You are on page 1of 9

1 2 3 4 5 6 7 8

201

F3(1P4A)
200
D D
PT
Running Contactor Motor
Q Main Power Switch KJT Main Control Contactor KDY
U1 R U3
L1 2 1 U 1 2
R
KDY V3
L2 V1 4 3 S V 3 4
S
KDY W3
L3 W1 6 5 T W 5 6
T

NICE1000
KDY in-built

+5V 9 +5V
0V 7 0V
A+ 5 A+
A- 6 A-
C UPC B+ 8 B+ C
1 2
B- 1 B-
L21 NI NO
C+ PG
UPS C+ 10
3 4 C-
L31 LI LO C- 11
D+ 12 D+
PE D-
D- 13
5 6 BK3
Z+ 3 R+
Z- 4 R-
53 54 HEIDENHAIN 1387
UPC/72

83 84
UPC/62

Braking Resistor

Brake-release Contactor
21
P(+)
Emergency Contactor

B KJT B
22
RZD
For UPS emergency running A2 A2 PB
UPC KYJ
A1 A1

Brake-release Button SZ1


KUP Manual
For electric brake-release
Automatic Y0

MCB

M0

A A
Design 钱建强 Draw No. TRM510
Check Sheets 5
Approve 潘伟荣 Main Circuit Sheet 1B
Date 2008.11.1 Remark Monarch + Synchronous

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

U1 V1 W1

Control Power Breaker


D D
F1(3P6A)
Brake Contactor
Counter
KLZ
6 5
CNT

Brake-release Contactor Brake-release Button SZ2 Brake-release Contactor


KYJ To be conneted when there is an electric brake-release device KYJ
Phase Protection Relay 2 1 3 4 4 3

KXX

Door Lock Relay Running Contactor Brake Contactor Brake Contactor


Applicable for UPS Running
61 KMB KDY KLZ KLZ
71 BK1 Brake BK2
UPC UPC 1 2 44 43 2 1 4 3
LZ
62 72

D1 RLZ

TC1 Control Power Transformer F4(1P4A) Applicable when there is no brake discharge
103(+) circuit on traction machine
C C
AC220V +
DC110V/3A 102(-)
Brake: DC110V
To main control board CN3

AC0V AC110V -

101
A2 A2
XMC
KMB KJT 100a
A1 A1
21
UPC Safety Circuit F2(1P2A) To be connected when there is electric brake-release device
22 Brake-release Contactor Brake-release Button SZ2 Brake-release Contactor
21 KYJ KYJ
To main control board CN3

To be connected when there KYJ 2 1 3 4 4 3


is brake-release device22
11
To main cotnrol board CN3
KXXPhase Relay
X27 100
118 14
For UPS emergency running
116 Door Lock Relay Running Contactor Brake Contactor Brake Contactor
X25 SDT F5(1P4A)
T KMB KDY KLZ BK1 BK2 KLZ BK3 R
2 44 43 2 1 4 3 UPC 31
SMJ SJT Emergency Stop in M.R. Emergency Stop on Car Top 1 LZ 32
B SM1 B

Landing Door F1 Car Door Switch 105


117
115a
SDC
Emergency Stop in Car
SM2 X26 SPS Handwheel Switch
To main control board CN3 Brake: AC220V
Landing Door F2
SMn 110 106
115
Landing Door Fn
SM3 GJ
Emergency Electric Running
DJ
Inspection
SKT
Emergency Stop in Pit
SMn-1 Note: Brake circuit voltage of synchronous traction machine is according to the practice.
SCS Up Running Overspeed Switch

114a
SKS Rope Breakage Switch
SMn-2
SXS Governor Switch
111
Door Interlock 114 24V V+ C1 5
SNQ Safety Gear Switch
LCD Counter KLZ
A 6 A
SSJ Top Final Limit GND1 V- C2 Design 钱建强 Draw No. TRM510
108 Check Sheets 5
113
Approve Main Circuit
潘伟荣 Sheet 2
SXJ Bottom Final Limit
SHC Buffer Switch Date 2008.11.1 Remark Door Lock, Safety, Brake
109

