You are on page 1of 21

AHU

Standard Air Handling Unit


– Ceiling Type (EC)
Installation and Maintenance Manual
AHU

Contents

1 Safety Precautions .......................................................................................................... 3


2 Unit Outline Dimensions and Specifications.................................................................... 5
3 Handling and Storage ..................................................................................................... 6
3.1 Handling and Lifting of the Unit ............................................................................. 6
3.2 Unit Storage .......................................................................................................... 6
4 Installation ....................................................................................................................... 8
4.1 Installation of the Unit ........................................................................................... 8
4.2 Installation of Water Piping System ...................................................................... 8
4.3 Installation of the Ducting System ....................................................................... 10
4.4 Electrical Wiring .................................................................................................. 10
4.4.1 Connection Diagram for Single Phase, 200-277V EC Fan........................ 10
4.4.2 Connection Diagram for 3 Phase, 380-480V EC Fan (K3G355RG5602) .. 11
4.4.3 Connection Diagram for 3 Phase, 380-480V EC Fan (K3G500RA2803) .. 12
4.5 Integrated Protective Features ............................................................................ 16
5 Test Run ........................................................................................................................ 17
5.1 Pre-Startup Inspection ........................................................................................ 17
5.2 Test Run Procedure ............................................................................................ 17
6 Routine Maintenance .................................................................................................... 18
7 Troubleshooting ............................................................................................................ 20
8 Spare Part ..................................................................................................................... 21
AHU

1 Safety Precautions
Please read through the Safety Precautions carefully before installation and operation. Be
sure to understand and follow the instructions strictly.

WARNING

[Failure to follow the instructions may cause serious personal injury.]


• The unit maintenance and repair can only be conducted provided that the unit is
shut down and disconnected with the power supply. Wait for five minutes after the
disconnection to avoid possible electric shock and confirm that all moving parts
have stopped.
• Never allow any person or object to come into contact with the rotor and impeller
during operation. In the event of a fault, the rotor and the impeller will be energized.
• If control voltage or a stored speed set value is applied, the motor will restart
automatically, e.g. after a power failure.
• Do not wear any loose-fitting clothing or jewelry and confine long hair with a cap to
decrease the potential for entanglement in machinery.
• Ensure that the wiring and its insulation has been done correctly, otherwise, it might
result in fire or electric shock.
• Never connect the grounding wire to a gas pipeline, water pipe, lightning arrester,
etc. An improper grounding device can may to electric shock and other hazards.
• Never touch any electrical appliance with wet hands or flush the unit with water
directly. There is danger of electric shock or other accidents.

CAUTION

[Failure to follow the instructions may cause minor personal injury or property damage.]
• Installation and maintenance must be performed by qualified personnel who are
authorized by the supplier and are familiar with relevant local laws and regulations
and have experience in this type of equipment.
• Always keep the air inlet and supply paths unobstructed.
• Turn off the power supply if the unit will not be used for a long time.
• The air conditioning unit shall not operate in corrosive gas environment as it may
lead to damage to the unit enclosure, pipeline or electrical elements.
• Install and insulate the drain pipe according to the instructions to ensure smooth
water drainage and prevent condensation.
3
AHU

Note: Due to ordering difference, your unit may not have some functions contained in this
manual. Please inform us of the specific performance parameters before placing the order.

4
AHU
2 Unit Outline Dimensions and Specifications

Junction Box
A 135 C 40
Chilled Water
Outlet Pipe
L
Chilled Water

B
Inlet Pipe

Condensate
Drain Pipe

E D

Lifting Hole D=14

E - 40

C - 40

Outlet Header Pipe Drain Unit EC Fan Max.


Dimensions (mm) Flange Diameter Pipe Weight Motor Running
Model
(mm) (DN) Dia. (kg) Supply Ampere
39TF
V/Phase/
A B C D E L W 3/4R 4/6R DN 3/4R 4/6R (A)
Hz
020 763 630 900 1040 927 400 300 32 32 25 90 97 2.2
230/1/50
030 963 630 900 1040 1127 600 300 32 32 25 104 113 2.2
050 1383 630 1200 1340 1547 800 300 40 40 25 159 174 1.7
080 1608 780 1200 1340 1772 1000 500 40 50 25 217 243 400/3/50 5.6
120 2134 840 1200 1340 2298 1200 600 50 50 25 280 318 5.6

Note:

1. Abbreviation:

a) 3/4 R – 3/4 Rows

b) 4/6 R – 4/6 Rows.

