You are on page 1of 6

01

20' 20'
5'-3"

3'
WASHING AREA DUCT
DUCT ABOVE 3'-3" 3'-3"
8'-3"X3'-3"
5'-3"X3'-3"
BED BED
9' 10'-5"X9'-0" 9' 10'-5"X9'-0"

8'-3"
10'-5" 10'-5"
KITCHEN KITCHEN
3' 3'
8'-3"X12'-7" 8'-3"X12'-7"
3' 3'-9" 12'-7" 3' 3'-9" 12'-7"
DUCT TOILET DUCT TOILET
3'-3" 3'-3"
3 FEET WIDE

3'0"X3'3" 3'9"X3'3" 3'0"X3'3" 3'9"X3'3"


PASSAGE
8'-3" 11'-7"
2'-6" 2'-6"
DINING
BATH 6" BATH FREE SPACE 6"
30' 3'-3" 4'3"X3'3" 30' 3'-3" 4'3"X3'3"
4'-3" 4" 4'-3" 4"
3'-3" 3'-3"
3' UP 3' UP

HALL 10" HALL


12'-2"X9'-6" 9'-6" 9'-6" 12'-2"X9'-6"
6'-6"

3'-3"
3'-3"
12'-2" 12'-2"
3'
6" Riser=7" 6"
Tread=10" 3' BALCONY 3'
3' 12'5"x3' 3'
3' WIDE ENTRY Floor Ht.=10'6" 6'-6"
6'-8" 3'

GROUND FLOOR PLAN FIRST FLOOR PLAN

M A I N R O A D M A I N R O A D

N PROPOSED BUNGALOW AT AURANGABAD DATE: 19.07.2023 : R1


C10 C11
150x380 150x450 02
30' 20'
3"
29'-9"

3'-9"
4'-3"
C9
25'-6" 150x450

4'-7" C8
1" 150x450
12
20'-11"
1"
20'-92 C7
150x380 1"
32'-42
1"
7'-22

C4 1" C5
13'-7" 29'-22 30'
6" 150x450 150x530
13'-1"
6" C6
150x450
12'-7"

8'-10"

C1
3'-9" 150x450
1"
12
1"
3'-72
C2 C3
150x450 150x380
1"
3'-72 3'

6'-10"
0" 3" 1
42" 1"
10'-02 1"
1'-12
3"
6" 1"
72
origin
0.00
1"
72
0"

3"

10'-8"

11'-2"

1"

19'-9"
20'
12'-11"
12'-32

TILTLE OF SHEET: CENTER LINE PLAN

TILTLE OF PROJECT: PROPOSED RESIDENTIAL BUILDING


AT AURANGABAD

DATE: 20/07/2023 : R0
C10 C11 03
150x380 150x450 SCHEDULE OF COLUMN DESIGN FOR G+2 = 3 SLAB [ M20 GRADE OF CONCRETE ]

SIZE STEEL LATERAL TIES / CONFINED R/F


1500 1600 COLUMN
COLUMN NOS. SHAPE & ARRANGEMENT OF TIES
GROUP AT SUPPORT END L/4 AT MIDDEL PORTION
1200 1300 B D NOS. - DIA

1300
F1 C9 CG1 06 - 12 dia 6 dia @ 125 mm c/c 6 dia @ 150 mm c/c
+
F2 C3,C7,C10 150 380

1600
150x450 Alternate ring details

C1,C2,C4,C6,C8,C9,C11 +
CG2 150 450 08 - 12 dia 6 dia @ 125 mm c/c 6 dia @ 150 mm c/c

F2
1200 Alternate ring details
1200

C5 +
CG3 150 530 08 - 12 dia 8 dia @ 125 mm c/c 8 dia @ 150 mm c/c
Alternate ring details
1600
1500

