Professional Documents
Culture Documents
DATE :
DRG.NO.: PH10-1B-43-35-1112
DATE :
DRG.NO.: PH10-1B-43-35-1112
1 K94310 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94310 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94310 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94310 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94310 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94310 in 4
Position
Check Continuity at X511: 7-8 Spare Checked OK
Check Continuity at X511: 9-10 Spare Checked OK
Check Continuity at X511: 12-14 Load Shedding Trip to A310 Checked OK
2 K94330 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94330 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94330 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94330 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94330 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94330 in 4
Position
Check Continuity at X511: 15-16 Spare Checked OK
Check Continuity at X511: 17-18 Spare Checked OK
Check Continuity at X511: 20-22 Load Shedding Trip to A330 Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
3 K94350 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94350 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94350 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94350 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94350 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94350 in 4
Position
Check Continuity at X511: 23-24 Spare Checked OK
Check Continuity at X511: 25-26 Spare Checked OK
Check Continuity at X511: 28-30 Load Shedding Trip to A350 Checked OK
4 K94370 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94370 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94370 in 1A
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94370 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94370 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94370 in 4
Position
Check Continuity at X511: 31-32 Spare Checked OK
Check Continuity at X511: 33-34 Spare Checked OK
Check Continuity at X511: 36-38 Load Shedding Trip to A370 Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
5 K94390 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94390 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94390 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94390 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94390 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94390 in 4
Position
Check Continuity at X511: 39-40 Spare Checked OK
Check Continuity at X511: 41-42 Spare Checked OK
Check Continuity at X511: 44-46 Load Shedding Trip to A390 Checked OK
6 K94410 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94410 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94410 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94410 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94410 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94410 in 4
Position
Check Continuity at X511: 47-48 Spare Checked OK
Check Continuity at X511: 49-50 Spare Checked OK
Check Continuity at X511: 52-54 Load Shedding Trip to A410 Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
7 K94430 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94430 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94430 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94430 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94430 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94430 in 4
Position
Check Continuity at X511: 55-56 Spare Checked OK
Check Continuity at X511: 57-58 Spare Checked OK
Check Continuity at X511: 60-62 Load Shedding Trip to A430 Checked OK
8 K94450 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94450 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94450 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94450 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94450 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94450 in 4
Position
Check Continuity at X511: 63-64 Spare Checked OK
Check Continuity at X511: 65-66 Spare Checked OK
Check Continuity at X511: 68-70 Load Shedding Trip to A450 Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
9 K94470 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94470 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94470 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94470 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94470 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94470 in 4
Position
Check Continuity at X511: 71-72 Spare Checked OK
Check Continuity at X511: 73-74 Spare Checked OK
Check Continuity at X511: 76-78 Load Shedding Trip to A470 Checked OK
10 K94490 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94490 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94490 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94490 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94490 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94490 in 4
Position
Check Continuity at X511: 163-164 Spare Checked OK
Check Continuity at X511: 165-166 Spare Checked OK
Check Continuity at X511: 168-170 Load Shedding Trip to A490 Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
11 K94320 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94320 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94320 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94320 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94320 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94320 in 4
Position
Check Continuity at X511: 79-80 Spare Checked OK
Check Continuity at X511: 81-82 Spare Checked OK
Check Continuity at X511: 84-86 Load Shedding Trip to A320 Checked OK
12 K94340 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94340 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94340 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94340 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94340 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94340 in 4
Position
Check Continuity at X511: 87-88 Spare Checked OK
Check Continuity at X511: 89-90 Spare Checked OK
Check Continuity at X511: 92-94 Load Shedding Trip to A340 Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
13 K94360 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94360 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94360 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94360 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94360 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94360 in 4
Position
Check Continuity at X511: 95-96 Spare Checked OK
Check Continuity at X511: 97-98 Spare Checked OK
Check Continuity at X511: 100-102 Load Shedding Trip to A360 Checked OK
14 K94380 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94380 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94380 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94380 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94380 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94380 in 4
