Maintaining the health of water based solutions that circulate through a hydronic system is of critical importance for
its operation. The DISCAL® air separator and DIRTMAG® PRO dirt separator duo ensures maximum protection and
system efficiency. The DISCAL air separator’s unique bell shape geometry coupled with a coalescing element forces
micro-bubble oxygen to be efficiently collected and automatically vented from the system. The DIRTMAG PRO’s
magnetic technology and particle mesh removes both ferrous and problematic non-ferrous debris helping to keep
expensive heat exchangers and ECM circulators running smoothly. CALEFFI GUARANTEED.
FROM THE GENERAL MANAGER & CEO
In 2020, 75 percent of all new electrical power generation in the US was from solar
photovoltaic and wind turbine systems. Wow! Renewably-sourced electricity is growing
faster than I had imagined.
This issue of idronics describes the concepts and technical details for designing hydronic
systems for low energy and net zero buildings. It stresses simple, cost effective, and resilient
approaches that deliver the superior comfort hydronic systems have long been known for.
Several system examples are provided that deliver heating, cooling, and domestic hot water.
We hope you enjoy this issue of idronics and encourage you to send us any feedback by
e-mailing us at idronics@caleffi.com.
For prior issues please visit us at www.caleffi.us, and click on the icon. There you
can download the PDF files. You can also register to receive hard copies of future issues.
Mark Olson
3
TABLE OFOF
TABLE CONTENTS
CONTENTS
TABLE OF CONTENTS
SECTION PAGE
1 55 INTRODUCTION
Introduction
5
26
30
Lowering water temperature in existing hydronic heating systems
2 87 CHARACTERISTICS
Pipe & fitting priorities
Changing OF A NET_ZERO BUILDING
nomenclature
25
What is “net-zero?”
Pipe vs. tube
Changes are needed Domestic hot water conservation
Net metering
Pipe size Embodied energy considerations
9 Why Electrical
lower energy
water storage & management
temperatures
Pipe fitting terminology are Global warming considerations
important
January 2020
January 2022 High-performance thermal envelopes
Modulating/condensing boilers
The market for net-zero
Biomass
Indoor boilers
air quality Creative hydronic system design
July 2019 Solar thermal collectors
Couplings
Geothermal water-to-water-heat pumps
Elbows
3 15 Air-to-water OF
ADVANTAGES heat pumps
HYDRONIC SYSTEMS IN LOW-ENERGY & NET-ZERO BUILDINGS
Biomass boilers
Superior thermal comfort Distribution efficiency
12 Metal Future-proofing
Acoustical comfort
pipe joining hydronics &
methods systems
materials Minimally invasive installation
Global
Reduced
Steel trends
pipe in hydronics
air velocity Refrigerant considerations
Easy zoning Piping flexibility
Stainless steel&pipe
16 Methods
Electric heating
for reducingcooling
watersource
temperature Versatility of hydronic systems
Wrought
Reducing
iron pipe
equipment building load Thermal storage potential
Black iron
Electric pipe
boilers Easy expandability
Partial load vs design load consideration
Geothermal
Cast iron water-to-water heat
pipe All loads from a single heat pump
A Technical Journal Outdoor
Copper reset
pumpswater Resiliency
A Technical Journal Adding heatheat tube
emitters
Air-to-water pumps
from Brass
Adding more fin-tube baseboard
from Bronze
CALEFFI NORTH AMERICA, INC Adding the same type of fin-tube baseboard
CALEFFI NORTH AMERICA, INC 4 30 KEY Metallurgical
DESIGN
Adding joiningfin-tube
high CONCEPTS
output methods baseboard
3883 W. Milwaukee Rd Soft
Heat soldering
Adding other
emitter heat emitters
options Incorporating heat recovery ventilation
3883 W. Milwaukee Rd Brazing
Milwaukee, Wisconsin 53208 Fan-coils
Low thermal mass radiant panels Buffer tanks
Milwaukee, Welding
Panel radiatorsr
Sizing supplemental heat emitters Buffer tank sizing
USA Wisconsin 53208 Fan-assisted panel radiators Buffer tanks & variable-capacity heat
USA Thermal performance of fan-coils
Fan-coils pumps
Adding radiant panels
Tel: 414-238-2360
29 Polymer
Air handlers
pipe joining
Evaluating existing methods & materials
cast iron radiators
Cooling mode control
Tel: 414-238-2360 1-pipe cast
Polyvinyl iron radiators
chloride tubing (PVC)
FAX: 414-238-2366
FAX: 414-238-2366 5 48 EXAMPLE
2-pipe cast
Chlorinated iron radiators
PolyVinyl
SYSTEMS Chloride tubing (CPVC)
Estimating
High-Density
System #1 heat output from cast
Polyethylene iron(HDPE)
tubing radiators
System #5
The effect
Cross-linked
System #2 of flow rate on heat output
Polyethylene tubing (PEX)System #6
E-mail:E-mail:
idronics@caleffi.com System
Oxygen #3diffusion System #7
idronics@caleffi.com
36 Piping
Systemmodifications
#4
Composite PEX-AL-PEX tubing
Website: www.caleffi.us
Website: www.caleffi.us Zoning possibilities temperature tubing (PE-RT)
Polyethylene-raised
59 SUMMARY
Zoning with non-electric thermostatic
PolyPropylene-random
Zoning with manifold
tubing (PP-R)
valve actuators
radiator valves
Fusion joining methods
To receive futurefuture
To receive idronics issues
idronics issues Boiler protection
FREE, FREE,
register onlineonline
register
60
41 Summary
APPENDIX
Heat source A: configuration
CALEFFI HYDRONIC COMPONENTS
Design guildlines
www.caleffi.us
www.caleffi.us
47
61 APPENDIX B: CALEFFI PLUMBING COMPONENTS
Example Systems
System #1
20212019
© Copyright
© Copyright 2019 System #2
CaleffiCaleffi
North North America,
America, Inc. Inc.