C7
150x380 C8 SCHEDULE OF FOOTING DESIGN FOR G+2 = 3 SLAB [ M20 GRADE OF CONCRETE ]
F3
F1

150x450 AT BOTTOM FACE AT TOP FACE


FOOTING COLUMN NOS. PCC/PIT SIZE RCC SIZE DEPTH TYPE OF
STEEL ALONG STEEL ALONG STEEL ALONG STEEL ALONG
GROUP ( L1 X B1 ) (LXB) (D) FOOTING
SHORTER DIRECTION LONGER DIRECTION SHORTER DIRECTION LONGER DIRECTION
1300
F1 C3,C7,C10 1700 x 1400 1500 x 1200 400 10 mm @ 150 mm c/c 10 mm @ 175 mm c/c 10 mm @ 150 mm c/c 10 mm @ 175 mm c/c BOX FOOTING
1300

1600
1600

F2 C1,C4,C6,C9,C11 1800 x 1500 1600 x 1300 450 10 mm @ 150 mm c/c 10 mm @ 175 mm c/c 10 mm @ 150 mm c/c 10 mm @ 175 mm c/c BOX FOOTING
1200
1600

C4 C5 C6
F2

150x450 F3 150x530 150x450 F3 C2,C5,C8 1800 x 1400 1600 x 1200 400 10 mm @ 125 mm c/c 10 mm @ 125 mm c/c - - BOX FOOTING
F2

NOTE: FOUNDATION IS DESIGNED AS PER S.B.C. 275 kN/m2, MUST BE CHECKED AND VERIFIED AT SITE BEFORE EXECUTION THROUGH SOIL INVESTIGATION.

IMPORTANT NOTES :-
GL 1. All work shall be strictly executed as per the drawing.
2. Structure is designed for G+2 (3 SLABS) only.
Column Main steel as 3. Concrete Grade M20 and Steel Fe500 shall be used.
1300

1200

1200

Chimta bars

UP TO HARD STRATA
4. Load of Red Bricks for partition walls are considered for design.
First Link Position 5. Take permission from structural engineer before concreting at site.

(Min. 1.50m)

150
6. Clear Cover to R/F bars shall be -Footings 50mm, Column 40mm ,
1600

1600

1500

C1 C2 C3 At top Beams 30mm, Slab 25mm.


3 Nos 12 dia 7. Developement/Lap length shall be used
150x450 150x450 150x380 400mm Total Depth(D)

100 mm as 50 times dia of bar.


F1
F2

F3

8. Stripping time of formwork Shall be as per I.S.456-2000.


P.C.C. = 100 mm Thk.(M15 Grade 1:2:4)
9. False work/ Shuttering Stability is responsibility of contractor.
Steel R/F both ways at Bottom D 10. Live load considered over these slab is 2.0 kN/m2
TYP. SECTION OF BOX FOOTING 450 11. If any Special Loads are there kindly inform to
100mm
PCC 100mm structural engineer before applying.
12. Any descripency shall be asked and discussed to
Structural Engineer.
13. Structure is design for Gravity Load Only.
STRUCTURAL LAYOUT OF COLUMNS & FOOTINGS Main steel as 14.Do not change or alter structural drawing.
Chimta bars Distribution 3 Nos 12 dia
Along Short steel at Bottom
PCC
Along long
PROJECTION
CONSTRUCTION NOTE:-

L
1. CHECK THE CENTERING OF COLUMN / SLAB / BEAM / STAIRCASE
BEFORE PLACING THE REINFORCEMENT IN PLACE.
Development Length (Ld=50*d) : RCC PCC 2. REFER ARCHITECTURE DRAWING ONLY
PROJECTION PROJECTION FOR LEVELS,DIMENSION,ETC.
BAR DIAMETER MIN. LAP LENGTH 3. REFER R.C.C. DRAWING FOR MEMBER SIZES AND STEEL
REINFORCEMENT SECTION.
10 mm 500 mm 100mm

