You are on page 1of 35

ANNEXURE - A: DC AND AC CIRCUIT CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test Result /


Test carried out for Test Description
No. Remark

1 Apply 110V DC Supply (Source-1) Apply 110V DC at X110: 1,2 - 3,4


Check Pickup of K131 Picked up OK
Switch ON MCB F132 Check Voltage at F811(F1-F2) Checked OK
Switch ON MCB F133 Check Voltage at I/O Box-1 of A201(F1-F2) Checked OK
Switch ON MCB F134 Check Voltage at I/O Box-2 of A202(F1-F2) Checked OK

2 Apply 110V DC Supply (Source-2) Apply 110V DC at X120: 1,2 - 3,4


Open Link X110: 1&3
Check Reset of K131 Reseted OK
Switch ON MCB F132 Check Voltage at F811(F1-F2) Checked OK
Switch ON MCB F133 Check Voltage at I/O Box-1 of A201(F1-F2) Checked OK
Switch ON MCB F134 Check Voltage at I/O Box-2 of A202(F1-F2) Checked OK

3 Apply 230V AC Supply Apply 1 ph 230V AC at X100: 3,4-7,8,9


Switch ON MCB F101
Space Heater Check Voltage Checked OK
Power Socket Check Voltage Checked OK
Cubicle Illumination lamp Check Illumination Checked OK

KAHRAMAA LI SIEMENS LTD


ANNEXURE - B: AUXILIARY RELAYS CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function Test Result / Remark
No. out for

1 K94310 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94310 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94310 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94310 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94310 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94310 in 4
Position
Check Continuity at X511: 7-8 Spare Checked OK
Check Continuity at X511: 9-10 Spare Checked OK
Check Continuity at X511: 12-14 Load Shedding Trip to A310 Checked OK

2 K94330 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94330 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94330 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94330 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94330 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94330 in 4
Position
Check Continuity at X511: 15-16 Spare Checked OK
Check Continuity at X511: 17-18 Spare Checked OK
Check Continuity at X511: 20-22 Load Shedding Trip to A330 Checked OK

KAHRAMAA LI SIEMENS LTD


ANNEXURE - B: AUXILIARY RELAYS CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function Test Result / Remark
No. out for

3 K94350 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94350 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94350 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94350 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94350 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94350 in 4
Position
Check Continuity at X511: 23-24 Spare Checked OK
Check Continuity at X511: 25-26 Spare Checked OK
Check Continuity at X511: 28-30 Load Shedding Trip to A350 Checked OK

4 K94370 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94370 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94370 in 1A
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94370 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94370 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94370 in 4
Position
Check Continuity at X511: 31-32 Spare Checked OK
Check Continuity at X511: 33-34 Spare Checked OK
Check Continuity at X511: 36-38 Load Shedding Trip to A370 Checked OK

KAHRAMAA LI SIEMENS LTD


ANNEXURE - B: AUXILIARY RELAYS CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function Test Result / Remark
No. out for

5 K94390 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94390 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94390 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94390 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94390 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94390 in 4
Position
Check Continuity at X511: 39-40 Spare Checked OK
Check Continuity at X511: 41-42 Spare Checked OK
Check Continuity at X511: 44-46 Load Shedding Trip to A390 Checked OK

6 K94410 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94410 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94410 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94410 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94410 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94410 in 4
Position
Check Continuity at X511: 47-48 Spare Checked OK
Check Continuity at X511: 49-50 Spare Checked OK
Check Continuity at X511: 52-54 Load Shedding Trip to A410 Checked OK

KAHRAMAA LI SIEMENS LTD


ANNEXURE - B: AUXILIARY RELAYS CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function Test Result / Remark
No. out for

7 K94430 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94430 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94430 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94430 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94430 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94430 in 4
Position
Check Continuity at X511: 55-56 Spare Checked OK
Check Continuity at X511: 57-58 Spare Checked OK
Check Continuity at X511: 60-62 Load Shedding Trip to A430 Checked OK