61 System #3
APPENDIX C: GENERIC COMPONENTS
Printed:Printed: Milwaukee,
Milwaukee, Wisconsin
Wisconsin 55 Appendix A: Generic piping symbol legend
USA USA 62
56
APPENDIX D: ESTIMATING PANEL RADIATOR HEAT OUTPUT
Appendix B: Component Symbol legend
AT REDUCED WATER TEMPERATURES
Disclaimer: Caleffi makes no warranty that the information presented in idronics meets the mechanical, electrical or other code requirements
Disclaimer:
applicableCaleffi
within makes
a givenno warrantyThe
jurisdiction. thatdiagrams
the information
presentedpresented in are
in idronics idronics meets and
conceptual, the mechanical, electrical
do not represent or other
complete code requirements
schematics for any
applicable within a given
specific installation. Localjurisdiction.
codes may The diagrams
require presented
differences in or
in design, idronics are conceptual,
safety devices relative to and
thosedoshown
not represent
in idronics.complete schematicsoffor any
It is the responsibility
those installation.
specific adapting anyLocal
information
codespresented
may requirein idronics to verify
differences that such
in design, oradaptations meetrelative
safety devices or exceed local code
to those shown requirements.
in idronics. It is the responsibility
4 4 N° 55 giugno 2019
4 N° 55 giugno 2019
1. INTRODUCTION
For decades, the majority of the Figure 1-1
energy used to heat buildings has
been supplied from fossil fuels,
mostly in the form of natural gas, fuel
oil and propane. During this time,
the vast majority of hydronic heating
systems were supplied by boilers
burning these fuels.
5
Figure 1-3
12
electricity
renewables
10 petroleum
natural gas
8 coal
Quadrillion Btus
4
US residential sector energy consumption
2 by energy source (1950-2020)
0
1955
1960
1965
1970
1975
1980
1985
1990
1995
2000
2005
2010
2015
2020
1950
Other developments that continue to influence the market Today, a 2,500 square foot house built to one or more of
for hydronic systems are evolving building technology these standards could have a design heating load in the
and regulations that significantly reduce building heating range of 10-15 Btu/hr/ft2 of floor area, approximately 1/3
and cooling loads relative to those common during the that of a similar-sized home built 50 years ago.
20th century.
Figure 1-4
During the latter half of the 20th century, it was common
for single family homes to have design heating loads
in the range of 30-35 Btu/hr/ft2 of floor area. A typical
2,500 square foot home would require a heat source
with a capacity of 75,000 to 88,000 Btu/hr. A home with
an 88,000 Btu/hr design load, in a cold winter climate
(7,000ºF•day and -5ºF outdoor design temperature)
would require about 128 million Btu (128 MMBtu) of
delivered heat to maintain an average indoor temperature
of 70ºF over an average heating season.
Courtesy of Rachel Wagner
6
Figure 1-5 The growing availability and increasing efficiency of air-to-
water heat pumps (Figure 1-5) and geothermal water-to-water
heat pumps, will also significantly influence the market for
hydronic systems. Unlike boilers, nearly all these heat pumps
can provide chilled water for cooling. This characteristic alone
opens many opportunities that were previously impractical.
As 2022 and the years following unfold, heat pumps will
gain an increasing portion of the hydronic heat source
market. The flexibility of modern hydronics technology
allows informed designers to craft systems that allow heat
pumps to operate at peak performance.