L
ALL ARROUND 4. OUR RESPONSIBILITY WILL BE LIMITED TO SAFE AND STABLE
RCC
12 mm 600 mm PROJECTION
STRUCTURAL DESIGN ONLY, WE HAVE NO ANY CONCERN WITH
B CONSTRUCTION PERMISSION AND LEGAL ISSUES.
16 mm 800 mm 100mm
TYPICAL RING / STIRRUP TYP. PLAN OF BOX FOOTING
20 mm 1000 mm
STRUCTURAL DETAILS OF
B TILTLE OF SHEET:
COLUMNS & FOOTINGS
PLAN OF ONE SIDE BOX FOOTING
TILTLE OF PROJECT: PROPOSED RESIDENTIAL BUILDING
AT AURANGABAD

DATE: 20/07/2023 : R0
C11
SCHEDULE OF GROUND & PLINTH BEAMS. M20 GRADE OF CONCRETE

Beam Size Straight Straight Curtail Bar Extra Top Legged Stirrups Stirrups
04
C10 Remark
150x450 Group BxD Top Bar Bottom Bar Middle 0.65*L Ends L/4 of stirups End zone L/4 Middle Half
150x380 B4 B2
B0 150 X 380 2 - 10 Dia 2 - 10 Dia --- --- 2-Legged 6 dia - 150mm c/c 6 dia - 150mm c/c beam

BR1
3'-3" B1 150 X 380 2 - 10 Dia 2 - 12 Dia 1 - 12 Dia --- 2-Legged 6 dia - 150mm c/c 6 dia - 200mm c/c beam

C9 B2 150 X 380 2 - 10 Dia 2 - 12 Dia --- 1 - 12 Dia 2-Legged 6 dia - 150mm c/c 6 dia - 200mm c/c beam
150x450
B4

B5
8'-10" B2 B3 150 X 380 2 - 10 Dia 2 - 12 Dia 1 - 12 Dia 1 - 12 Dia 2-Legged 6 dia - 150mm c/c 6 dia - 200mm c/c beam
10'-5" 8'-1" B4 150 X 450 2 - 10 Dia 2 - 12 Dia 1 - 10 Dia 2 - 12 Dia 2-Legged 6 dia - 150mm c/c 6 dia - 175mm c/c beam

B5 150 X 450 2 - 12 Dia 2 - 12 Dia 2 - 12 Dia 2 - 12 Dia 2-Legged 6 dia - 150mm c/c 6 dia - 175mm c/c beam
C7 B5 C8
150x380 B6 150 X 450 2 - 10 Dia 2 - 12 Dia 1 - 10 Dia 2 - 12 Dia 2-Legged 6 dia - 150mm c/c 6 dia - 175mm c/c beam

B6
150x450
3' 3'-5" 12'-5"
beam
B0

Open 3'-1" B7 150 X 450 2 - 12 Dia 3 - 12 Dia 1 - 12 Dia 2 - 12 Dia 2-Legged 6 dia - 150mm c/c 6 dia - 175mm c/c
B1 3' BR1 150 X 450 4 - 12 Dia 2 - 12 Dia --- --- 2-Legged 6 dia - 100mm c/c 6 dia - 100mm c/c bracket
B3
B5

B3

4'-1" BR2 150 X 450 4 - 12 Dia 2 - 12 Dia --- --- 2-Legged 6 dia - 100mm c/c 6 dia - 100mm c/c bracket
3'-3"
B0

B4
C4
150x450 B7 C6
C5 End bent to All
150x450
150x530 Top,Bottom & Continue
Extra Top Bars extra top
12'-2" (d=depth of beam) Column links at
Ld=Development upto L/4
end zone stirrups Rest span column-beam junction are necessary
Length ( L/4 ) stirrups (Middle zone)
B6
B4

B4

9'-4" Ld= 42xbar dia.