8 K94450 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94450 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94450 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94450 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94450 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94450 in 4
Position
Check Continuity at X511: 63-64 Spare Checked OK
Check Continuity at X511: 65-66 Spare Checked OK
Check Continuity at X511: 68-70 Load Shedding Trip to A450 Checked OK

KAHRAMAA LI SIEMENS LTD


ANNEXURE - B: AUXILIARY RELAYS CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function Test Result / Remark
No. out for

9 K94470 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94470 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94470 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94470 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94470 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94470 in 4
Position
Check Continuity at X511: 71-72 Spare Checked OK
Check Continuity at X511: 73-74 Spare Checked OK
Check Continuity at X511: 76-78 Load Shedding Trip to A470 Checked OK

10 K94490 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94490 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94490 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94490 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94490 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94490 in 4
Position
Check Continuity at X511: 163-164 Spare Checked OK
Check Continuity at X511: 165-166 Spare Checked OK
Check Continuity at X511: 168-170 Load Shedding Trip to A490 Checked OK

KAHRAMAA LI SIEMENS LTD


ANNEXURE - B: AUXILIARY RELAYS CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function Test Result / Remark
No. out for

11 K94320 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94320 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94320 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94320 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94320 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94320 in 4
Position
Check Continuity at X511: 79-80 Spare Checked OK
Check Continuity at X511: 81-82 Spare Checked OK
Check Continuity at X511: 84-86 Load Shedding Trip to A320 Checked OK

12 K94340 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94340 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94340 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94340 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94340 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94340 in 4
Position
Check Continuity at X511: 87-88 Spare Checked OK
Check Continuity at X511: 89-90 Spare Checked OK
Check Continuity at X511: 92-94 Load Shedding Trip to A340 Checked OK

KAHRAMAA LI SIEMENS LTD


ANNEXURE - B: AUXILIARY RELAYS CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function Test Result / Remark
No. out for

13 K94360 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94360 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94360 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94360 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94360 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94360 in 4
Position
Check Continuity at X511: 95-96 Spare Checked OK
Check Continuity at X511: 97-98 Spare Checked OK
Check Continuity at X511: 100-102 Load Shedding Trip to A360 Checked OK

14 K94380 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94380 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94380 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94380 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94380 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94380 in 4
Position
Check Continuity at X511: 103-104 Spare Checked OK
Check Continuity at X511: 105-106 Spare Checked OK
Check Continuity at X511: 108-110 Load Shedding Trip to A380 Checked OK

KAHRAMAA LI SIEMENS LTD


ANNEXURE - B: AUXILIARY RELAYS CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function Test Result / Remark
No. out for

15 K94400 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94400 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94400 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94400 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94400 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94400 in 4
Position
Check Continuity at X511: 111-112 Spare Checked OK
Check Continuity at X511: 113-114 Spare Checked OK
Check Continuity at X511: 116-118 Load Shedding Trip to A400 Checked OK

16 K94420 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94420 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94420 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94420 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94420 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94420 in 4
Position
Check Continuity at X511: 119-120 Spare Checked OK
Check Continuity at X511: 121-122 Spare Checked OK
Check Continuity at X511: 124-126 Load Shedding Trip to A420 Checked OK

KAHRAMAA LI SIEMENS LTD


ANNEXURE - B: AUXILIARY RELAYS CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function Test Result / Remark
No. out for

17 K94440 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94440 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94440 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94440 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94440 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94440 in 4
Position
Check Continuity at X511: 127-128 Spare Checked OK
Check Continuity at X511: 129-130 Spare Checked OK
Check Continuity at X511: 132-134 Load Shedding Trip to A440 Checked OK

18 K94460 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94460 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94460 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94460 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94460 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94460 in 4
Position
Check Continuity at X511: 135-136 Spare Checked OK
Check Continuity at X511: 137-138 Spare Checked OK
Check Continuity at X511: 140-142 Load Shedding Trip to A460 Checked OK

KAHRAMAA LI SIEMENS LTD


ANNEXURE - B: AUXILIARY RELAYS CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function Test Result / Remark
No. out for

