You are on page 1of 10

500 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO.

2, APRIL 2002

Modeling Transformers With Internal Incipient Faults


Hang Wang, Student Member, IEEE, and Karen L. Butler, Senior Member, IEEE

Abstract—Incipient fault detection in transformers can provide fault in transformers. This paper presents a new methodology
early warning of electrical failure and could prevent catastrophic developed to model internal incipient winding faults in distribu-
losses. To develop transformer incipient fault detection technique, tion transformers based on the author’s earlier work involving
a transformer model to simulate internal incipient faults is
required. This paper presents a methodology to model internal the development of a two-dimensional (2-D) nonlinear finite
incipient winding faults in distribution transformers. These element analysis internal short circuit fault model [9].
models were implemented by combining deteriorating insulation This method contains a degrading insulation model and a
models with an internal short circuit fault model. The internal transformer internal short circuit fault model. Since deteri-
short circuit fault model was developed using finite element orating insulation involves two stages aging and arcing, the
analysis. The deteriorating insulation model, including an aging
model and an arcing model connected in parallel, was developed degrading insulation model is composed of an aging model and
based on the physical behavior of aging insulation and the arcing an arcing model connected in parallel. The degrading insulation
phenomena occurring when the insulation was severely damaged. model was combined with the internal short circuit model,
The characteristics of the incipient faults from the simulation were developed in our earlier work, to simulate internal winding
compared with those from some potential experimental incipient incipient faults. The transformer internal incipient fault model
fault cases. The comparison showed the experimentally obtained
characteristics of terminal behaviors of the faulted transformer was implemented using commercially available finite element
were similar to the simulation results from the incipient fault analysis software. Various incipient fault scenarios at different
models. degrading levels of the transformer winding insulation were
Index Terms—Aging, arcing, distribution transformer, finite- simulated. In these fault scenarios, the terminal voltages and
element analysis, internal incipient winding fault, modeling. currents of the transformer were analyzed in both time domain
and frequency domain. The characteristics obtained from the
simulation were compared with the characteristics obtained
I. INTRODUCTION from some experimental fault cases that conveyed incipient-like
behavior.
I NTERNAL winding faults resulting from the degradation
of transformer winding insulation can be catastrophic and
hence expensive. In the new environment of deregulation, utili-
In this paper, the transformer model to simulate internal short
circuit winding faults is briefly introduced in Section II. Then
ties therefore are needing inexpensive methods employed to de- the method to simulate an incipient internal winding fault is dis-
tect such faults in the incipient stage. However, the implemen- cussed in more detail in Section III. In Section IV, some simu-
tations of the existing monitoring methods [1]–[4] tend to cost lation results are discussed and compared with experimental re-
too much to be applied to distribution transformers. Therefore, sults. The conclusions are given in Section V.
an ongoing project in the Power Systems Automation Labora-
tory (PSAL) of Texas A&M University is to develop an on-line
II. INTERNAL SHORT CIRCUIT FAULT MODEL
incipient fault detection method for single-phase distribution
transformers that utilizes the terminal parameters of voltages A method was developed to apply finite element analysis to
and currents. The development of an accurate internal fault di- calculate the parameters for an equivalent circuit of the trans-
agnostic technique for transformers must be based on the anal- former with an internal short circuit fault using ANSOFT’s
ysis of quantities from fault scenarios. Considering the safety Maxwell Software [9]. The 2-D Magnetostatic solver in the
of personnel, the damage that will occur in the transformer, the package was used to compute the model of the transformer and
consumed time, and related cost, simulation involving the mod- export an equivalent circuit in the format of SPICE subcircuits.
eling of transformers at various incipient fault stages is the best Using finite element analysis to solve problems involves three
way to generate these fault cases. stages. The first step consists of meshing the problem space
Several transformer models have been developed for the into contiguous elements of suitable geometry and assigning
study of transformers with internal short circuit winding faults appropriate values of the material parameters—conductivity,
[5]–[9] and some research work on the representation of permeability, and permittivity—to each element. Since an
insulation material was done in the past [10]–[12]. However, object with permeability equal to 1 in a magnetic model does
none of them discussed how to simulate an internal incipient not need to be modeled, the insulation between the turns and
layers were ignored completely. The core was represented by a
Manuscript received May 7, 2001. This work was supported by the National rectangle with two windows. The nonlinear characteristics of
Science Foundation through Grant ECS-9522208. the core were input manually into the solver and assigned to the
The authors are with the Department of Electrical Engineering, Power core. To model an internal fault on the primary or secondary
Systems Automation Laboratory,Texas A&M University, College Station, TX
77843-3128 USA. winding, the faulted winding is divided into two subcoils “a”
Publisher Item Identifier S 0885-8977(02)02742-5. and “b” (turn-to-earth fault) or three subcoils “a,” “b,” and “c”
0885-8977/02$17.00 © 2002 IEEE