50mm max Curtail Bar


C1 B5 C3 anchorage pins First stirrup Position at Middle 0.65L At intermediate beam junctions TYPICAL RING / STIRRUP
16mmØ Continue Top & Bottom bars as per
150x450 150x380 L=Length of Beam
development Length(Ld) criteria
C2 Development Length (Ld=50*d) :
BR1
BR2

Column Column
BR1

3' 150x450
TYP. DETAILS OF LONGITUDINAL SECTION OF BEAM. BAR DIAMETER MIN. LAP LENGTH
B5 B3 10 mm 500 mm
12 mm 600 mm
16 mm 800 mm
STRUCTURAL LAYOUT OF GROUND & PLINTH BEAMS IMPORTANT NOTES :- GRADE OF CONCRETE M20 20 mm 1000 mm
1. All work shall be strictly executed as per the drawing. Fe500
GRADE OF STEEL
2. Structure is designed for G+2 (3 SLABS) only. CONSTRUCTION NOTE:-
3. Concrete Grade M20 and Steel Fe500 shall be used. SBC ASSUMED 275 Kn/m2 1. CHECK THE CENTERING OF COLUMN / SLAB / BEAM / STAIRCASE
4. Load of Red Bricks for partition walls are considered for design. COVER 1) SLAB 20 MM BEFORE PLACING THE REINFORCEMENT IN PLACE.
5. Take permission from structural engineer before concreting at site. 2. REFER ARCHITECTURE DRAWING ONLY
6. Clear Cover to R/F bars shall be -Footings 50mm, Column 40mm , 2) BEAM 30 MM FOR LEVELS,DIMENSION,ETC.
3. REFER R.C.C. DRAWING FOR MEMBER SIZES AND STEEL
Beams 30mm, Slab 25mm. 3) COLUMN 40 MM REINFORCEMENT SECTION.
7. Developement/Lap length shall be used 4. OUR RESPONSIBILITY WILL BE LIMITED TO SAFE AND STABLE
LEGENDS: GROUND BEAMS 4) FOOTING 50 MM
as 50 times dia of bar. STRUCTURAL DESIGN ONLY, WE HAVE NO ANY CONCERN WITH
8. Stripping time of formwork Shall be as per I.S.456-2000. CONSTRUCTION PERMISSION AND LEGAL ISSUES.
(Beam bottom min. 150mm below NGL) DESIGN FOR G+2
9. False work/ Shuttering Stability is responsibility of contractor.
10. Live load considered over these slab is 2.0 kN/m2
11. If any Special Loads are there kindly inform to
PLINTH BEAMS structural engineer before applying.
(Plinth beam top min. 100mm below Plinth level) 12. Any descripency shall be asked and discussed to
Structural Engineer.
13. Structure is design for Gravity Load Only. TILTLE OF SHEET: STRUCTURAL DETAILS OF
14.Do not change or alter structural drawing. GROUND & PLINTH BEAMS

TILTLE OF PROJECT: PROPOSED RESIDENTIAL BUILDING


AT AURANGABAD
DATE: 20/07/2023 : R0
FIRST FLOOR LEVEL
05

135
L
0.3 SLAB AND BEAM
Main steel AS PER SCHEDULE
10dia@100mm c/c

MID LANDING LEVEL SECOND FLIGHT OF STAIRCASE


L
0.3 WAIST SLAB THK.
135mm thick

MID LANDING LEVEL


0.3
L
MId Landing
Beam
secondary steel
secondary steel 08dia@175mm c/c
08dia@175mm c/c
L 0.3
L
Main steel

135
PLINTH LEVEL 10dia@100mm c/c PLINTH LEVEL

150
WAIST SLAB THK.
135mm thick
Plinth Beams
FIRST FLIGHT OF STAIRCASE As per shedule

TYPICAL SECTION THROUGH


FLIGHTS OF STAIRCASE

TILTLE OF SHEET: STRUCTURAL DETAILS OF


STAIRCASE

TILTLE OF PROJECT: PROPOSED RESIDENTIAL BUILDING


AT AURANGABAD
DATE: 20/07/2023 : R0
C10
C11
150x450
SCHEDULE OF BEAMS. M20 GRADE OF CONCRETE 06
150x380 FB4 FB2 Beam Size Straight Straight Curtail Bar Extra Top Legged Stirrups Stirrups
Group Remark
BxD Top Bar Bottom Bar Middle 0.65*L Ends L/4 of stirups End zone L/4 Middle Half
3'-6"