19 K94480 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94480 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94480 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94480 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94480 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94480 in 4
Position
Check Continuity at X511: 143-144 Spare Checked OK
Check Continuity at X511: 145-146 Spare Checked OK
Check Continuity at X511: 148-150 Load Shedding Trip to A480 Checked OK

20 K94500 Pickup Short F811 (R1-R3) with S811 Stage-1A Load Shedding Picked up OK
in Service & Put SW S94500 in 1A
Position
Short F811 (R3-R2) with S811 Stage-1 Load Shedding Picked up OK
in Service & Put SW S94500 in 1
Position
Short F811 (R4-R5) with S811 Stage-2 Load Shedding Picked up OK
in Service & Put SW S94500 in 2
Position
Short F811 (R5-R6) with S811 Stage-3 Load Shedding Picked up OK
in Service & Put SW S94500 in 3
Position
Short F811 (F8-F9) with S811 Stage-4 Load Shedding Picked up OK
in Service & Put SW S94500 in 4
Position
Check Continuity at X511: 171-172 Spare Checked OK
Check Continuity at X511: 173-174 Spare Checked OK
Check Continuity at X511: 176-178 Load Shedding Trip to A500 Checked OK

KAHRAMAA LI SIEMENS LTD


ANNEXURE - C : NUMERICAL RELAY BINARY INPUT CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function
No. out for

Switch ON MCB F135


1 Relay: F811 Details:
MLFB : 7SJ6211-5EB90-1FC0+L0S
Sr.No.: BF1309514692

BI 1 Put Switch S810 in OUT Load Shedding Block /


Position / VT selection S/W in OFF
Put Switch S66 in OFF Position position
BI 2 Spare
BI 3 Insert Test Handle Load Shedding Relay Test Block
at S811 in Test Position.
BI 4 Put Switch S66 in VT 1 Bus VT 1 "IN" position
Position.
BI 5 Put Switch S66 in VT 2 Bus VT 2 "IN" position
Position.
BI 6 Short X511: 2-4 Spare
BI 7 Switch OFF MCB F135 Load Shedding Relay BI DC
Supply Fail
BI 8 Switch OFF MCB F101 AC MCB Trip

2 Relay: A201 Details:


MLFB : 6MD6130-4FB90-0AA0+L0S
Sr.No.: BF1309516157

BI 1 Switch OFF MCB F132 / Load Shedding Relay Unhealthy /


Short F811(F3-F5) MCB Trip
BI 2 Spare
BI 3 Switch OFF MCB F135 LSP Trip Relay/LSP Relay BI
MCB Trip/OFF
BI 4 S94310 Switch in OFF Position LSP Selector Switch on OFF
Position
BI 5 S94310 Switch in 1A Position Load Shedding Stage-1A
Selected for A310
BI 6 S94310 Switch in Stage-1 Load Shedding Stage-1
Position Selected for A310
BI 7 S94310 Switch in Stage-2 Load Shedding Stage-2
Position Selected for A310
BI 8 S94310 Switch in Stage-3 Load Shedding Stage-3
Position Selected for A310

KAHRAMAA LI SIEMENS LTD


ANNEXURE - C : NUMERICAL RELAY BINARY INPUT CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function
No. out for

BI 9 S94310 Switch in Stage-4 Load Shedding Stage-4


Position Selected for A310
BI 10 Short K94310(9-11) Load Shedding Trip Relay Optd.
BI 11 S94330 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 12 S94330 Switch in 1A Position Load Shedding Stage-1A
Selected for A330
BI 13 S94330 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A330
BI 14 S94330 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A330
BI 15 S94330 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A330
BI 16 S94330 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A330
BI 17 Short K94330(9-11) Load Shedding Trip Relay Optd.
BI 18 S94350 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 19 S94350 Switch in 1A Position Load Shedding Stage-1A
Selected for A350
BI 20 S94350 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A350
BI 21 S94350 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A350
BI 22 S94350 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A350
BI 23 S94350 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A350
BI 24 Short K94350(9-11) Load Shedding Trip Relay Optd.
BI 25 S94370 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 26 S94370 Switch in 1A Position Load Shedding Stage-1A
Selected for A370
BI 27 S94370 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A370
BI 28 S94370 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A370

