Electrical Industries Co. Ltd.

INSPECTION AND TEST RECORD


Description: Contract no.: Customer Ref .No
FLAG RELAY – RXSF1 4400006595 -
Customer: End Client: Sheet:
SEC-COA SEC-COA Page 1 of 2

Site: Location #: Project name:


SS 7707 ,AL KHARJ 13.8 KV SWG Protection modifaction of 13.8KV Switchgear

GENERAL DATA AND INFORMATION:

Panel Designation : H1 Relay Designation : +D1-74DC

Manufacturer : ABB Rated Voltage : 48 VDC

Relay Type : RK 271019- AH S. No : N/A

No of contact per coil : 2NC -1 NO Per coil

1. MECHANICAL CHECK AND VISUAL INSPECTION :


ITEM DESCRIPTION CHECKED
1 Inspect for physical damage / defects. Ok
2 Verify connections as per approved drawings. Ok
3 Check tightness of all connections. Ok
4 Check Ferrules Ok
5 Check apparatus lists Ok

2.ELECTRICAL TESTS :
ITEM DESCRIPTION CHECKED
1 Flag Operation checked. Ok
2 ALL contacts checked. Ok
3 All output contacts resistance measured Ok

2.1 Pick up and drop-off test :


Terminal Pick-up Current Drop-out Current
Coil Remarks
no Voltage (V) (mA) Voltage (V) (mA)
A 11-12 19.0 9.5 6.3 3 OK
B 21-22 17.5 8.5 5.3 2.6 OK
NOTE: USER MANUAL 1MRK 508 015-BEN Page 10
• Pickup voltage is < 80 % of Ur
• Drop-out voltage is > 5% of Ur

2.2.Operation Time at Rated Voltage :


COMPANY ABB Electrical Industries CO.LTD SEC – COA
NAME M.ABDULLAH
SIGNATURE
DATE
TEST EQUIPMENT USED: Sverker 750
Rxsf1 Page 1 of 2
Electrical Industries Co. Ltd. INSPECTION AND TEST RECORD
Description: Contract no.: Customer Ref .No
FLAG RELAY – RXSF1 4400006595 -
Customer: End Client: Sheet:
SEC-COA SEC-COA Page 2 of 2

Site: Location #: Project name:


SS 7707 ,AL KHARJ 13.8 KV SWG Protection modifaction of 13.8KV Switchgear

Operating Operating
Terminal
Coil Time for Pick- up (mS) Time for Drop-out (mS)
no
Make Break Make Break
13-14 21 - - 6
Coil 1
15-16 - 15 6 -
23-24 18 - - 7
Coil 2
25-26 - 14 7 -
NOTE: USER MANUAL 1MRK 508 015-BEN Page 10
Pick-up time typical values make/break contact: 30/20 ms
Drop-out time typical values make/break contact: 5/10 ms

2.3.Power consumption:
Resistance
Coil Voltage (V) Current (mA) Power(watt)
(kΩ)
A 48 23.1 1.1 2.01
B 48 23.2 1.1 2.00
Note USER MANUAL 1MRK 508 015-BEN Page 11
Power consumption at U = Ur : 1,1-1,3 W

2.4 Contact resistance:


Coil Terminal no Contact Resistance (Ω)
A 13-14 0.2
A 15-16 0.2
A 17-18 0.2
B 23-24 0.2
B 25-26 0.2
B 27-28 0.2

COMPANY ABB Electrical Industries CO.LTD SEC – COA


NAME M.ABDULLAH
SIGNATURE
DATE
TEST EQUIPMENT USED: Sverker 750