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on June 28,2022 at 01:12:24 UTC from IEEE Xplore. Restrictions apply.
WANG AND BUTLER: MODELING TRANSFORMERS WITH INTERNAL INCIPIENT FAULTS 501

tures, electrical stresses may act to further accelerate material


degradation. Mechanical stresses are caused by assembly con-
figurations, manufacturing techniques, centrifugal forces and
vibration. Moisture is another major cause of lowered dielectric
properties. It can form a conductive path on the surfaces of
material or react with the material to cause chemical reversion.
The structure of a dielectric may be altered significantly
(a) (b) during the aging process, and these changes will affect the
Fig. 1. Transformer model to simulate an internal fault.
electrical properties of the dielectric even before insulation
failure occurs [13], [14]. The relaxation processes a dielectric
undergoes, and hence the characteristics of dielectric loss,
(turn-to-turn fault). The primary winding and the secondary depend on the structure. As the structure of the dielectric
windings are represented by polygons of corresponding ma- molecules alter during aging, the dielectric characteristics and
terials. For instance, to simulate a turn-to-earth fault on the electrical properties change. Normal aging of the insulation
primary winding, the transformer is modeled as shown in the may be manifested by the gradual reduction in its withstand
Fig. 1(a). The primary winding is divided into two subcoils “a” capability over a long period of time. In addtion, discharges
and “b.” The transformer model to simulate a turn-to-turn fault would like to take place on the surface of the solid insulation or
between two turns on the primary winding is represented as within enclosed voids. The gas ions driven by the electric field
shown in Fig. 1(b). The primary winding is divided into three would hit on the wall of the insulation and react chemically
coils, “a,” “b,” and “c.” with some of its surface layer molecules. Thus chemical and
Second, the model has to be excited to set up the initial condi- thermal degradation of the insulating material occurs at these
tions. Since the subcoil with the maximum number of turns con- microscopic sites. When a persistent discharge continues, it
tributes more in the magnetic field, the current source is input is called an arc discharge. This can result in the failure of the
into that subcoil and all the other coils are open-circuit. In the dielectric and a sudden breakdown under operating voltage.
above example, since subcoil “b” in Fig. 1(a) and subcoil “c” in To simulate the incipient internal winding faults completely,
Fig. 1(b) represent more turns, respectively, they are energized both the aging phase and the arcing phase have to be taken into
by the current source. account. Therefore, a combination of an insulation aging model
Finally, the boundary conditions for the problem have to be and an arcing model was developed to model an incipient in-
specified. Balloon boundary is adopted in the simulation. Bal- ternal winding fault.
loon boundaries model the region outside the drawing space as
being nearly “infinitely” large; thus, it can effectively isolate the A. Aging Model
model from other voltage sources.
In considering the electrical behavior of dielectric material,
In post-processing, the calculated parameters can be exported
it has been traditional to approach the subject in terms of an
into a SPICE subcircuit based on field solutions created in the
equivalent parallel circuit as shown in Fig. 2 [14]. is the ap-
Maxwell 2-D field solver. The equivalent circuit derived from
plied voltage and is the current through the insulation. is the
the finite element analysis is displayed as a black box with a
capacitive component of current and the resistive component of
set of interface terminals. The internal faults are simulated by
the current is . The resistance represents the lossy part
shorting the two terminals or connecting one terminal to the
of the dielectric, taking account of the losses that may result
ground.
from electronic and ionic conductivity, dipole orientation and
To simulate an incipient internal winding fault, a model of
space charge polarization. The capacitance of the dielectric
degraded insulation before breakdown replaced the switch be-
is given by (1), where is the equivalent capacitance in the
tween two turns to model an incipient internal winding fault.
vacuum of the insulation and is the relative permittivity or
dielectric constant
III. DETERIORATING INSULATION MODEL
(1)
The deteriorating insulation between the turns is a major
cause of incipient internal winding faults in transformers. In Fig. 2(b), is defined as the loss angle, which represents
During the operation of the transformer, a strong electric the dielectric energy losses in the insulation. is commonly
field is applied to the dielectric material. It can result in the known as loss tangent or dissipation factor. is the power
aging and deterioration of the insulation. The relevant factors factor of the dielectric. For a perfect dielectric, the loss is very
generally recognized as causing the aging and deterioration small ( 0); the current leads the applied voltage by 90 degrees.
of an insulation include thermal stresses, electrical stresses, During aging of the dielectric, the loss increases; therefore the
mechanical stresses, moisture, and so on [13]. Thermal stresses angle between the current vector and the applied voltage is less
are caused by the internal heating due to current overloads than 90 degrees. The dissipation factor may also be expressed
plus ambient temperatures. Electrical stresses are caused by as (2)
the voltage gradient in the insulation. Under normal operating
conditions, high voltage gradients below the breakdown voltage
(2)
do not cause detectable aging. However at elevated tempera-

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on June 28,2022 at 01:12:24 UTC from IEEE Xplore. Restrictions apply.
502 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002

(a) (b)
Fig. 2. Equivalent circuit of a dielectric material. (a) Parallel equivalent circuit.
(b) Corresponding phasor diagram.

