Using 595 x 595 Face Size

and
Neck Size 450 x 450
Refer to Page No-5 for
Acoustic Data and Velocity
as highlighted with red
colour.
R. GLAZEN SINGAPORE PTE L 1D October, 2000 Page 10 of 14

TEST CERTIFICATE No. 1

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF A CEILING DIFFUSER

SUPPLIED BY: R. GLAZEN SINGAPORE PTE LTD


TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD
TEST DATE: 29/9/2000
CLIENT: R. GLAZEN SINGAPORE PTE LTD
UNIT: Perforated 4-way Ceiling Diffuser with Volume Control Damper
Neck size: 140mm x 140mm
Face size: 595mm x 595mm
Volume Control Damper fully open

TEST CONDITIONS SOUND POWER LEVEL, dB re 1E-12 W


OCTAVE BAND CENTRE FREQUENCY (Hz)
Qs Qs Ps T(m) NR NC 125 250 500 1000 2000 4000 8000
(I/s) (cmh) (Pa)
.\
45 162 14 1.2 14 13 <45.0 34.0 27.8 24.1 15.5 <9.2 <9.8
55 198 21 1.5 23 21 <46.0 38.3 34.7 32.6 25.0 <11.2 <9.8
-.
70 252 30 2 29 28 <47.0 42.3 39.7 39.1 34.0 20.5 <10.8
90 324 50 2.6 37 36 <48.5 45.8 46.2 46.6 44.0 32.0 17.7
120 432 82 3.5 45 43 53.3 49.3 51.7 52.1 52.5 43.0 31.1

LEGEND

Qs - Primary Air Flow Rate


Ps - Supply Static Pressure (Pa)
< - Insufficient margin ab,ove background noise to allow accurate determination
NR - Noise Rating number based upon room absorption of 10 dB
NC - Noise Criterion number based upon room absorption of 10 dB
T - Throw in meters to a terminal velocity of 0.25 mls

Greg Theodoridis Norm ~oner


PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.


The tests reported herein have been performed in accordance with its terms of accreditation. This document
shall not be reproduced except in full.

N.A. T.A. Report No.: 302455-1 I'illGT302455-I.doc