1 2 3 4 5 6 7 8
B
C

A
D

+24V
GND1

1
1

Emergency Electric Operation

129
GJ
3

X4
130
2

Jog Up
ES1

138
1
S1

X5
HF70W-D

3
L13 118

DJ
+24V 200

FMG
M1 24V L

139
SH1

FMS FMX
2

Jog Down
1
24V+

X6
COM in M.R.
101 Power Unit
M2 201
ES2 S2 GND1

5
COM N
24V-

L14

KMB
SH2

2
2

KLZ Brake Contactor

Car Top InspectionDMG


A2 A1

COM on Car Top


Y1

DMS DMX
ES3 S3
L15 SMQ KDY Running Contactor

Jog up on car top Jog down on car top


SH3 125 门区 A2 A1 EN1
X1 Y2 N1
L5
KDY Car Call 1 SN1
31 32 Running Contactor
ES4
X2
S4
L16 KLZ KM1 Door Open 1 EN2
43 44 Brake Contactor Car Call 2 N2
SH4 X3 Y6 L6
SXF SN2
127

3
3

Fireman Switch GM1 Door Close 1


X7 Y7
ES5 S5 CXF EN3
L11 Car Call 3 N3
For Fire Emergency Interaction
KM2 Door Open 2 L7
SH5 Y8
SDF SN3
128
X8 Electric Lock (locked when it is open)
GM2 Door Close 2
EX2 X2 Y9 EN4
Car Call 4 N4
L17 Top Limit L8
121 SXV 121a SXV1 Inspection Top Limit CM1 COM
XH2 X9
YM1 SN4
Limit
122Bottom
XXV
122b XXV1 Inspection Bottom Limit
X10 EN5
EX3 X3 Car Call 5 N5
L18 L9

4
4

123 SDZ Top Terminal a


XH3 X11 Y10 SN5
b
124 Y11
XDZ Bottom Terminal EN6
X12 c
EX4 Y12 Car Call 6 N6
X4 L10
L19
145 SCZ Overload Switch SN6
XH4

NICE1000
X13

146 SBZ Half-load Switch JX


EX5 X5 X14 Y16
L20
BCD code indicator (com"-")

SZH -
Y19
NICE1000

XH5
-
+

150 By attendant when it is open

5
5

X15 Door Open 1 SKM1


152
EX6
L1
+24V

X6
L12 SGM1
132 KMV1 Door Open Limit 1
Door Close 1153
XH6 X16 ES L2
Up Direction
Y17
133 45
GMV1Door Close Limit 1 EXDown Direction
X17
Y18
46
134 KAB1 Safety Edge 1
X18 BEL arrival gong
BL1
Y20
137 KAB2 Safety Edge 2 Door Opening Holding
Black

X19

6
6

Yellow
Red

154 EY
135 KMV2 Door Open Limit 2
L3
X20
Date

SKY
+24V

Check
Design

136
Approve

X21 GMV2 Door Close Limit 2


FMQ
KBK KBK1 Brake Detecting 1 Buzz 44
X22
Y21
钱建强

KBK2 Brake Detecting 2 ECZ Overload Light

47
Y22
7
7

13 14
KXFL
UPC Fireman Interaction
14
14 13
13 Y15
X23 KJT KXFL
YM2

Emergency Contactor Detecting LD1 LD2


5 9

3 4
Input & Output

X24 KMB
YM3

Door Lock Contactor Detecting 14 13


+24V Y3
24V KZM
M3

Car Light Relay


Sheet
Remark
Sheets
+24V

GND1

GND1

8
8

43 44
X19
UPC UPS Running Signal
3
5
Draw No. TRM511
running without rear door
B
C

A
D

Applicable for emergency running


1 2 3 4 5 6 7 8

D D

U5 U6

V5 Motor V6 Motor
Motor Motor
W5 W6

200 200
Power
201
Power
C 201 C

VVVF Door Operator VVVF Door Operator

Door Open Limit 132 Door Open Limit 135

Door Close Limit 133 Door Close Limit 136

COM for Output +24V COM +24V

KM1 KM2
Door Open Signal Door Open Signal

GM1 GM2
Door Close Signal
Door Close Signal

CM1 CM1
COM
COM for Input

B Main Door Sub-door B

A A
Design 钱建强 Draw No. TRM511
Check Sheets 5
Approve Door Circuit
潘伟荣 Sheet 4
Date Remark