Fig. 3. r
Concentrated insulation model between the th turn and ( r + m)th Fig. 4. Arcing voltage and current.
turn.

The dissipation factor is generally used for describing macro-


scopic properties of dielectric material. The energy dissipated
as heat in the dielectric is proportional to . The variation
of with the applied voltage is an important relation which
gives useful information about the quality of the insulation
and whether an imperfection exists in the insulation [15], [16]. (a) (b)
Therefore, in the work reported in this paper, we investigated Fig. 5. Equivalent circuits of the arc (a) during the burning period (b) during
the modeling of the deterioration of the insulation by varying the extinction period.
the dissipation factors to represent the different degradation
levels of the insulation. Then the equivalent resistance and The arcing characteristics are illustrated in Fig. 4. The figure
capacitance corresponding to the selected dissipation factor shows the simple case of arcing current and arcing voltage in a
were computed. These values represent the insulation at a resistive load circuit. The dotted line is the arcing current; the
specific degradation level. solid line is the arcing voltage; the dash-dot line is the system
The equivalent resistance and capacitance of the insulation voltage. The arc ignites only after sufficient voltage is across
between the adjacent turns can be calculated based on the ge- the gap. It extinguishes when voltage drops below that needed
ometry information and the material properties of the insulation. to sustain the arc. Arcing voltage is almost a square wave, ex-
Then a reasonable dissipation factor, which represents the cept for the transient near current zero. In the figure, the magni-
degrading degree of the insulation, is selected. Since the equiv- tude of the square wave, is the voltage needed to sustain the
alent capacitance, , changes little, the resistance in the equiv- arc. The choppiness of the voltage trace indicates another dis-
alent circuit of the insulation between two adjacent turns can be tinct characteristic of the arc, that of a high-frequency voltage
computed by (3) source. In addition, arcing is random. Once it starts, it may be
interspersed with segments of normal current. The rms value of
(3) arc current and energy is less than that of a bolted fault.
For arcs of very small length, such as the arcing between two
After the equivalent circuit of the insulation between the adja- turns of a transformer winding, a fixed back voltage opposing
cent turns is obtained, the aging model of the insulation between the source is commonly used to represent the arc as shown in
the th turn and ( )th turn can be illustrated as shown in Fig. 5 [19]. The equivalent circuit comprises a resistance and an
Fig. 3, where , . inductance that are functions of the arc length , its current ,
and the current’s rate of change with time . The above param-
B. Arcing Model eters can be experimentally obtained. Fig. 5(a) would apply for
An arc is defined as a continuous luminous discharge of elec- both dc and ac circuits during periods when the arc is burning.
tricity across an insulating medium, usually accompanied by the During periods of effective current zero, however, the arc can
partial volatilization of the electrodes [17]. Arcs may develop be represented by a high resistance, , that increases with
from a spark when arc tracking occurs across a partially conduc- time. In Fig. 5(b), represents the stray capacitance.
tive surface, such as damaged insulation. Once extinguished, an Since the insulation between the two layers or the two turns in
arc requires a potential, known as the restrike voltage, to reignite the windings is very thin, the resistance , inductance and the
the arc. After an AC current becomes zero, the restrike voltage stray capacitance in the equivalent circuit are small enough
establishes the potential needed to restrike the arc with the op- to be ignored. Thus, the arcing model can be represented by the
posite polarity. From experimental results and analysis, Schurig equivalent circuit shown in Fig. 6. The voltage source is a
reported that the arc voltage is usually flap-topped and that the random square wave representing the equivalent arcing voltage.
magnitude of arcing fault currents ranged from 57% to 100% of S1 and S2 are time-controlled switches. If there is no arcing in
the available short-circuit current [18]. the circuit, S1 is closed and S2 is open, and the value of is

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on June 28,2022 at 01:12:24 UTC from IEEE Xplore. Restrictions apply.
WANG AND BUTLER: MODELING TRANSFORMERS WITH INTERNAL INCIPIENT FAULTS 503

TABLE II
PARAMETERS IN AGING MODEL FOR PRIMARY FAULT P15_55

Fig. 6. Arcing model for incipient internal winding faults.


similar to those from the field tests, this paper focuses on dis-
cussing the implementation of the parallel combination model
and the corresponding simulation results.