2. The weight listed in the table is the operation weight.

3. The company reserves the right to change the specifications without prior notice.

5
AHU

3 Handling and Storage


3.1 Handling and Lifting of the Unit
The performance of tools such as cranes or forklifts used for unit transportation must meet
safety requirements. The quality and transportation methods must comply with local laws
and regulations to avoid accidents. The unit or packing box should be paid special
attention to keep horizontal and avoid unnecessary damage to the components when
handling and lifting. The forklift loading and unloading port, and lifting lugs are reserved for
the unit or packaging box before delivery. Operate according to the method shown in the
figure during lifting to avoid danger or damage to the unit.
• Insert material such as hard cardboard at the position where the wire rope comes
into contact with the unit, preventing the wire rope from scratching the unit.
• Before lifting, estimate the approximate center of gravity of the unit.
• Use lifting straps with sufficient strength to carry the unit for safety.
• Hoist the unit using the lifting lugs provided at the bottom of the unit.
• Run test-liftings to ensure that the unit is balance and stable before the installation.
• Never lift the unit above personnel. This may lead to serious injury or even death.

Figure 3.1 Unit Lifting Method.

3.2 Unit Storage


1. Units and their parts should be stored in the following indoor environment:
Relative humidity: <80%
Ambient temperature: -30℃ - +50℃.
Units and their parts should be kept far from dust, gas, steam or any other
chemicals that may affect their performance.
2. The unit is packaged as a whole and cannot be stacked up.
3. It is recommended to store the unit for no longer than one year in order to
guarantee trouble-free operation and the longest possible service life.
4. If the unit needs to be kept outdoors before being installed in the equipment room,

6
AHU

prevent the unit from being affected by dirt, rain and snow or destroyed by animals,
and do not remove the protective film on the surface of the unit. Do not expose the
unit under direct sunshine to prevent deformation of the PU board.
If the unit needs to be installed outdoors, specify this requirement when placing the order
so that the factory can take special treatment measures.

7
AHU

4 Installation
4.1 Installation of the Unit
1. Carefully check whether the unit is damaged before unit installation. If any of the
following cases occurs, contact the distributor as soon as possible for repairing or
replacement:
a. Impact or serious deformation of the unit.
b. Damage of internal parts;
c. Malfunction of the fan.
2. The installation of the unit shall be conducted by professionals who are familiar with
the product and understand related local regulations. Do not collide or scratch the
unit during installation.
3. For the sake of safety, the supporting structure of ceiling type unit must be strong
enough to bear the weight of the unit and the vibration during unit operation. The
unit must also be kept horizontal to prevent overflow of condensate water from the
drain pan.
4. Space of at least 700 - 800 mm should be reserved around the unit, especially at
the side of the access door (panel) and external water pipe to ease the
maintenance and installation work.
5. The drain piping and exhaust valve are set at the side of heat exchanger header.
Loosen the exhaust valve to discharge air when water is supplied and tighten it
after finish discharging. Drain all the accumulated water in the unit if the unit is to
be stopped operating for a period of time.

4.2 Installation of Water Piping System


1. Before installation, clean the water pipe. Install filter at the water inlet section to
prevent impurities from entering the heat exchanger.
2. When connecting the water inlet and outlet pipe to the unit, use a double tube
clamp to exert even force to the opposite direction at the same time. The torque
force cannot exceed 250.8 N.m (21 Kgf.m), otherwise the pipe would crack due to
twisting and lead to water leakage. The water supply/return pipe outside the unit
must be install with a valve (excluding the condensate drain pipe) to regulate the
flow and cut off the water source during unit overhauling. Thermal insulation
measures must be taken for the water pipes connected to the unit.
3. For the heat exchanger using cold water as medium, the lower pipe is for the water
inlet, while the upper pipe is for the water outlet. Please connect the pipes

8
AHU

according to the labels on the unit.