KAHRAMAA LI SIEMENS LTD


ANNEXURE - C : NUMERICAL RELAY BINARY INPUT CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function
No. out for

BI 29 S94370 Switch in Stage-3 Position Load Shedding Stage-3


Selected for A370
BI 30 S94370 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A370
BI 31 Short K94370(9-11) Load Shedding Trip Relay Optd.
BI 32 S94390 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 33 S94390 Switch in 1A Position Load Shedding Stage-1A
Selected for A390
BI 34 S94390 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A390
BI 35 S94390 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A390
BI 36 S94390 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A390
BI 37 S94390 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A390
BI 38 Short K94390(9-11) Load Shedding Trip Relay Optd.
BI 39 S94410 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 40 S94410 Switch in 1A Position Load Shedding Stage-1A
Selected for A410
BI 41 S94410 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A410
BI 42 S94410 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A410
BI 43 S94410 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A410
BI 44 S94410 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A410
BI 45 Short K94410(9-11) Load Shedding Trip Relay Optd.
BI 46 S94430 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 47 S94430 Switch in 1A Position Load Shedding Stage-1A
Selected for A430
BI 48 S94430 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A430

KAHRAMAA LI SIEMENS LTD


ANNEXURE - C : NUMERICAL RELAY BINARY INPUT CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function
No. out for

BI 49 S94430 Switch in Stage-2 Position Load Shedding Stage-2


Selected for A430
BI 50 S94430 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A430
BI 51 S94430 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A430
BI 52 Short K94430(9-11) Load Shedding Trip Relay Optd.
BI 53 S94450 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 54 S94450 Switch in 1A Position Load Shedding Stage-1A
Selected for A450
BI 55 S94450 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A450
BI 56 S94450 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A450
BI 57 S94450 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A450
BI 58 S94450 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A450
BI 59 Short K94450(9-11) Load Shedding Trip Relay Optd.
BI 60 S94470 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 61 S94470 Switch in 1A Position Load Shedding Stage-1A
Selected for A470
BI 62 S94470 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A470
BI 63 S94470 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A470
BI 64 S94470 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A470
BI 65 S94470 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A470
BI 66 Short K94470(9-11) Load Shedding Trip Relay Optd.
BI 67 Spare
BI 68 S94490 Switch in OFF Position LSP Selector Switch on OFF
Position.

KAHRAMAA LI SIEMENS LTD


ANNEXURE - C : NUMERICAL RELAY BINARY INPUT CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function
No. out for

BI 69 S94490 Switch in 1A Position Load Shedding Stage-1A


Selected for A490
BI 70 S94490 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A490
BI 71 S94490 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A490
BI 72 S94490 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A490
BI 73 S94490 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A490
BI 74 Short K94490(9-11) Load Shedding Trip Relay Optd.
BI 75 Short X511: 151,152-153 Spare
BI 76 Short X511: 151,152-154 Spare
BI 77 Short X511: 151,152-155 Spare
BI 78 Short X511: 151,152-156 Spare
BI 79 Spare
BI 80 Open Link X133: 2 & 4 I/O Box-1 BI DC Fail

3 Relay: A202 Details:


MLFB : 6MD6130-4FB90-0AA0+L0S
Sr.No.: BF1309516188

BI 1 Short X511: 179,180-181 Spare


BI 2 Short X511: 179,180-182 Spare
BI 3 Short X511: 179,180-183 Spare
BI 4 S94320 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 5 S93420 Switch in 1A Position Load Shedding Stage-1A
Selected for A320
BI 6 S94320 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A320
BI 7 S94320 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A320
BI 8 S94320 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A320

KAHRAMAA LI SIEMENS LTD


ANNEXURE - C : NUMERICAL RELAY BINARY INPUT CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function
No. out for

