVIDED TO PROVIDE SMOKE DETECTOR
INSIDE THE TOILET
SURROUNDING AREA MIXED WITH REMOVE ALL COMBUSTIBLE
COMBUSTIBLE MATERIALS AND THAT MATERIALS NEAR FROM THE
AREA DESIGNATED FOR FABRICATION PROTABLE CABIN AND AVOID HOT
WORKS LIKE CUTTING OF STEEL BARS WORKS THERE IF POSSIBLE, IT CAN
TRANSFER HEAT TO PORTABLE CABIN
FABRICATION YARDS COMBUSTIBLE AND FLAMMABLE REMOVE ALL COMBUSTIBLE AND
MATERIALS FOUND NEAR AND INSIDE FLAMMABLE MATERIALS NEAR THE
THE FABRICATION WORKSHOP. NET WORKING AREA. REMOVE NET FROM
LAID OVER THE SAND AND TOO CLOSE THERE THIS IS VERY CLOSE TO THE
TOO CLOSE TO THE HOT WORK AREA. HOT WORK AREA.

NO PROPER ACCESS PROVIDED FOR TO PROVIDE ACCESS/EGRESS FOR


EMERFGENCY EVACUATION THE FABRICATION WORKERS. THIS IS
VIOLATION OF COMPANY ERP
PROCEDURE.
DB PROVIDED TOO CLOSE TO THE HOT CHANGE THE DB FROM PRESENT
WORKING AREA, DOING WELDING AND LOCATION AND ANOTHER AREA OF
CUTTING VERY NEAR TO THE DB AND THE WORK SHOP WHERE IT IS SAFE
COVER NOT PROVIDED FROM THE HEAT AND FIRE
ADEQUATE FIRE EXTINGUISHERS NOT TO PROVIDE ADEQUATE NUMBER OF
PROVIDED FIRE EXTINGUISHERS
USING SUBSTANDARD EXTENSION TO PROVIDE STANDARD
CORDS AND PLUGS USING FOR THE CABLES ,PLUGS, AND SOCKETS
WORK AND BYPASSING FUSES ON PLUG INDUSTRIAL TYPE AND MAKE SURE
FOR THE ELECTRIC ARC WELDING ALL THE CONNECTION ARE THROUGH
MACHINE GFCI/ELCB AND THERE IS APPRPRIATE
RATING BETWEEN EQUIPMENTS AND
EXTENSION CORDS.
NO FIRE BLANKET AVAILABLE TO PROVIDE FIRE BLANKET WITH
ADEQUATE NUMBER
GAS CYLINDER CYLINDERS ARE NOT FASTENED AGAINST TO PROVIDE CHAIN OR EQUIVILANT
STORAGE AREA FALLING HAZARDS MEANS FOR CYLINDERS TO SECURE
CYLINDERS FROM FALLING
ACCIDENTS
ACCETYLENE AND OXYGEN CYLINDERS TO STACK CYLINDERS SEPERATELY
ARE COMBINE TOGETHER WITH OUT SUCH AS OXYGEN AND ACCETYLENE
CAPS, AND EMPTY CYLINDERS ARE AND EMPTY FUEL CYLINDERS. TO
MIXED WITH FULL CYLINDERS.NO PROVIDE ADEQUATE SPACE FOR THE
ADEQUATE SPACE AVAILABLE FOR THE STORAGE CYLINDERS, PROVIDE CAP
STORAGE CYLINDERS AND THERE IS NO FOR ALL CYLINDERS. TO PROVIDE
SAFE ACCESS/EGRESS FOR HANDLING OF SAFE ACCESS BETWEEN
GAS CYLINDERS. NO SIGN BOARDS FABRIACATION YARD AND CYLINDER
AVAILABLE SUCH AS SAFE HANDLING OF STORAGE AREA AS WELL INFRONT OF
GAS CYLINDERS, AND STORAGE CYLINDER STORAGE AREA. REMOVE
PROCEDURE ALL UNWANTED MATERIALS FROM
SURROUNDING OF GAS CYLINDER
STORAGE AREA. PROVIDE SIGN
BOARDS.
A/C WORK SHOP CYLINDERS WITHOUT FASTENING AND PROVIDE ONE AREA FOR STORAGE OF
CAPS AND AREA NOT SEPARATED FOR CYLINDERS AND STACK SEPERATELY
CYLINDER STORAGE AND FASTEN ALL CYLINDERS TO
PREVENT FALLING HAZARSDS.
USING BROCKEN ELECTRICAL SOCKETS PROVIDE ADEQUATE NUMBER OF
FOR THE EXTENSION AND LAID ON THE INDUSTRIAL SOCKETS AND PLUGS
GROUND AND MIXED WITH FOR ALL WORK SHOPS AND
COMBUSTIBLE MATERIALS, MAINTAIN GOOD HOUSEKEEPING
HOUSEKEEPING NOT SATISAFACTORILY INSIDE THE WORKSHOPS
NO EASY ACCESSIBILITY TO REACH THE PROVIDE ADEQAUTE NUMBER OF
FIRE EXTINGUISHER FIRE EXTINGUISHERS AND REMOVE
ALL ONSTRUCTION THAT MAY CAUSE
UNEASY FOR THE HANDLING AND
USAGE OF FIRE EXTINGUISHERS IN
THE A/C WORK SHOP
STORE II SEPARATE STORAGE AREA NOT PROVIDE AREA FOR STORAGE AND
PROVIDED FOR THE CORROSSIVE HANDLING OF CHEMICALS ONLY.
CHEMICALS, IT IS ALSO STORED WITH THIS SHOULD BE IN WELL
COMBUSTIBLE MATERIALS. VENTILATED AREA AND PROVIDE
SIGN BOARDS FOR ALL CHEMICAL
THAT WILL HELP TO EMPLOYEES TO
WARN OF ITS POTENTIAL HAZARDS.
IMPROPER STORAGE OF MATERIALS TO STACK MATERIALS PROPERLY, ALL
AND NO PROPER ACCESS BULK/HEAVY OBJECTS ALWAYS KEEP
IN THE BOTTOM AND PROVIDE
ADEQUATE VENTILATION AND
ACCESS FOR THE STORAGE AREA
PAINTING NO EAZY ACCESSIBILITY TO REACH THE PROVIDE ADEQAUTE NUMBER OF
WORKSHOP FIRE EXTINGUISHER FIRE EXTINGUISHERS AND REMOVE
ALL ONSTRUCTION THAT MAY CAUSE
UNEASY FOR THE HANDLING AND
USAGE OF FIRE EXTINGUISHERS IN
THE PAINTING WORK SHOP
NO SIGN BOARDS PROVIDE SIGN BOARDS TO BE
PROVIDED FOR HANDLING AND
STORAGE OF PAINTS.
YARD AREA HOUSE KEEPING ALL UNWANTED/ COMBUSTIBLE
MATERIALS TO BE REMOVED
FROM/NEAR THE GENERATOR YARD
AND OTHER HEAT EMITING
EQUIPMENTS WHERE USED, AND
STACK MATERIALS PROPERLY,
PROVIDE ONE AREA FOR STORAGE OF
ALL OTHER EQUIPMENTS

NOTE: TO PROVIDE SMOKE DETECTORS FOR ALL PORTABLE CABINS AND ALL ELECTRICAL CABLES AND
EQUIPMENTS NEED TO BE INSPECT BY ELECTICIAL TECHNITION.