4. All the water pipe joints must be sealed to prevent water leakage.
5. The unit is unable to bear extra weight other than the drain pipe, water inlet and
outlet pipes.
6. The temperature of refrigerant used for standard model cannot be less than 5°C.
7. The condensate drain piping is located at the bottom of the unit. The U-trap should
be installed according to the internal negative pressure of the unit under operation,
in order to ensure a smooth discharge of condensate and prevent external odor
from entering the cabinet.

When the internal negative


pressure is greater than 800 Pa, H
needs to be increased.

Figure 4.1 U-Trap Installation.

9
AHU

4.3 Installation of the Ducting System


1. The inlet and outlet duct connected to the unit should be sealed to prevent air
leakage. Thermal insulation measures must be taken at the joint of the air outlet
flange and the ducting.
2. Install flexible connector between the air inlet/outlet and the ducting to prevent the
vibration from the unit from transmitting to the ducts or floor.
3. Support the ductwork independently of unit to prevent overloading, and excess
noise and vibration.

4.4 Electrical Wiring


The figure below shows the general wiring diagram of the EC fan. The factory only
connects the power cable and part of the signal cables. Hence, if special control
requirement is needed, please specify it while placing the order.

4.4.1 Connection Diagram for Single Phase, 200-277V EC Fan

Customer Circuit ebm-papst Circuit

Interface
Full Speed Adjustable Speed
PE
1
PE
8 8 2
+ PE1

- 1-10 V N
13 12
3 +
10 V → n = max L
1 V → n = min 5 -
<1 V → n = 0 A2
14

NC
6
Speed Adjustable COM
via Potentiometer 7
A1
11

0-10 V
13 8 0-10 V
RSB 47k 47k
10 RSB 470 nF
12 RSA
10k 11 RSA
GND
12 0V
12 10 V
13 10 V
10
Imax = 10 mA

No. Conn. Designation Color Function/Assignment


1 1,2 PE Green/Yellow Protective earth
1 3 N Blue Power supply, neutral conductor, 50/60 Hz
1 5 L Black Power supply, phase, 50/60 Hz

10
AHU
Status relay, floating status contact; break for failure,
contact rating 250 VAC/2A (AC1)/min. 10 mA, basic
1 6 NC White 1
insulation on supply side and reinforced insulation on
control interface side.
Status relay, floating status contact; common
connection, contact rating 250 VAC/2A (AC1)/min.
1 7 COM White 2
10mA, basic insulation on supply side and reinforced
insulation on control interface side.

Analog input (set value); 0-10 V; Ri = 100 kΩ; adjustable


2 8 0-10V Yellow
curve
2 10 RSB Brown RS485 interface for MODBUS, RSB
2 11 RSA White RS485 interface for MODBUS, RSA
2 12 GND Blue Reference ground for control interface, SELV

Fixed voltage output 10 VDC, +10 V ±3 %; max. 10 mA;


2 13 +10V Red short-circuit-proof; power supply for external devices
(e.g. pot)

4.4.2 Connection Diagram for 3 Phase, 380-480V EC Fan (K3G355RG5602)

Connection Fan / Motor

Customer Circuit KL3

RSA
Full Speed Adjustable Speed 12
RSB
11
RSA
4 3/7 10 RSA
+ RSB
9 RSB
- 1-10 V GND
3 2/8 8 IN
10 V → n = max 0-10V 47k
7
1 V → n = min I O
4-20mA
<1 V → n = 0 6 1
+20V
5 20V
Set Value Requirement, Speed Adjustable +10V
eg. via Pressure via Potentiometer 4 10V
0-10V 33
3 100 47k 2.2μF
5 GND
+ 4 2
OUT
- 4-20 mV 1 OUT
6
3/7
10k
GND
2/8 KL2
NO
A2
14
12