Position
Check Continuity at X511: 103-104 Spare Checked OK
Check Continuity at X511: 105-106 Spare Checked OK
Check Continuity at X511: 108-110 Load Shedding Trip to A380 Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
15 K94400 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94400 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94400 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94400 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94400 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94400 in 4
Position
Check Continuity at X511: 111-112 Spare Checked OK
Check Continuity at X511: 113-114 Spare Checked OK
Check Continuity at X511: 116-118 Load Shedding Trip to A400 Checked OK
16 K94420 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94420 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94420 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94420 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94420 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94420 in 4
Position
Check Continuity at X511: 119-120 Spare Checked OK
Check Continuity at X511: 121-122 Spare Checked OK
Check Continuity at X511: 124-126 Load Shedding Trip to A420 Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
17 K94440 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94440 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94440 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94440 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94440 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94440 in 4
Position
Check Continuity at X511: 127-128 Spare Checked OK
Check Continuity at X511: 129-130 Spare Checked OK
Check Continuity at X511: 132-134 Load Shedding Trip to A440 Checked OK
18 K94460 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94460 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94460 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94460 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94460 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94460 in 4
Position
Check Continuity at X511: 135-136 Spare Checked OK
Check Continuity at X511: 137-138 Spare Checked OK
Check Continuity at X511: 140-142 Load Shedding Trip to A460 Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
19 K94480 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94480 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94480 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94480 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94480 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94480 in 4
Position
Check Continuity at X511: 143-144 Spare Checked OK
Check Continuity at X511: 145-146 Spare Checked OK
Check Continuity at X511: 148-150 Load Shedding Trip to A480 Checked OK
20 K94500 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94500 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94500 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94500 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94500 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94500 in 4
Position
Check Continuity at X511: 171-172 Spare Checked OK
Check Continuity at X511: 173-174 Spare Checked OK
Check Continuity at X511: 176-178 Load Shedding Trip to A500 Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
DATE :
DRG.NO.: PH10-1B-43-35-1112
DATE :
DRG.NO.: PH10-1B-43-35-1112
DATE :
DRG.NO.: PH10-1B-43-35-1112
DATE :
DRG.NO.: PH10-1B-43-35-1112
DATE :
DRG.NO.: PH10-1B-43-35-1112
DATE :
DRG.NO.: PH10-1B-43-35-1112
DATE :
DRG.NO.: PH10-1B-43-35-1112
DATE :
DRG.NO.: PH10-1B-43-35-1112
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
1 Relay : F811
7SJ621 Binary Outputs Operate BO from DIGSI & Check at
BO 1 Check Continuity at X511 : 5-6 Spare Checked OK
BO 2 Put all Switch in Stage-4 Local Stage-4 Load Shed Checked OK
Position with S811 in Service
and Check Pickup of all Relays/
BO 3 & 4 Spare
BO 5 Put all Switch in Stage-1A Local Stage-1A Load Shed Checked OK
Position with S811 in Service
and Check Pickup of all Relays/
BO 6 Put all Switch in Stage-1 Local Stage-1 Load Shed Checked OK
Position with S811 in Service
and Check Pickup of all Relays/
BO 7 Put all Switch in Stage-2 Local Stage-2 Load Shed Checked OK
Position with S811 in Service
and Check Pickup of all Relays/
BO 8 Put all Switch in Stage-3 Local Stage-3 Load Shed Checked OK
Position with S811 in Service
and Check Pickup of all Relays/
2 Relay : A201
6MD613 Binary Outputs Operate BO from DIGSI & Check at
BO 1 to 53 Spare
3 Relay : A202
6MD613 Binary Outputs Operate BO from DIGSI & Check at
BO 1 to 53 Spare
DATE :
DRG.NO.: PH10-1B-43-35-1112
1 Relay : F811
7SJ621 BI Power up the relay & Inject variable DC voltage to relay BI terminal
BI 2 F15-F16 Threshold voltage >= 65V Checked OK
BI 3 F17-F18 Threshold voltage >= 65V Checked OK
BI 6 R11-R13 Threshold voltage >= 65V Checked OK
BI 8 R7-R8 Threshold voltage >= 65V Checked OK
2 Relay : A201
6MD613 BI Power up the relay & Inject variable DC voltage to relay BI terminal
BI 1 F10-F14 Threshold voltage >= 65V Checked OK
BI 10 H17-G12 Threshold voltage >= 65V Checked OK
BI 20 G9-G12 Threshold voltage >= 65V Checked OK
BI 30 J4-J12 Threshold voltage >= 65V Checked OK
BI 40 M17-L12 Threshold voltage >= 65V Checked OK
BI 50 L9-L12 Threshold voltage >= 65V Checked OK
BI 60 N4-N12 Threshold voltage >= 65V Checked OK
BI 70 R17-Q12 Threshold voltage >= 65V Checked OK
BI 80 Q9-Q12 Threshold voltage >= 65V Checked OK
3 Relay : A202
6MD613 BI Power up the relay & Inject variable DC voltage to relay BI terminal
BI 1 F10-F14 Threshold voltage >= 65V Checked OK
BI 10 H17-G12 Threshold voltage >= 65V Checked OK
BI 20 G9-G12 Threshold voltage >= 65V Checked OK
BI 30 J4-J12 Threshold voltage >= 65V Checked OK
BI 40 M17-L12 Threshold voltage >= 65V Checked OK
BI 50 L9-L12 Threshold voltage >= 65V Checked OK
BI 60 N4-N12 Threshold voltage >= 65V Checked OK
BI 70 R17-Q12 Threshold voltage >= 65V Checked OK
BI 80 Q9-Q12 Threshold voltage >= 65V Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
Sr.
Test carried out for Test Description Test Result /Remark
No.
DATE :
DRG.NO.: PH10-1B-43-35-1112
Sr.
Test carried out for Test Description Test Result /Remark
No.
1 Operation test for F811(7SJ621) Stage FSET (Hz) TSET (sec) TOPTD (sec)
Inject 3 ph 110VAC, Change
frequency and Operate different 1A 49.80 10.0
stages Only feeders on Stage 1A were tripped Checked OK
1 49.60 5.0
Only feeders on Stage 1 were tripped Checked OK
2 49.40 3.0
Only feeders on Stage 2 were tripped Checked OK
3 49.20 2.0
Only feeders on Stage 3 were tripped Checked OK
4 49.0 0.0
Only feeders on Stage 4 were tripped Checked OK
DATE :
DRG.NO.: PH10-1B-43-35-1112
1 DC-1/2 Supply Fail /BCU unhealthy Short A201(F3-F4) / X239: 1,2-3,4 Checked OK
I/O BOX DC-1/2 MCB trip Short A202(F3-F4) /
Switch OFF MCB F133 /
Switch OFF MCB F134