IV. IMPLEMENTATION AND SIMULATION RESULTS


A. Transformer Parameters
Simulations were carried out based on a custom-built 25 kVA,
60 Hz, single-phase, shell-form transformer used for field ex-
periments. The design data were as follows.
• The rated voltage ratio was 7200 V/240 V/120 V.
Fig. 7. Parallel combination model for the insulation. • The normal impedance was 1.75%, and normal reactance
was 1.62%.
TABLE I
• The turns ratio was 780/26.
SUMMARY OF VALUES OF VARIABLES DURING DIFFERENT PERIODS • The primary winding was made of copper; the secondary
subwindings were made of aluminum.
• The insulation between the layers in the custom-built
transformer was made of Aramid paper.
The custom-built transformer was equipped with various taps
placed on both windings so that internal faults could be per-
formed by connecting two taps or connecting a tap to ground
[21].

B. Incipient Faults With Aging Model Only


zero. When equals to , the model represents arcing. When Based on the transformer information listed above and the
S1 is closed and S2 is open, the arcing model is in the burning modeling principles discussed in Section II, the parameters of
period. Otherwise, when S1 is open and S2 is closed, the arcing the equivalent circuit for the perfect insulation between two ad-
model is in the extinction period. jacent turns of the transformer were calculated. According to
the literatures and previous experimental results, the equivalent
C. Combination Models capacitance, , changes little. Therefore, we fix the equiva-
Fig. 7 represents the parallel combination model. Table I lent capacitance. Then, by changing , the different values
shows the values of various parameters in the different periods of for the various fault scenarios were computed using (3)
to represent the insulation in different degraded levels. For in-
of this model. The parallel model represents a perfect insulation
stance, to simulate an incipient winding fault between the 15th
when S1 and S2 are open; the value of is zero and
turn and the 55th turn on the primary winding, the parameters in
is a very large resistance so that the current in the insulation
the insulation model for different deteriorated insulation levels
is almost zero. To represent deteriorating insulation, is
are shown in Table II. The equivalent capacitance for the insu-
decreased to a small value. When the random square wave is lation between 15th and 55th turns was 89 nF. For the perfect
zero, S1 and S2 are open. The model represents the nonarcing insulation of Aramid paper as shown in Case 1, the dissipation
deteriorating insulation. When the value of is , the model factor, , was 0.006. Thus the calculated result for the equiv-
represents the degrading insulation with arcing. In this case, alent resistance was 49.0 M using (3). With the deterioration
when S1 is closed and S2 is open, the model simulates the of the insulation, the dissipation factor increased. When the dis-
burning period. If S1 is open and S2 is closed, it models the sipation factor increased to 3 10 as shown in Case 11, the in-
extinction period. sulation was broken down completely. Thus, according to the
The aging model and the arcing model can also be connected similar method, the equivalent resistances for all of the cases
in series into a series combination insulation model. In [20] the listed in Table II were calculated.
simulation using the series combination insulation model was After the aging model was obtained, it was combined with
discussed in more detail. Since the comparison between the sim- the FEA internal short circuit fault model to investigate the ter-
ulation and the field test results showed the terminal character- minal behaviors of the transformer when the insulation is de-
istics obtained from the parallel combination model were more grading. When the incipient fault occurred between the 15th

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on June 28,2022 at 01:12:24 UTC from IEEE Xplore. Restrictions apply.
504 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002

(a)

(a)

(b)
Fig. 9. Terminal voltage and currents with the aging model to simulate
secondary incipient fault. (a) Relationship between primary current and R .
(b) Relationship between secondary current and R .