3
COM
2
NC
1
A1

KL1
L1
3
L2 + P
2
L3 - N
1

PE
PE1 / Housing

11
AHU

No. Conn. Designation Function/Assignment


PE PE Protective earth
KL1 1,2,3 L1, L2, L3 Power supply, voltage range (see nameplate), 50/60 Hz
KL2 1 NC Floating status contact, break for failure
floating status contact, changeover contact, common connection (2 A,
KL2 2 COM
max. 250 VAC, min. 10 mA, AC1)
KL2 3 NO Floating status contact, make for failure
Analog output, 0-10 VDC, max. 3 mA, SELV,
output of current motor modulation level:
KL3 1 OUT
1 V corresponds to 10% modulation level.
10 V corresponds to 100% modulation level.
KL3 2,8 GND Reference ground for control interface, SELV
Use control / current sensor value input 0-10 VDC, impedance 100 kΩ
KL3 3,7 0-10 V
only as alternative to 4-20 mA input, SELV
Voltage output 10 VDC (±3%), max. 10 mA, power supply for external
KL3 4 +10 V
devices (e.g. potentiometer), SELV
Voltage output 20 VDC (+25%/-10%), max. 50 mA, power supply for
KL3 5 +20 V
external devices (e.g. sensors), SELV
Use control / current sensor value input 4-20 mA, impedance 100 Ω only
KL3 6 4-20 mA
as alternative to 0-10 V input, SELV
KL3 9,11 RSB RS485 interface for MODBUS, RSB
KL3 10,12 RSA RS485 interface for MODBUS, RSA

4.4.3 Connection Diagram for 3 Phase, 380-480V EC Fan (K3G500RA2803)

12
AHU

Conn. Designation Function/Assignment


CON1 L1, L2, L3 Power supply, phase, see nameplate for voltage range
PE PE Protective earth
CON2 RSA RS485 interface for MODBUS, RSA; SELV
CON2 RSB RS485 interface for MODBUS, RSB; SELV
CON2 GND Reference ground for control interface, SELV
Function parameterizable (see “Optional interface functions” table)
Factory setting:
Digital input – high active, function: Disable input, SELV
CON2 IO1 - Inactive: Pin open or applied voltage < 1.5 VDC
- Active: Applied voltage 3.5-50 VDC
Reset function: Triggering of error reset on change of state from “enabled”
to “disabled”
Function parameterizable (see “Optional interface functions” table)
Factory setting:
CON2 IO2 Analog input 0-10V / PWM, Ri = 100 kΩ, function: Set value
Characteristic curve parameterizable (see input characteristic curve
P1-IN), SELV
Function parameterizable (see “Optional interface functions” table)
Factory setting:
CON2 IO3 Analog output 0-10V, max. 5mA, function: Fan modulation level
Characteristic curve parameterizable (see output characteristic curve
P3-OUT), SELV
Voltage output 3.3-24 VDC ±5%, Pmax=800 mW, voltage parameterizable
Factory setting: 10 VDC
CON2 Vout Short-circuit-proof, supply for external devices, SELV
Alternatively: 15-50 VDC input for parameterization via MODBUS without
line voltage
Status relay, floating status contact, common connection, contact rating
CON2 COM 250 VAC / 2A (AC1) / min. 10 mA, reinforced insulation on supply side and
on control interface side
CON2 NC Status relay, floating status contact, break for failure
Green: Status = Good, ready for operation
LED Orange: Status = Warning
Red: Status = Failure
P1-IN Input characteristic curve
P3-OUT Output characteristic curve

13
AHU

Terminal / Plug Assignment

(Selected directly

(Selected directly
D16C [...]
D12E [...]

D16A [...]
D101 [...]
D147 [...]
D104 [...]

D148 [...]

D00C [1]
via IO mode)

via IO mode)
D130 [0]
D130 [1]
D130 [2]
D130 [5]

D130 [4]
INPUT OUTPUT

Switch: Control function: Heating (Pos.) /


Functions: Normal / Inverse

Switch: Direction of rotation: CW / CCW

Signal: Remote control output 0-10V


Signal: System modulation level %

Pulse output for auto-adressing


Signal: Fan modulation level %
Switch: Parameter set: #1 / #2

Pulse input for auto-adressing


Configurable IO

Switch: Fan enable / disable


Switch: Set value source
● Configurable Option

Signal: Diagnostics out


Source: Sensor value

Signal: Actual speed


Source: Set value

Signal: Tach out


Cooling (Neg.)
MODBUS
Register for IO
Mode
CON2 Configurable IO Mode Electrical Specification Configuration
Not active: Pin open or applied voltage < 1.5VDC
● Din1 (Active high): Digital input Active: Applied voltage 3.5-50VDC, SELV
D158 [0] ● ● ● ● ● ●