FBR2
10'-5" --- --- beam
Open 3'-3" S2 FB0 150 X 380 2 - 10 Dia 2 - 10 Dia 2-Legged 6 dia - 150mm c/c 6 dia - 150mm c/c
4'-7" C9 FB1 150 X 380 2 - 10 Dia 2 - 12 Dia 1 - 12 Dia --- 2-Legged 6 dia - 150mm c/c 6 dia - 200mm c/c beam
S3 150x450
FB4

FB5
8'-10" FB3 FB2 150 X 380 2 - 10 Dia 2 - 12 Dia --- 1 - 12 Dia 2-Legged 6 dia - 150mm c/c 6 dia - 200mm c/c beam

FB3 150 X 380 2 - 12 Dia 2 - 12 Dia 1 - 12 Dia 1 - 12 Dia 2-Legged 6 dia - 150mm c/c 6 dia - 200mm c/c beam
8'-1"
FB4 150 X 450 2 - 10 Dia 2 - 12 Dia 2 - 12 Dia 2 - 12 Dia 2-Legged 6 dia - 150mm c/c 6 dia - 175mm c/c beam
C7 FB5 C8
150x380

FB6
FB5 150 X 450 2 - 12 Dia 2 - 12 Dia 2 - 12 Dia 2 - 12 Dia 2-Legged 6 dia - 125mm c/c 6 dia - 175mm c/c beam
150x450
3' 3'-5" 12'-5"
FB0

3'-1" S1
S3 FB6 150 X 450 3 - 12 Dia 3 - 12 Dia 2 - 12 Dia 2 - 12 Dia 2-Legged 6 dia - 100mm c/c 6 dia - 150mm c/c beam
Open
FB1 3'

FB3
2 - 12 Dia bracket
FB5

FB7 150 X 530 2 - 12 Dia 3 - 12 Dia 2 - 12 Dia 2-Legged 6 dia - 100mm c/c 6 dia - 150mm c/c
FB3

4'-1" S1 --- ---


FBR1 150 X 380 4 - 12 Dia 3 - 12 Dia 2-Legged 6 dia - 075mm c/c 6 dia - 075mm c/c bracket
S1 3'-3" S2
HB

FB4 C6 FBR2 150 X 380 5 - 12 Dia 3 - 12 Dia --- --- 2-Legged 6 dia - 075mm c/c 6 dia - 075mm c/c bracket
C4 150x450
FB7 HB 150 X 115 2 - 12 Dia 2 - 12 Dia --- --- 2-Legged 6 dia - 100mm c/c 6 dia - 100mm c/c Hidden Beam
150x450 C5
150x530 150 X 380 2 - 12 Dia 2 - 12 Dia --- --- 2-Legged 6 dia - 150mm c/c 6 dia - 150mm c/c Mid landing
MLB Beam
12'-2"
150 X 380 4 - 12 Dia 2 - 12 Dia --- --- 2-Legged 6 dia - 100mm c/c 6 dia - 100mm c/c Mid landing
MLBR bracket

FB6
S3
FB4

FB4

9'-4"
SCHEDULE OF SLAB. M20 GRADE OF CONCRETE
S4 Steel Along Extra Top
S4 Slab Thickness Remark
Width Length At Discontinue Edge
C2 C3
150x450 S1 115 mm 08 mm @ 125 c/c 08 mm @ 125 c/c --- One Way
C1 FB5 150x380
150x450 S2 115 mm 08 mm @ 125 c/c 08 mm @ 200 c/c --- One Way
MLBR