BI 9 S94320 Switch in Stage-4 Position Load Shedding Stage-4


Selected for A320
BI 10 Short K94320(9-11) Load Shedding Trip Relay Optd.
BI 11 S94340 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 12 S94340 Switch in 1A Position Load Shedding Stage-1A
Selected for A340
BI 13 S94340 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A340
BI 14 S94340 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A340
BI 15 S94340 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A340
BI 16 S94340 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A340
BI 17 Short K94340(9-11) Load Shedding Trip Relay Optd.
BI 18 S94360 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 19 S94360 Switch in 1A Position Load Shedding Stage-1A
Selected for A360
BI 20 S94360 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A360
BI 21 S94360 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A360
BI 22 S94360 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A360
BI 23 S94360 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A360
BI 24 Short K94360(9-11) Load Shedding Trip Relay Optd.
BI 25 S94380 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 26 S94380 Switch in 1A Position Load Shedding Stage-1A
Selected for A380
BI 27 S94380 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A380
BI 28 S94380 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A380

KAHRAMAA LI SIEMENS LTD


ANNEXURE - C : NUMERICAL RELAY BINARY INPUT CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function
No. out for

BI 29 S94380 Switch in Stage-3 Position Load Shedding Stage-3


Selected for A380
BI 30 S94380 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A380
BI 31 Short K94380(9-11) Load Shedding Trip Relay Optd.
BI 32 S94400 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 33 S94400 Switch in 1A Position Load Shedding Stage-1A
Selected for A400
BI 34 S94400 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A400
BI 35 S94400 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A400
BI 36 S94400 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A400
BI 37 S94400 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A400
BI 38 Short K94400(9-11) Load Shedding Trip Relay Optd.
BI 39 S94420 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 40 S94420 Switch in 1A Position Load Shedding Stage-1A
Selected for A420
BI 41 S94420 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A420
BI 42 S94420 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A420
BI 43 S94420 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A420
BI 44 S94420 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A420
BI 45 Short K94420(9-11) Load Shedding Trip Relay Optd.
BI 46 S94440 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 47 S94440 Switch in 1A Position Load Shedding Stage-1A
Selected for A440
BI 48 S94440 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A440

KAHRAMAA LI SIEMENS LTD


ANNEXURE - C : NUMERICAL RELAY BINARY INPUT CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function
No. out for

BI 49 S94440 Switch in Stage-2 Position Load Shedding Stage-2


Selected for A440
BI 50 S94440 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A440
BI 51 S94440 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A440
BI 52 Short K94440(9-11) Load Shedding Trip Relay Optd.
BI 53 S94460 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 54 S94460 Switch in 1A Position Load Shedding Stage-1A
Selected for A460
BI 55 S94460 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A460
BI 56 S94460 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A460
BI 57 S94460 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A460
BI 58 S94460 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A460
BI 59 Short K94460(9-11) Load Shedding Trip Relay Optd.
BI 60 S94480 Switch in OFF Position LSP Selector Switch on OFF
Position.
BI 61 S94480 Switch in 1A Position Load Shedding Stage-1A
Selected for A480
BI 62 S94480 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A480
BI 63 S94480 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A480
BI 64 S94480 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A480
BI 65 S94480 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A480
BI 66 Short K94480(9-11) Load Shedding Trip Relay Optd.
BI 67 Spare

KAHRAMAA LI SIEMENS LTD


ANNEXURE - C : NUMERICAL RELAY BINARY INPUT CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function
No. out for

BI 68 S94500 Switch in OFF Position LSP Selector Switch on OFF


Position.
BI 69 S94500 Switch in 1A Position Load Shedding Stage-1A
Selected for A500
BI 70 S94500 Switch in Stage-1 Position Load Shedding Stage-1
Selected for A500
BI 71 S94500 Switch in Stage-2 Position Load Shedding Stage-2
Selected for A500
BI 72 S94500 Switch in Stage-3 Position Load Shedding Stage-3
Selected for A500
BI 73 S94500 Switch in Stage-4 Position Load Shedding Stage-4
Selected for A500
BI 74 Short K94500(9-11) Load Shedding Trip Relay Optd.
BI 75 Short X511: 157,158-159 Spare
BI 76 Short X511: 157,158-160 Spare
BI 77 Short X511: 157,158-161 Spare
BI 78 Short X511: 157,158-162 Spare
BI 79 Spare
BI 80 Open Link X134: 2 & 4 I/O Box 2 BI DC supply Fail