(b)
Fig. 8. Terminal currents with the aging model to simulate primary incipient and paralleled with the internal short circuit fault model in the
fault. (a) Relationship between primary current and R . (b) Relationship Maxwell Spice, as shown in Fig. 7. The aging model and the
between secondary current and R . arcing model connected in parallel were used to investigate ter-
minal voltages and currents, and the circulating current flowing
and the 55th turns on the primary winding, the relationships be- through the insulation model when the insulation was degrading
tween the RMS values of primary current and secondary cur- and the arcing phenomena appeared.
rent in one power cycle and the resistance are illustrated in For the case where the insulation resistance, , in the par-
Fig. 8(a) and (b). From the plots, some conclusions were ob- allel model was 0.1 (i.e., the dissipation factor is equal
tained. First, when was larger than 10 , the primary cur- to 3 10 ), and the waveforms of and the time sequences
rent was very close to the transformer rated values. In other to control S1 and S2 in Fig. 7 were as shown in Fig. 10, respec-
words, the transformer was in good condition. When was tively, the waveforms of primary current ( ), secondary cur-
less than 0.01 , the primary current was approximately equal to rent ( ) and the circulating current ( ) are shown in Fig. 11. In
the internal short circuit current. Namely, an internal short-cir-
Fig. 10, the arcing voltage is 260 V. When the time sequence is
cuit fault occurred in the transformer. When the value of was
1, the controlled switch is on; if it is 0, the switch is off.
in the range of [0.01, 10], the primary current changed between
In Fig. 11, when there was no arcing, for instance, at time
the rated current and the short circuit current value. That shows
s, the primary current and circulating current were
an incipient fault occurred in the transformer. Second, the sec-
ondary voltage and current were almost at the rated values when very large and close to the short circuit current level for this
an incipient internal winding fault existed in the transformer. case. When arcing occurred, such as at time s, the
Fig. 9(a) and (b) show the relationships between the RMS primary current and the circulating current was less than the
values of primary current and secondary current in one power internal short circuit current values. During the full time frame
cycle and the resistance when the incipient fault occurred of the case, the secondary current did not change much.
between the tenth and the 13th turns on the secondary winding. To investigate more characteristics of the arcing from trans-
Similarly, when was larger than 1 , the primary current was former incipient faults, the waveforms of the primary current
very close to the rated values and the transformer was in good were investigated in the frequency domain. Since the frequency
condition. When was less than 0.0001 , the primary current domain of the secondary current was dominated by 60 Hz com-
was approximately equal to the internal short circuit current and ponent, only the frequency characteristics of primary current
an internal short-circuit fault occurred in the transformer. When are discussed in this section. In addition, because the funda-
the value of increased from 0.0001 to 1 , the primary mental component, 60 Hz, is so large that other frequency com-
current decreased from the short circuit current to the rated cur- ponents are hardly seen, the primary current was filtered by a
rent. That shows an incipient fault occurred in the transformer. simulated digital 60 Hz notch filter before the FFT analysis was
Also, when the resistance decreased, i.e., the insulation was performed. In the simulation, the sampling rate was 3840 Hz. A
deteriorating, the secondary voltage and current decreased from 64-point FFT was performed over one power cycle.
their normal values. Fig. 12 shows the frequency spectrum of the primary current
at time of 0.025 s when parallel combination model was used
C. Incipient Fault With Aging and Arcing Models to simulate the incipient fault between the 15th and 55th turns
After the aging model and arcing model were implemented, on the primary winding. The waveforms in time domain for this
they were combined into a combination model for the insulation case were shown in Fig. 11. In this case, the insulation resistance

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on June 28,2022 at 01:12:24 UTC from IEEE Xplore. Restrictions apply.
WANG AND BUTLER: MODELING TRANSFORMERS WITH INTERNAL INCIPIENT FAULTS 505

(a)
(a)

(b)
(b)

(c) (c)

Fig. 10. Waveforms of E(t) and time sequences to control S1 and S2 for Fig. 11. Terminal currents and circulating current for the transformer with an
P15_55. (a) Waveform of E (t). (b) Time sequence to control S1. (c) Time incipient internal fault between the 15th and the 55th turns on primary winding
sequence to control S2. (R = 0.1 ). (a) Primary current. (b) Secondary current. (c) Circulating
current.

in the insulation model was 0.1 . The current harmonic compo-


nents were concentrated in the lower frequencies below 960 Hz.
Of these frequency components, the odd harmonics were the
dominant frequencies accounting for 29% of the total primary
current, respectively. The even harmonics comprised only 8%
of the primary current. The dc component comprised 6% of the
total primary current. The fundamental 60 Hz component in the
filtered primary current comprised only 4% of the total primary
current.
Similarly, the parallel combination model of the insulation
Fig. 12. Frequency analysis of primary current for the transformer with an
was used to model an incipient winding fault between the 10th incipient internal fault between the 15th and 55th turns on the primary winding
and 13th turns on the secondary winding. Fig. 13 shows the (R = 0.1 , t = 0:025 s).
waveforms of and time sequences to control switch S1 and
S2 in this case. primary winding and faulted turns. The secondary current de-
Fig. 14 presents waveforms of terminal currents and the cir- creased during arcing.
culating current when the resistance in the aging model was Fig. 15 shows the spectrum of the primary current at time of
0.1 and the dissipation factor is equal to 5.4 10 . At 0.025 s in the case shown in Fig. 14(a). In the scenario, a sec-
time s, the waveform shows no arcing. The insula- ondary incipient fault was simulated between the tenth and 13th
tion was in the aging phase so that the primary current and sec- turns with the insulation resistance of 0.1 . The spectrum
ondary current were higher than the normal rated current. At of the primary current shows that the third harmonic was the
the same time, a small circulating current flowed in the faulty dominant harmonic, accounting for approximately 25% of the
turns. During the arcing period, for instance, at time peak value of the total primary current at s. The spec-
s, the waveform shows large pulse currents flowed through the trum shown in Fig. 15 showed 39% was concentrated in the odd

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on June 28,2022 at 01:12:24 UTC from IEEE Xplore. Restrictions apply.
506 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002

(a) (a)

(b) (b)