● Ain1 0-10V/PWM: Analog input Ri=100K, characteristic curve parameterizable, fPWM=1k..10kHz, SELV D158 [2] ● ●
IO1
● Tach out (Open collector output) Umax=50VDC, Imax=20mA, SELV D158 [5] ●
● Diagnostics out (Open collector output) Umax=50VDC, Imax=20mA, SELV D158 [6] ●
Not active: Pin open or applied voltage < 1.5VDC
● Din2 (Active high): Digital input D159 [0] ● ● ● ● ●
Active: Applied voltage 3.5-50VDC, SELV
IO2 ● Ain2 0-10V/PWM: Analog input Ri=100K, characteristic curve parameterizable, fPWM=1k..10kHz, SELV D159 [2]
● ●
● Ain2 4-20mA: Analog input Ri=125R, characteristic curve parameterizable, SELV D159 [3]
Not active: Pin open or applied voltage < 1.5VDC
● Din3 (Active high): Digital input D15A [0]
Active: Applied voltage 3.5-50VDC, SELV
● ● ● ● ●
IO3 Not active: Pin open or applied voltage 3.5-50VDC
● Din3 (Active low): Digital input D15A [1]
Active: Applied voltage < 1.5VDC, SELV
40Hz - 10kHz, characteristics parameterizable
● PWMin3: Digital input Not active: Pin open or applied voltage 3.5-50VDC D15A [7] ●
Active: Applied voltage < 1.5VDC, SELV
● Aout3 0-10V: Analog output Function parameterizable, Max. 5mA, Max output frequency 300Hz, SELV D15A [4] ● ● ● ● ●
● Tach out (Pulses), Analog output 0-10V max. 5mA, Max output frequency 300Hz, SELV D15A [5] ●
● Diagnostics out (Pulses) 0-10V max. 5mA, Max output frequency 300Hz, SELV D15A [6] ●
RSA
● RS485 bus connection MODBUS RTU, Specification V6.0, SELV ● ● ● ● ● ●
RSB
Voltage parameterizable 3.3...24VDC +/- 5,5%, Pmax=800mW,
● Voltage output D16E [...]
Short-circuit-proof, Supply for external devices, SELV
Vout ● Alternatively: Input auxillary power supply for
parameter-ization via RS485/MODBUS RTU 15...50VDC
without line voltage

14
AHU

0-10 V

+10 V
COM

GND
RSB
RSA

PE
NC

1 N
2 L
1

7
3
2

6
5
Figure 4.2: Junction Box Connection Diagram for Single Phase, 200-277V EC Fan.
4 Ain1U

9 COM
6 DIN1
5 GND

7 Aout
RSA
2 RSB
3 10V

8 NC

PE

L1
2 L2
3 L3
1

1
Figure 4.3: Junction Box Connection Diagram for 3 Phase, 380-480V EC Fan
(K3G355RG5602).
9 COM
3 Vout
RSA
2 RSB

5 GND
4 IO2

6 IO1
7 IO3
8 NC

PE

L1
2 L2
3 L3
1

Figure 4.4: Junction Box Connection Diagram for Single Phase, 200-277V EC Fan.

Note: The wiring will be connected as shown above unless otherwise specified by the
customer.

15
AHU

4.5 Integrated Protective Features


The integrated protective functions cause the EC Fan motor to switch off automatically in
the event of the faults described in the table.

Fault Safety feature description/function


Rotor position detection error An automatic restart follows.
After the blockage is removed, the motor restarts
Blocked rotor
automatically.
Line undervoltage (line
If the line voltage returns to permitted values, the motor
voltage outside of permitted
restarts automatically.
nominal voltage range)
A phase of the supply voltage fails for at least 5 s. When
Phase failure all phases are correctly supplied again, the motor
automatically restarts after 10-40 s.