KAHRAMAA LI SIEMENS LTD


Test Result /Remark

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

KAHRAMAA LI SIEMENS LTD


Test Result /Remark

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

KAHRAMAA LI SIEMENS LTD


Test Result /Remark

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

KAHRAMAA LI SIEMENS LTD


Test Result /Remark

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

KAHRAMAA LI SIEMENS LTD


Test Result /Remark

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK
Checked OK

Checked OK
Checked OK
Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

KAHRAMAA LI SIEMENS LTD


Test Result /Remark

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

KAHRAMAA LI SIEMENS LTD


Test Result /Remark

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

KAHRAMAA LI SIEMENS LTD


Test Result /Remark

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

KAHRAMAA LI SIEMENS LTD


Test Result /Remark

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK

Checked OK
Checked OK
Checked OK
Checked OK
Checked OK

Checked OK

KAHRAMAA LI SIEMENS LTD


ANNEXURE C : NUMERICAL RELAY BINARY OUTPUT CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function Test Result /Remark
No. out for

1 Relay : F811
7SJ621 Binary Outputs Operate BO from DIGSI & Check at
BO 1 Check Continuity at X511 : 5-6 Spare Checked OK
BO 2 Put all Switch in Stage-4 Local Stage-4 Load Shed Checked OK
Position with S811 in Service
and Check Pickup of all Relays/
BO 3 & 4 Spare
BO 5 Put all Switch in Stage-1A Local Stage-1A Load Shed Checked OK
Position with S811 in Service
and Check Pickup of all Relays/
BO 6 Put all Switch in Stage-1 Local Stage-1 Load Shed Checked OK
Position with S811 in Service
and Check Pickup of all Relays/
BO 7 Put all Switch in Stage-2 Local Stage-2 Load Shed Checked OK
Position with S811 in Service
and Check Pickup of all Relays/
BO 8 Put all Switch in Stage-3 Local Stage-3 Load Shed Checked OK
Position with S811 in Service
and Check Pickup of all Relays/

2 Relay : A201
6MD613 Binary Outputs Operate BO from DIGSI & Check at
BO 1 to 53 Spare

3 Relay : A202
6MD613 Binary Outputs Operate BO from DIGSI & Check at
BO 1 to 53 Spare

KAHRAMAA LI SIEMENS LTD


ANNEXURE - D: NUMERICAL RELAY BI THRESHOLD CHECK

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test carried


Test Description Function Test Result / Remark
No. out for
Test Carried out for 10% of total number of Binary inputs

1 Relay : F811
7SJ621 BI Power up the relay & Inject variable DC voltage to relay BI terminal
BI 2 F15-F16 Threshold voltage >= 65V Checked OK
BI 3 F17-F18 Threshold voltage >= 65V Checked OK
BI 6 R11-R13 Threshold voltage >= 65V Checked OK
BI 8 R7-R8 Threshold voltage >= 65V Checked OK

2 Relay : A201
6MD613 BI Power up the relay & Inject variable DC voltage to relay BI terminal
BI 1 F10-F14 Threshold voltage >= 65V Checked OK
BI 10 H17-G12 Threshold voltage >= 65V Checked OK
BI 20 G9-G12 Threshold voltage >= 65V Checked OK
BI 30 J4-J12 Threshold voltage >= 65V Checked OK
BI 40 M17-L12 Threshold voltage >= 65V Checked OK
BI 50 L9-L12 Threshold voltage >= 65V Checked OK
BI 60 N4-N12 Threshold voltage >= 65V Checked OK
BI 70 R17-Q12 Threshold voltage >= 65V Checked OK
BI 80 Q9-Q12 Threshold voltage >= 65V Checked OK