(c)
Fig. 13. Waveforms of E(t) and time sequences to control S1 and S2 for
(c)
S10_13. (a) Waveform of E (t). (b) Time sequence to control S1. (c) Time Fig. 14. Terminal currents and circulating current for the transformer with an
sequence to control S2. incipient internal fault between the tenth and 13th turn on the secondary winding
(R = 0.1 ).
harmonics and 11% in the even harmonics. The remaining 50%
was the fundamental 60 Hz component which were filtered out
before the FFT analysis. Since the dc offset of the primary cur-
rent was small, the dc component in the spectrum was small.
Compared with the spectrum shown in Fig. 12, the percentage
of third harmonics shown in Fig. 12 is more distinct. This is be-
cause the deterioration levels of the insulation in the two cases
were different. When resistance was 0.1 W and the dissi-
pation factor was equal to 5.4 10 , the deterioration of
the insulation between tenth and 13th turns on the secondary
winding was not very severe. Thus, the primary current during Fig. 15. Frequency analysis of primary current for the transformer with an
arcing period is larger than that in nonarcing period. So the spec- incipient internal fault between tenth th and 13th turns on the secondary winding
trum shows a large third harmonics. However in the case shown (R = 0.1 , t = 0:025 s).
in Fig. 12, , was equal to 3 10 for the same . Thus the
deterioration of the insulation between 15th and 55th turns on of the experimental methodology for staging incipient faults is
the primary winding was very severe. This leads to the result that still ongoing. However, it was noticed at some point during the
the primary current during nonarcing period was larger than the short circuit field tests that the tests were conveying arcing phe-
primary current in arcing period. Therefore, the spectrum shows nomena. Recordings of the field experiments were analyzed for
a large fundamental component. the purpose of characterizing the incipient-like behaviors of the
transformers. The characteristics from the field tests were com-
D. Comparison With Incipient-Like Behavior During Field pared with the characteristics obtained from the simulations.
Experiments In the experiments, the transformer was supplied by a
Internal short circuit winding fault field experiments were single-phase lateral distribution line through a fuse and an oil
performed on the custom-built transformer at Texas A&M Uni- switch. Considering the excessive and dangerous levels of the
versity Downed Conductor Test Facility [20]. The development circulating current, the turns were shorted through a fuse. The

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on June 28,2022 at 01:12:24 UTC from IEEE Xplore. Restrictions apply.
WANG AND BUTLER: MODELING TRANSFORMERS WITH INTERNAL INCIPIENT FAULTS 507

Fig. 17. Frequency spectrum of the notch filtered primary current (t = 28:9 s).

(a)
At this point, a series of load and short circuit tests were per-
formed on two separate days to determine where the deterio-
rating insulation was located. During the load tests, contrary to
expectations, arcing-like phenomena appeared. Finally at some
point during tests on the third day, the transformer windings
burst out of the transformer casing during a turn-to-earth fault
between the 15th turn on the primary winding and ground.
The first fault scenario in which arcing apparently was
shown was a secondary short circuit fault between the tenth
and 13th turns, which represented the 95th field test. When
the experiment was performed, a smell was emitted by the
transformer winding, which was noticeable from the observa-
tion deck about 10 m from the transformer. The time domain
(b) waveforms of primary current, secondary current and circu-
lating current are plotted in Fig. 16(a)–(c), respectively. The
transformer was energized at about 5 s and the internal short
circuit fault was introduced at about 28.7 s. Fig. 16 shows the
waveforms in the time frame of [28.8, 29.2] s when arcing
was very active.
In the normal condition, the peak value of the primary cur-
rent should be around 5 A. If a solid, internal short circuit is
introduced between the tenth and 13th turns, the peak value of
the primary current should be about 30 A. However, in this case,
the peak value of the primary current was about 10 A. The wave-
form of unfiltered signal indicates the arcing discharge appeared
in some part of the transformer winding. Fig. 16(b) shows the
secondary current; in this case, the secondary current decreased
(c)
during the time when arcing occurred, which suggested the insu-
Fig. 16. Terminal currents for field test internal short circuit fault between lation on the secondary winding was degrading. The circulating
the tenth and 13th turns on the secondary winding. (a) Primary current.
(b) Secondary current. (c) Circulating current. current shown in Fig. 16(c) shows some characteristics similar
to the simulation results obtained from the incipient fault model
in Fig. 14(c). The random large current sparks indicate the in-
sulation in the transformer winding were in a degrading condi-
primary voltage, secondary voltage, secondary current, primary tion. Thus, some arcing discharge appeared in the transformer
current and circulating current were stepped down by potential winding and conveyed itself in the terminal currents and the cir-
transformers (PT), current transformers (CT), and an interface culating current. From the waveforms, it is supposed that the
box for monitoring by a computer acquisition system. deterioration of the insulation was in its beginning period since
Using the experimental setup in [21], 109 internal short cir- the primary current, secondary current were approximately the
cuit fault tests were performed over a two-year period. After 20 normal values and circulating current was almost zero in the
months and 94 internal short circuit fault tests, some phenomena nonarcing period.
appearing during the experiments indicated that the transformer Fig. 17 shows the FFT of one power cycle after the fault
was in the deteriorating condition. For instance, a buzzing sound for the primary current through a 60 Hz notch filter when
was heard in some experiments, a smell was noticeable, and arcing phenomena appeared between the tenth and 13th turns
arcing-like phenomena was observed in the waveforms of the on the secondary winding at time 28.9 s in Fig. 16. The result
recorded signals. This suggests that at some location or loca- shows that the notch filtered primary current was composed of
tions in the transformer, the insulation was severely degraded. frequency components below 360 Hz. Of the low-frequency

