Professional Documents
Culture Documents
15 09 2023
Electrical Resistivity Survey
Report for Ground Water
Investigation
Contents
INTRODUCTION ............................................................................................................................................. 1
FIELD PROCEDURE......................................................................................................................................... 5
CONCLUSIONS/RECOMMENDATIONS ........................................................................................................ 10
FIELD CURVE................................................................................................................................................ 19
REFERENCES ................................................................................................................................................ 23
INTRODUCTION
A large quantity of water is a primary requirement for commercial project, to meet the daily
requirement of water, the administration of GH2 INDUSTRIES asked the Geolog Services to
conduct an Electrical Resistivity Survey for groundwater investigations and recommend a
suitable location for installation of tube well for their industrial Project.
The area was investigated at eight locations (ERS-1 to ERS-8), up to a depth of 200 m This
report presents the findings of the electrical resistivity survey for groundwater investigations
at proposed locations in the area. Schlumberger Electrode configuration was used to conduct
Vertical Electrical Soundings (VES) at proposed locations (Fig.1).The Electrical Resistivity
Survey for groundwater investigation was conducted by Geolog Services.
The recommendations for test drilling are made at the locations ERS-06 and ERS-8 at a depth
of 500 ft after considerations of lithology and electrical resistivity of the aquifers. The aquifers
are brackish and not suitable for drinking, agriculture, and construction purposes unless
passes through RO process.
Location Coordinates :
Where,
I = Current in milliamps
K= Geoelectric constant
K = π [(AB/2)2 – (MN/2)2]
MN
The depth for which resistivity measured, was controlled by varying the spacing between the
electrodes. For depth scanning, the central point was fixed and the spacing of electrodes was
gradually increased with a fixed distance interval horizontally. Thus, the depth of scanning
was increased and apparent resistivity was obtained as function of depth.
Stainless steel rods were used as electrodes. Electrodes spacing were measured by numbered
marking on the current cables to reduce risk of gross error which can easily arise when survey
tapes are used.
surface of the earth. To achieve this, electric current is inserted into the ground via two
electrodes and the potential difference, which is caused by the inserted current, is measured
in two other electrodes. The measured potential difference gives an image for the difficulty
of the current flow through the subsurface. This is an indication of the electrical resistance of
the subsurface.
The observations were made by adopting the Schlumberger electrode configuration using
Vertical Electrical Sounding technique (Fig: 2). The current electrode spacing was increased
in steps from 3 m to 200m.
Observations were taken using the controlled current which was sent to earth between
current electrodes, A & B, and Potential thus developed was measured between potential
electrodes, M & N (Fig:2).The apparent resistivity values were calculated for each step and
plotted on 2x3 cycle bi-logarithmic graph.
The resistivity field curves have been analyzed qualitatively by the empirical method in order
to determine the possible number of subsurface lithological/geoelectrical layers, their
tentative depth and the ranges of their approximate resistivity values (Wetzel & Mooney,
1956). This data was formatted for ASCII data file to be used in the modeling program. The
data which was affected by presence of man mad structures was inserted after interpolation
of data from nearby soundings.
Fig: 3. Vertical columns showing the interpreted lithological layers of ERS-1 and ERS-6
Fig: 3. Vertical columns showing the interpreted lithological layers of ERS-1 and ERS-6
1. The electrical resistivity investigation in the area indicates the presence of water at all
locations.
2. The main aquifer zones are 0-50 meter sand ,50-90 meters limestone,120-70 meters
lime stone and bore hole data provided by client is almost same.
3. The area is promising for Brackish groundwater potential. However, a test hole
minimum, 152 m (approx. 500 feet) deep will be drilled at ER-06 and ERS-08 where
brackish water aquifer expected.
4. Upper 24m (80 ft) zone should be seal with the help of cement and bentonite.
5. The expected TDS is expected to have 2000 - 4,000 ppm with approx. discharge of
80,000-120,000 USGPD.
9. Test hole should be geo physically logged in order to have better picture of the
aquifers and lithologies needed for better completion of the well.
10. Geophysical logs, at least natural gamma and resistivity logs should be run (Very
Important for delineation of aquifers of interest and tube-well installation).
12. Water samples should be collected and tested for quality of water.
ERS - 1
ERS - 2
ERS - 4
ERS - 6
ERS - 8