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

L31 L21
Car Light Switch
SDM L311 Car Light EDM
D D
Car lighting Socket XD
201 Remote Governor Release Device
Pit Light Switch
SKK L312
200 Pit Light EKM

FXS Pit Lighting Socket XK

XS2 Control Cabinet Socket XJ


XS1 3
KZM
11
Car Top Light Switch
L33 Car Light
Governor Reset SDM EM
Governor Action EM1

Note: For MRL Elevator EM2


Car Top Light Switch
C SDM FA Car Fan C
FAN

Fan
FAR

For floor no. >6

Q Q1 L31
L3

Lighting electrical leakage protection switch 10A Car Light Breaker (1P4A)
L2 L21
(Safety 5-party intercom)

Emergency Power Box Intercom (M.R.) Intercom on Car Top Intercom in Pit Intercom in Guard Room Q2
Car Intercom
L32
Alarm Emergency LightIntercom
AC220V + - + - + - + - R L + - R L + - R L + - R L Red Black Yellow Blue Shaft Light Breaker (1P10A)
B B
P+ P- L21
Alarm

Call
EYJ

P2+ P2- R
JL2

SJL
JL1
L32 Shaft Light Switch (M.R.) Shaft Light Switch (Pit) L21
SZMf L32A SZMk ECM1
L31 L21
AC220V Shaft Light

L32B ECMn
L35
Shaft lighting by others

A A
Design 钱建强 Draw No. TRM511
Lighting
Check Sheets 5
Approve Circuit
潘伟荣 Sheet 5
Date Remark

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

200

Top Final Limit Switch SSJ

D 100 D

Top Limit Switch SSV

Top Terminal Switch SSD *1

200
Bottom Final Limit Switch SXJ

Bottom Limit Switch SXV


100
C C

Bottom Sub-Terminal Switch

Bottom Terminal Switch SXD


*1

Leveling Position

Leveling Zone Switch MQ Cabin


SMQ
(Unit:mm)
Shelter board
200

UP DOWN
B B

Hoistway learning must be done before elevator high-speed running.


Elevator must have the following conditions before hoistway learning:
1.Top /Bottom limit switch , Top/Bottom terminal switch are installed and wired correctly. Speed
2.Upper/ Lower leveling zone switch and shelter boards on every floor are installed and wired correctly. Item 0.3m/s 0.4m/s
3.Safety circuit and door interlock circuit are normal. *1 500 650
4.General parameters and running parameters are set properly.
5.Elevator can run in inspection mode normally.

A A
Design 钱建强 Draw No. TRM511
Check Sheets 4
Approve Hoistway Signal
Sheet 1
Date Remark

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Power Motor

D L1 L2 L3 U3 V3 W3 D

Terminals in Control Cabinet


L31 L32 L33 L21 44 45 46 47 100 102 103 BK1 BK2 106 108 109 110 111 113 114 115 116 117 118 121 122 123 124 125 126 127 128 130 132 133 134 138 139 145 146

150 151 152 153 200 201 +24VGND1 BL1 CM1 KM GM a b c d 检修 - N1 N8 S1 S7 X2 X8

135 136 137 GM2KM2 P2+ P2- R

C C

Note: when there is no hand-wheel Switch


Power Supply Cable (3 phase, 4 wires)

Jump the terminals 115 and 115a


PE L1 L2 L3 Brake Cable Traction Machine Cable

Traveling Cable Hoistway Cable

Motor Thermal Switch


Hand-wheel Switch
Up Overspeed Switch
BK2 R
P2+ P2- U3 V3 W3
115 115a + - R
LZ
Intercom
SCS SPS M1
BK1
114a 115 ~
B B
SXS Motor