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on June 28,2022 at 01:12:24 UTC from IEEE Xplore. Restrictions apply.
508 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002

current harmonics components, the third harmonic comprised ACKNOWLEDGMENT


45% of the magnitude of the notch-filtered primary current.
The small dc component in the spectrum matched the small dc The authors highly appreciate P. Palmer-Buckle for providing
offset in the primary current. The frequency spectrum shows the experimental results and ANSOFT technical support per-
that 55% of the notch filtered primary current was concentrated sonnel, M. Christini, for his assistance.
in the odd harmonics and 6% in the even harmonics comprised
The percentage of odd harmonics was much larger than the
even harmonics. This characteristic matched the simulation REFERENCES
result shown in Fig. 15.
[1] C. E. Lin, J. M. Ling, and C. L. Huang, “Expert system for transformer
The analysis of the experimental results [21] shows that fault diagnosis using dissolved gas analysis,” IEEE Trans. Power Del.,
when the insulation was deteriorating to some point, arcing vol. 8, pp. 231–238, Jan. 1993.
phenomena would appear and could be monitored in the [2] W. Yue, H. Zhuxiao, and Z. Jiaxiang, “Expediting cellulose insulation
aging evaluation and life prediction thorough degree of polymerization
primary current, secondary current and circulating current. measurements,” in Proc. 3rd Int. Conf. Properties Appl. Dielectric Ma-
The waveforms in time domain showed that arcing current terials, 1988, pp. 328–331.
composed of two periods, arcing burning period and arcing [3] A. Noro, K. Nakamura, T. Watanabe, and T. Morita, “Acoustic-based
extinction period. During the burning period, big current sparks real-time partial discharge location in model transformer,” in Proc. IC-
SPAT, pp. 1077–1082.
often occurred in the primary current and circulating current. [4] J. Bak-Jensen, B. Bak-Jensen, and S. D. Mikkelsen, “Detection of faults
The magnitudes of arcing currents were less than the values of and aging phenomena in transformers by transfer functions,” IEEE
current during internal short circuit faults. During the extinction Trans. Power Del., vol. 10, pp. 308–314, Jan. 1995.
[5] P. Bastard, P. Bertrand, and M. Meunier, “A transformer model for
period, the circulating current was close to zero and primary winding fault studies,” IEEE Trans. Power Del., vol. 9, pp. 690–699,
current was close to the normal current. In the frequency Mar. 1994.
domain, the frequency components were concentrated in the [6] A. Guzman, D. Hou, and S. E. Zocholl, “Transformer modeling as ap-
low frequencies below 960 Hz. In the harmonic components, plied to differential protection,” in Proc. Can. Conf. Elect. Comput. Eng.,
vol. 1, 1996, pp. 108–114.
the percentage of odd harmonics was larger than that of even [7] H. Wang and K. L. Butler, “Modeling transformer with internal winding
harmonics as shown in Fig. 15. The results from the simulations faults by calculating leakage factors,” in Proc. 31st North Amer. Power
using the internal incipient fault model presented in this paper Symp., San Luis Obispo, CA, Oct. 1999, pp. 176–182.
[8] H. Wang, P. Palmer-Buckle, and K. L. Butler, “Transformer models for
showed similar characteristics. detection of incipient internal winding faults,” in Proc. 30th North Amer.
Power Symp., Cleveland, OH, Oct. 1998, pp. 90–98.
[9] H. Wang and K. L. Butler, “Finite element analysis of internal winding
V. CONCLUSIONS faults in distribution transformers,” IEEE Trans. Power Del., vol. 16, pp.
422–427, July 2001.
[10] J. Hong, Y. Lee, K. Kim, H. Shin, and S. Kim, “Dielectric characteristics
This paper presented a new transformer model to simulate an on insulation oil due to the aging by electron beam irradiation,” in Proc.
internal incipient winding fault. The new transformer model was Fifth Int. Conf. Properties Appl. Dielectric Materials, vol. 1, 1997, pp.
implemented by combining deteriorating insulation model with 170–173.
a finite element analysis internal short circuit fault model. The [11] G. Yilmaz and O. Kalenderli, “Dielectric properties of aged polyester
films,” in Annu. Rep. IEEE Conf. Elect. Insul. Dielect. Phenomena, vol.
new deteriorating insulation model, which includes an aging 2, 1997, pp. 444–446.
model and an arcing model, was developed based on the phys- [12] B. Fatmi, A. Bui, C. Boisdon, and P. Vuarchex, “PPS electrical properties
ical behavior of aging insulation and the arcing phenomena oc- for power transformers,” IEEE Trans. Dielect. Elect. Insul., vol. 5, pp.
618–621, July 1998.
curring when the insulation was severely damaged. The aging [13] R. Bartnikas, “Engineering dielectrics volume II B—Electrical proper-
model and the arcing model of the insulation were connected in ties of solid insulating materials: Measurement techniques,” , Philadel-
parallel to produce a parallel combination insulation model. The phia, PA, Special Tech. Pub. 926, 1987.
[14] N. H. Malik, A. A. Al-Arainy, and M. I. Qureshi, Electrical Insulation
parallel combination insulation model was combined with the in Power Systems. New York: Marcel Dekker, 1998.
internal short circuit model to predict the terminal voltages and [15] J. P. Bellomo, A. Baye, and T. Lebey, “Ageing properties of polyimide
currents of the transformer under various incipient fault condi- and polyester films: Experimental results and discussion,” in Conf. Rec.
tions. The characteristics of the terminal currents and circulating IEEE Int. Symp. Elect. Insul., vol. 1, 1998, pp. 177–180.
[16] J. P. Bellomo, T. Lebey, J. M. Oraison, and F. Peltier, “Study of the
current in the faulted winding were analyzed in time domain and ageing of different dielectrics under specific electrical constraints,” in
frequency domain. Proc. Fourth Int. Conf. Properties Appl. Dielect. Materials, vol. 2, 1994,
Some incipient-like fault cases obtained from internal short pp. 796–799.
[17] R. H. Lee, “The other electrical hazard: Electric arc blast burns,” IEEE
circuit field tests were also analyzed in time domain and Trans. Ind. Applicat., vol. IA-18, pp. 246–251, May 1982.
frequency domain. The comparisons between the incipient-like [18] O. R. Schurig, “Fault voltage drop and impedance at short-circuit cur-
fault experimental test cases and simulation results showed rents in low-voltage circuits,” AIEE Trans., vol. 60, pp. 479–487, 1941.
that terminal behaviors of the faulted transformer obtained [19] T. Gammon and J. Matthews, “The historical evolution of arcing-fault
models for low-voltage systems,” in Proc. IEEE Ind. Commercial Power
from the field tests show some similar characteristics to those Syst. Tech. Conf., 1999, pp. 1–6.
from simulations using the parallel combination model. In [20] H. Wang, “Models for short circuit and incipient internal faults in single-
future work, the incipient fault transformer model will be used phase distribution transformers,” Ph.D. dissertation, Texas A&M Univ.,
College Station, TX, May 2001.
to generate a database of incipient internal winding faults in
[21] P. Palmer-Buckle, “A Methodology for experimentally verifying simu-
distribution transformers for the development of intelligent lation models for distribution transformer internal faults,” M.S. thesis,
transformer fault detection techniques. Texas A&M Univ., College Station, Dec. 1998.