16
AHU

5 Test Run
5.1 Pre-Startup Inspection
1. Ensure that the unit is mounted securely to the supporting structure and is kept
level.
2. Check that all the ducting and piping are connected correctly to the unit.
3. Check that the electrical wiring of the fan is complete and in accordance with the
wiring diagram. Make sure that the fan is grounded.
4. Open the exhaust valve on the water return pipe and close it after air is removed
from the coil and pipeline.
5. Rotate the fan impeller manually to check whether there is any abnormal friction
sound. If yes, eliminate the cause.
6. Ensure the condensate drainage is unobstructed and properly installed.
7. Verify that the interior of the unit is clean and free from dirt, tool, or any other
foreign objects.
8. Check the condition of the filter and make sure that the duct connected to the unit is
clean.
9. Make sure that the power supply matches the device voltage.

5.2 Test Run Procedure


1. Start the test run after the pre-startup inspection has been well completed.
2. Make sure the fan operating current do not exceed the rated current.
3. Ensure low-vibration operation of the fan over the entire speed control range.
4. Check whether the condensate is drained properly without water leakage.
5. Check whether there is any abnormal air noise and air leakage.
6. Check whether the unit air flow and air pressure are normal. The cooling capacity
should be regulated according to different operating conditions.
7. If the EC fan needs to be switched off during operation, switch it off via the control
input. Do not switch the motor (e.g. in cyclic operation) on and off via power supply.
8. Disconnect the ground connection last if the EC fan is to be removed for
maintenance.

17
AHU

6 Routine Maintenance
Note: Maintenance work can only be carried out after the unit has been completely
stopped.
Check the unit operating status on an irregular basis, and implement long-term and
effective maintenance for the unit so as to greatly improve the unit operation reliability and
service life.
1. To ensure good ventilation and achieve high heat exchange efficiency, check the
condition of air filters on a monthly basis, or on a weekly basis in places where air
environment is poor. Once the maximum pressure drop has been reached, clean or
replace the filter. The factory recommended the following maximum pressure drop:
Filter Maximum Pressure Drop (Pa)
MERV 5 (Primary Efficiency) 100
2. Inspect the condition of coil quarterly to confirm whether it is necessary to clean the
coil. Clean when fouling is observed. After the unit has been used for 2-3 years,
clear the water scale inside the pipe.
3. Check that the condensate discharge has no clogging and leaking issues.
4. Clean the drain pan and water seal elbow on an annual basis.
5. Check the flexible connector of air duct regularly. In case of air leakage, repair it in
time.
6. Inspect the wiring to make sure that the connections are tight and well insulated.
7. After checking, make sure that the EC fan terminal box is completely closed and that
all screws and cable glands have been properly tightened.
8. Inspect the fan for proper operation and soiling. Only clean when the fan is not in
motion. Do not disconnect the fan from power supply, just switch it off via control input
to prevent startup of the fan.
9. Use dry cleaning method (e.g. compressed air) to clean the fan. Deposition of dirt on
the motor housing can cause overheating of the motor, and soiling of the impeller can
cause vibration that will shorten the service life of the fan. Do not use aggressive
cleaning agent such as acid, alkali, or solvent-based cleaning agent.
10. If cleaning does not eliminate vibrations, the fan may need to be rebalanced. To have it
rebalanced, contact the supplier.
11. The fan is equipped with maintenance-free ball bearings. The lifetime lubrication of the
ball bearings is designed for a service life of at least 40,000 hours. If bearing
replacement is necessary after that period, contact the supplier.
12. Do not perform any repairs on the fan. Send it to supplier for repair or replacement.

18
AHU

13. If the unit is under prolonged downtime in winter, turn off the power supply and fully
drain the coil to prevent freezing. Compressed air can be utilized to remove residue
water in the coil. During the downtime, start and operate the EC fan at full speed for
one hour at least every four months to move the bearings and allow any condensate
that may have ingressed to evaporate.
14. To remove the service panel, do not pull it out from the bottom. Remove it slowly
from the top, otherwise the lining board of service panel would be damaged by
pulling.

