You are on page 1of 1

CHILLED WATER SYSTEM

ITEM
Circulation Water
Make Up Water
(20°C or Less)

pH (25°C) 6.0 ~ 8.0 6.0 ~ 8.0


Electric Conductivity
40 or less 30 or less
(mS/m) (25°C) (1)
(400 or less) (300 or less)
Standard item

(µS/cm) (25°)
Chloride Ion (mgCl/L) 50 or less 50 or less
Sulphate (mgSO42-/L) 50 or less 50 or less
Acid Consumption (pH
(mgCaCO3/L) 50 or less 50 or less
4.8)
Overall Hardness (mgCaCO3/L) 70 or less 70 or less
Calcium Hardness (mgCaCO3/L) 50 or less 50 or less
Silica Ion (mgSiO2/L) 30 or less 30 or less
Iron (mgFe/L) 1.0 or less 0.3 or less
Copper (mgCu/L) 1.0 or less 0.1 or less
Reference item

Sulfide Ion (mgS2-/L) Not to ne detected Not to ne detected


Ammonium Ion (mgNH4+/L) 1.0 or less 1.0 or less
Residual Chlorine (mgCI/L) 0.3 or less 0.3 or less
Free Carbon Dioxide (mgCO2/L) 4.0 or less 4.0 or less
Stability index - -