3 Relay : A202
6MD613 BI Power up the relay & Inject variable DC voltage to relay BI terminal
BI 1 F10-F14 Threshold voltage >= 65V Checked OK
BI 10 H17-G12 Threshold voltage >= 65V Checked OK
BI 20 G9-G12 Threshold voltage >= 65V Checked OK
BI 30 J4-J12 Threshold voltage >= 65V Checked OK
BI 40 M17-L12 Threshold voltage >= 65V Checked OK
BI 50 L9-L12 Threshold voltage >= 65V Checked OK
BI 60 N4-N12 Threshold voltage >= 65V Checked OK
BI 70 R17-Q12 Threshold voltage >= 65V Checked OK
BI 80 Q9-Q12 Threshold voltage >= 65V Checked OK

KAHRAMAA LI SIEMENS LTD.


ANNEXURE - E : CURRENT & VOLTAGE INJECTION TEST

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr.
Test carried out for Test Description Test Result /Remark
No.

1 Bus-1 VT Voltage Distribution : F811


Apply 63.5 V in each Phase w.r.t neutral Inject 3 ph 110VAC at:
and verify reading on relay Display: X231: 9-10-11-12 VRY=
VRY , VYB & VBR Put S66 in VT1 Position
Check voltage at : VYB=
S811 & F811
VBR=

2 Bus-2 VT Voltage Distribution : F811


Apply 63.5 V in each Phase w.r.t neutral Inject 3 ph 110VAC at:
and verify reading on relay Display: X231: 1-3-5-7 VRY=
VRY , VYB & VBR Put S66 in VT2 Position
Check voltage at: VYB=
S811 & F811
VBR=

KAHRAMAA LI SIEMENS LTD


ANNEXURE - F : RELAY OPERATION TEST

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr.
Test carried out for Test Description Test Result /Remark
No.

1 Operation test for F811(7SJ621) Stage FSET (Hz) TSET (sec) TOPTD (sec)
Inject 3 ph 110VAC, Change
frequency and Operate different 1A 49.80 10.0
stages Only feeders on Stage 1A were tripped Checked OK

1 49.60 5.0
Only feeders on Stage 1 were tripped Checked OK

2 49.40 3.0
Only feeders on Stage 2 were tripped Checked OK

3 49.20 2.0
Only feeders on Stage 3 were tripped Checked OK

4 49.0 0.0
Only feeders on Stage 4 were tripped Checked OK

Fault Recording Check Checked OK

2 Load Shedding blocking conditions check


S810 Switch in OUT Position/ Blocked OK
S66 Switch in OFF Position/
Put S810 in IN Position,
Put S66 in VT1 Position,
Inject Voltage <65V in VT1 /
Put S810 in IN Position,
Put S66 in VT2 Position,
Inject Voltage <65V in VT2 /
Put S810 in IN Position.

KAHRAMAA LI SIEMENS LTD


ANNEXURE - H : ALARM CIRCUIT

NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE

DATE :

DRG.NO.: PH10-1B-43-35-1112

Sr. Test Description Test Result /


No Test carried out for
operate relay / Short at check Continuity at Remark
.

1 DC-1/2 Supply Fail /BCU unhealthy Short A201(F3-F4) / X239: 1,2-3,4 Checked OK
I/O BOX DC-1/2 MCB trip Short A202(F3-F4) /
Switch OFF MCB F133 /
Switch OFF MCB F134

KAHRAMAA LI SIEMENS LTD


NAME: 11KV LOAD SHEDDING PROTECTION CUBICLE
DRG.NO.: PH10-1B-43-35-1112

<< Select feeder number from here


B RP LSP
Designatio 1 MLFB
F811 2 7SJ6211-5EB90-1FC0+L0S 1309514692
A201 3 6MD6130-4FB90-0AA0+L0S 1309516157
A202 4 6MD6130-4FB90-0AA0+L0S 1309516188
5
6

You might also like