Service panel
Heat exchanger
Service panel Heat exchanger

Remove upward from Remove downward


the bottom from the top

15. Before installing the removed service panel, clean the dried sealant at the side of
drain pan near to the service panel, and then apply it again for sealing to prevent
air and water leakage.

19
AHU

7 Troubleshooting
Common Fault Possible Cause Solution
1. Loosening of fan mounting. 1. Fasten the bolt.
2. Presence of foreign matter in the impeller. 2. Clear the foreign matter.
3. Loosening of air duct and regulating valve. 3. Fasten them.
Abnormal sound
4. Incorrect size of flexible connector. 4. Replace it with a proper flexible connector.
5. Loosening of connection ducts at unit’s inlet and
5. Fasten them.
outlet.
1. Dirty filter. 1. Clean the filter.
2. Poor air duct sealing. 2. Check the air duct and fix the pipeline leakage.
Low air supply
3. Presence of obstacle in the air duct. 3. Check the pipeline and remove the obstacle.
volume
4. Close of air damper. 4. Open the damper.
5. Low fan rotation speed. 5. Adjust the fan speed.
High air supply
1. High fan rotation speed. 1. Adjust the fan speed.
volume
1. Splashing of water caused by high air speed. 1. Reduce the unit air flow.
2. Check whether the prepared drainage U-trap is
Water leakage 2. Overflow of water from drain pan. properly installed, and clear the dirt from the
drainage pipe.
3. Condensation due to unit air leakage. 3. Seal the air leakage point.
1. High inlet water temperature supplied to the coil. 1. Adjust the inlet water temperature.
Insufficient 2. Fouling of coil. 2. Clean the coil.
cooling capacity
3. Eliminate the cause of insufficient air supply
3. Insufficient air supply volume.
volume and increase the air supply volume.
Impeller not 1. Clean the device; replace it if imbalance persists
running 1. Imbalance in rotating parts after cleaning. Make sure no weight clips are
smoothly removed during cleaning.
1. Switch off, isolate from supply and remove
1.Mechanical blockage
mechanical blockage.
2. Check line voltage, restore power supply. The
2.Line voltage faulty error message resets automatically. Device
restarts automatically without warning.
3. Isolate from supply, correct connection; see
3.Faulty connection
connection diagram.
4.Broken motor winding 4. Replace device
5. Improve cooling. Let the device cool down. To
reset the error message, switch off the line voltage
for at least 25s and then switch it on again.
5.Deficient cooling
Motor not Alternatively, reset the error message by applying
turning a control signal of < 0.5 V to Din1 or by shorting
Din1 to GND.
6. Reduce the ambient temperature. Let the device
cool down. To reset the error message, switch off
the line voltage for at least 25 s and then switch it
6.Ambient temperature too high
on again. Alternatively, reset the error message by
applying a control signal of < 0.5 V to Din1 or by
shorting Din1 to GND.
8. Correct the operating point. Let the device cool
down. To reset the error message, switch off the
7.Impermissible point of operation (e.g. back line voltage for at least 25 s and then switch it on
pressure too high) again. Alternatively, reset the error message by
applying a control signal of < 0.5 V to Din1 or by
shorting Din1 to GND.

20
AHU

8 Spare Part

Model Spare Part Main Specification Quantity

Air Filter Panel type, MERV 5, 290*493*46mm 2


39TF020
EC Fan K3G280RR03H2 1

Panel type, MERV 5, 493*493*46mm 1


Air Filter
39TF030 Panel type, MERV 5, 290*493*46mm 1

EC Fan K3G280RR03H2 1

Air Filter Panel type, MERV 5, 493*595*46mm 2


39TF050
EC Fan K3G355RG5601 1

Panel type, MERV 5, 595*595*46mm 2


Air Filter
39TF080 Panel type, MERV 5, 290*595*46mm 1

EC Fan K3G500RA2803 1

Panel type, MERV 5, 595*595*46mm 2

Air Filter Panel type, MERV 5, 493*595*46mm 1


39TF120
Panel type, MERV 5, 290*595*46mm 1
EC Fan K3G500RA2803 1

21

You might also like