MLBR
FBR1
FBR2

3' S2 S3 115 mm 08 mm @ 150 c/c 08 mm @ 150 c/c 08 mm @ 300 c/c Two Way
S4 135 mm 08 mm @ 175 c/c 10 mm @ 100 c/c 10 mm @ 100 c/c STAIRS
FB3 MLB
INVERTED BEAMS NOTE : Alternate B/U of one span shall extend to L/4 of other span.
TYPICAL RING / STIRRUP
End bent to All
Top,Bottom & Continue
Extra Top Bars
STRUCTURAL LAYOUT AT FIRST (1ST) SLAB LEVEL (d=depth of beam)
extra top
upto L/4 Column links at
Ld=Development end zone stirrups Rest span column-beam junction are necessary
Length ( L/4 ) stirrups (Middle zone)
Ld= 42xbar dia.
GRADE OF CONCRETE M20
GRADE OF STEEL Fe500
Development Length (Ld=50*d) : 50mm max Curtail Bar SBC ASSUMED 275 Kn/m2
LEGENDS: anchorage pins First stirrup Position at Middle 0.65L At intermediate beam junctions
Continue Top & Bottom bars as per
BAR DIAMETER MIN. LAP LENGTH 16mmØ L=Length of Beam COVER 1) SLAB 20 MM
development Length(Ld) criteria
Column Column
SUNK SLAB 10 mm 500 mm 2) BEAM 30 MM

12 mm 600 mm TYP. DETAILS OF LONGITUDINAL SECTION OF BEAM. 3) COLUMN 40 MM


MID LANDING BEAMS 16 mm 800 mm 4) FOOTING 50 MM
IMPORTANT NOTES :-
20 mm 1000 mm 1. All work shall be strictly executed as per the drawing. DESIGN FOR G+2
2. Structure is designed for G+2 (3 SLABS) only.
3. Concrete Grade M20 and Steel Fe500 shall be used.
CONSTRUCTION NOTE:-
Alt. bent up Steel continue from one span to other 4. Load of Red Bricks for partition walls are considered for design. 1. CHECK THE CENTERING OF COLUMN / SLAB / BEAM / STAIRCASE
5. Take permission from structural engineer before concreting at site. BEFORE PLACING THE REINFORCEMENT IN PLACE.
Alt. Bent up bars 0.3L1 0.3L2 6. Clear Cover to R/F bars shall be -Footings 50mm, Column 40mm , 2. REFER ARCHITECTURE DRAWING ONLY
Beams 30mm, Slab 25mm. FOR LEVELS,DIMENSION,ETC.
7. Developement/Lap length shall be used 3. REFER R.C.C. DRAWING FOR MEMBER SIZES AND STEEL
REINFORCEMENT SECTION.
as 50 times dia of bar. 4. OUR RESPONSIBILITY WILL BE LIMITED TO SAFE AND STABLE
8. Stripping time of formwork Shall be as per I.S.456-2000. STRUCTURAL DESIGN ONLY, WE HAVE NO ANY CONCERN WITH
0.25L1 0.25L2 9. False work/ Shuttering Stability is responsibility of contractor. CONSTRUCTION PERMISSION AND LEGAL ISSUES.
0.2L1
10. Live load considered over these slab is 2.0 kN/m2
L1 L2 11. If any Special Loads are there kindly inform to TILTLE OF SHEET: STRUCTURAL DETAILS AT
structural engineer before applying. FIRST (1ST) SLAB LEVEL
Slab Discontinuous end Slab continuous end 12. Any descripency shall be asked and discussed to PROPOSED RESIDENTIAL BUILDING
Structural Engineer. TILTLE OF PROJECT:
DETAILS OF BAR BENDING FOR SLABS AT AURANGABAD
13. Structure is design for Gravity Load Only.
14.Do not change or alter structural drawing. DATE: 20/07/2023 : R0