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on June 28,2022 at 01:12:24 UTC from IEEE Xplore. Restrictions apply.
WANG AND BUTLER: MODELING TRANSFORMERS WITH INTERNAL INCIPIENT FAULTS 509

Hang Wang (S’97) received the B.S. and M.S. degrees from Tsinghua Univer- Karen L. Butler (SM’02) received the B.S. degree from Southern University,
sity, Beijing, China, in 1994 and 1997, respectively, and the Ph.D. degree from Baton Rouge, LA, in 1985, the M.S. degree from the University of Texas, Austin,
the Department of Electrical Engineering, Texas A&M University, College Sta- in 1987, and the Ph.D. degree from Howard University, Washington, DC, in
tion, in May 2001. 1994, all in electrical engineering.
She is currently a Research Assistant with the Power System Automation She is an Assistant Professor with the Department of Electrical Engineering,
Laboratory at Texas A&M. Her research focuses on incipient fault detection in Texas A&M University, College Station. From 1988 to 1989, she was a Member
single-phase, distribution transformers. of Technical Staff at Hughes Aircraft Co., Culver City, CA. Her research focuses
Dr. Wang is a student member of the IEEE Power Engineering Society. on the areas of computer and intelligent systems applications in power, power
distribution automation, and modeling and simulation of power systems and
vehicles.
Dr. Butler received an NSF Early Career Award in 1996 and an Office of
Naval Research Young Investigator Award in 1999. She is a member of the IEEE
Power Engineering Society and the Louisiana Engineering Society. She is a Reg-
istered Professional Engineer in the states of Louisiana, Texas, and Mississippi.

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on June 28,2022 at 01:12:24 UTC from IEEE Xplore. Restrictions apply.

You might also like