Thyristor switched

capacitors banks
Thyristor switched capacitor banks
with high-speed switching capability
are designed to support the supply
voltage of distribution systems and
to correct the power factor of
connected loads.

Thyristor switches are resistant to


mechanical wear, operate without
noise, and are capable of practically
transient-free switching.

Control signals can be transmitted


to the capacitor bank straight from
the loads, which means power factor
correction with minimal delay.

The minimum time the control unit


needs for switching all the steps of
the capacitor bank on or off is the
period of only one cycle.

Each step of the capacitor bank


consists of a capacitor and a reactor
connected in series. These two form
a series resonant circuit tuned at a
frequency below the lowest harmonic
frequency present in the system.

The capacitor bank is selected


according to the desired control
method, the amount of reactive
power to be compensated, and the
connected loads. The loads can be
symmetrical or asymmetrical, and
they can be connected to the main
voltage or phase voltages.
Load controlled Capacitor banks controlled
capacitor banks by reactive power
A high-powered machine with rapidly changing Thyristor-switched capacitor banks are capable
load, such as a welding machine, causes drops of swift power factor correction of machines with
in the supply voltage. The amount of such a drop highly variable load, such as lift and crane drives.
depends on the output power of the machine Using thyristors instead of contactors gives a
and on the short-circuit power of the distribution higher switching speed and saves the work
network. A drop in the secondary voltage is caused by service and replacement of quickly
reflected in the primary voltage, causing the wearing contactors.
quality of the distribution voltage to deteriorate
The control system switches the capacitor bank
everywhere in the transformer circuit.
steps on and off according to the demand of
The effects of a voltage drop on a distribution reactive power. The control is based on a kind
network are proportioned to the amount of the of "first-in last-out" principle: the first step is
drop and to the frequency of its occurence. switched on first and switched off last. The
A thyristor-switched capacitor bank suppresses minimum time the control system needs to switch
these effects to a great extent, ensuring that the all the steps of the capacitor bank on or off is
distribution voltage conforms to the standards in as short as the one network period.
this respect.
Supporting and stabilizing the supply voltage, a
thyristor-switched capacitor bank decreases the
energy consumption of production equipment 20kV SK=73MVA
and thus increases their capacity.
To achieve the best possible results in the power 2000kVA
factor correction of high-speed welding machines, ZK=5,8%
SK=23MVA
control signals are sent to the capacitor bank 400V 50Hz
straight from the machines. The power factor
correction from the capacitor bank is pre-selected
according to the demand of reactive power.
Control

The required power factor correction is Crane


given by
Q = SK *ΔU(%)

where Fig. 2.
U = voltage drop at load connecting point Capacitor bank controlled by reactive power
SK = short-circuit power at load connecting point
Q = required power factor correction
TECHNICAL DATA
20kV SK=73MVA Network voltage: 400…690 V
Step power: 50…450 kvar
2000kVA Cubicle size: W * D * H (mm)
ZK=5,8%
SK=23MVA 1200*600*2000 / 450 kvar
400V 50Hz
Protection class: IP20C
Control unit:
• Number of steps 6 (capacitor banks with
measuring system)
Control

Welding
machine Direct control N/A
90 times/min • Installation Inside of capacitor bank

Fig. 1. Load controlled capacitor bank


EN-LV12-06/2006