Speed Gov. Switch


114
PG To inverter PG-B2 card
Encoder

A A
Design 钱建强 Draw No. TRM511
Check Machine Room Sheets 4
Approve Circuit Sheet 2
Date Remark

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

COP
Inspection Box on Car Top
a
a L21 130 110 100
b
D b 45 D
c S DMS DMX DJ SDT
c Traveling Cable XD
46
X
GND1
JX - L31 138 139
Inspection
- + +24V 24V 111 105
-

L31 L33 L21 44 45 46 47 100 106 108 110 111 116 117 125 126 130 132 133 134 138 139 145 146 151 152 153 200
N1 EN1
+24v
To be connected when there is rear door
201 CM1 KM GM BL1 a b c d JX - 135 136 137 CM1KM2 GM2
Nn ENn COP Cable

C C

47 ECZ
N1 Nn +24V GND1 P2+ P2- R

Car Lighting Cable


Bistable Switch Cable
Weighing Device Cable
FAN
N1 SN1 GND1
L33 L21
Fan Cable

SNn SNQ
Nn
SMQ
L33 EM1 L21 Safety Gear Cable 108 111
P1 (+)
Emergency Lighting

Emergency Light Alarm SMZ


HJ
SKM1 L31 DC12V P1- JL2 P3+
Input 125 GND1
152 146 GND1 +24V EM2 STAB
Power
L21 P2 (+) Safety Edge Cable 134 24V
SGM1 AC220V Intercom Arrival Gong Cable
153 DC12V P2-
B SCZ B

+24v BL1 GND1 145 GND1


44 HL P3 (+)
Alarm Red Yellow Black
DC12V P3- JL1 BEL
VVVF Door Operator Cable Optional

Car Door Lock Cable


EYJ
P1+ P1- CM1
200 201 132 133 GND1 GM KM

Door Open Limit


SMJ
Power COM Door Close Signal COM
PE Door Close Limit Door Open Signal

VVV Door Operator 116 117


SJL P2+ P2- R
JL2 JL1
+ - R
Intercom

A A
Design 钱建强 Draw No. TRM511
Check Sheets 4
Approve Car Circuit
Sheet 3
Date Remark

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

a
a
b
b 45
c
c
HOP on Top Floor
46

GND1 SSJ
D
Cable for Top Final Limit SMn D
+24V Cable for Landing Door Lock Hoistway Lighting
113 114
MSn-1 116
JX
- Inspection
- SXV ECMm1
Cable for Top Limit
SMn-1 L35
EXn 121 121a Cable for Landing Door Lock L21
+24V
MSn-2 MSn-1
XHn
Xn GND1 SXV1 ECMm
Inspection Cable for Top Limit
121a GND1 L21 L35

a SDZ
Cable for Top Terminal
a
b 123 GND1
b 45
c
c
C 46 SM1
C
XDZ
Cable for Bottom Terminal
HOP on Middle Floors

GND1 118 MS1


124 GND1
+24V Cable for Landing Door Lock

JX Inspection
- - XXV1
Inspection Cable for Bottom Limit
122a GND1
S(n-1) ES(n-1) +24V

ECM1
SH(n-1) GND1
Cable for Bottom LimitXXV SKT L21 L35
106 111a
X(n-1) EX(n-1) +24V 122 122a

L31 XK L21
XH(n-1) GND1
SXJ

Inspection Box in Pit


B Cable for Bottom Final Limit Hoistway Light Switch (Pit) B

108 109 L32A SZMk


L35

SKK
a L31 L312
a Fireman Switch on Main Floor
b L32B
b 45
c 127 GND1 EKM
c L312 L21
46
P2+
GND1 +
P2-
HOP on Main Floor

+24V - Intercom
SKS R
JX Inspection R
Cable for Tension Pulley
- -
111 111a
ES1 +24V
S1
A A
Design 钱建强 Draw No. TRM511
SH1 GND1 SHC SHC1 Check Hoistway Sheets 4
Approve Circuit
113 113a 109 Sheet 4
128 SDS +24V
Cable for Buffer Switch Date Remark

1 2 3 4 5 6 7 8