7
2. CHARACTERISTICS OF A NET-ZERO BUILDING
The first step in designing any heating of renewable energy and reducing During the 1970s, the cost of solar
or cooling system is to understand carbon-based emissions. photovoltaic modules was in the range
the building the system will supply. of $1,000 per peak watt. This limited
It could range from a 200-year-old Collectively, these new design their use to very specialized situations
building with little or no insulation, considerations allow contemporary such as power for spacecraft,
single pane windows and high rates buildings, as well as rehabilitated satellites and critical use applications
of air leakage, to a contemporary structures, to serve their such as remote mountaintop
structure built to the latest energy intended purposes with minimal communications equipment.
conservation standards. environmental impact. Extrapolating
these advancements into the Over the last 50 years, the price
For most buildings, and over many future suggests that buildings may of solar photovoltaic modules has
decades, customary practice was to eventually be environmentally benign decreased by orders of magnitude.
decide on the fuel source, select the as well as energy self-sufficient. Today, the retail cost of solar
type of heat emitters to be used, and photovoltaic modules is typically
then size a heat source to maintain WHAT IS “NET-ZERO?” between $1 and $2 per peak watt.
a selected interior air temperature There is no single definition or current The reliability and service life of
(typically 68-72ºF) under the coldest standard the specifies exactly what solar photovoltaic modules has
expected outdoor temperature. constitutes a “net-zero” building. also improved significantly over this
Although this approach has led to time. These advances now make it
acceptable installations, it often The original concept was a building practical to create onsite electricity
did not address issues such as that could produce all the energy it in a wide range of climates ranging
ideal comfort, reducing emissions required over a typical year using from tropical to arctic. The life-cycle
or energy use strategies that various combinations of onsite cost of energy provided by modern
could be mutually beneficial to the generation, energy storage and solar photovoltaic modules and
consumer, the energy supplier and “feedback” of surplus electrical balance of system components is
the environment. energy to a utility grid. The energy now competitive, and in some cases,
required included that used for lower than that of utility-supplied
The long-standing “customary” heating, cooling, domestic water electricity. Solar electric systems are
approach to building heating and heating, as well as for lights, now widely used to supply electricity
cooling is changing. Modern building appliances, cooking, etc. to buildings ranging from single family
designers are employing increasingly homes to large industrial facilities.
wholistic strategies that consider The only practical way to create such
more than the simple thermodynamic a building was to incorporate onsite Solar PV systems are an integral
balance of matching heating or cooling electrical energy generation using subsystem in most net-zero buildings.
source equipment to building loads. solar photovoltaic modules. In many cases, the solar PV array is
Figure 2-1
Because buildings represent
approximately 40 percent of the
total energy used in North America,
energy conservation efforts, both
voluntary and mandatory (in the
form of building codes and other
regulations) have accelerated over
the last decades. These efforts have
resulted in buildings that can maintain
comfortable interior conditions, such
as those based on ASHRAE Standard
55, while using less a 1/3 the energy
per square foot of floor space that
was required 50 years ago.
8
and fed back to the utility’s electrical grid. Furthermore,
Figure 2-2
each kilowatt•hour of electrical energy supplied by the
customer to the utility grid is credited to the customer
at the same retail rate as a kilowatt•hour supplied to the
building by the utility. When this concept is in effect, the
electrical grid becomes equivalent to a battery that is free,
100% efficient and practically infinite in size. Thus, it would
be possible for a photovoltaic system to send surplus
electrical energy into the grid during a sunny summer day,
and “pull” an equivalent amount of electrical energy back
Courtesy of Revision Energy
from the grid on a cold winter night, without any net cost
to the consumer. Electric utility meters that are certified
for bidirectional energy flow are used to ensure accurate
tallies for both ingoing and outgoing electrical energy.
9
production. This approach requires “all-electric” buildings,
and thus limits the choice of hydronic heating sources to Figure 2-5
heat pumps or electric resistance boilers. If cooling is to be non-limited power demand
provided, the building will likely use a reversible air-to-water
heat pump or geothermal water-to-water heat pump.
power demand
ELECTRICAL ENERGY STORAGE & MANAGEMENT
Another trend associated with modern net-zero buildings
is called resiliency. It refers to the ability of the building to
withstand unexpected events such as severe storms, blue shaded area
earthquakes or floods that could create widespread and proportional to daily
long-lasting utility power outages. Given that most or electrical energy use
all of the energy needed within the building under such
circumstances would be provided by electricity, the building
needs battery energy storage and the ability to operate as 0 4 8 12 16 20 24
an “island” completely independent of the utility grid.
time of day (hr)
Several companies now offer lithium ion battery storage
systems and load management controls that enable such
shifted electrical energy use
operation. Figure 2-4 shows one example of a residential
(all yellow shaded areas)
scale battery-based energy storage system.
eliminated
demand limit
Figure 2-4 peak demand
power demand
0 4 8 12 16 20 24
time of day (hr)
10
The lower graph demonstrates the
Figure 2-6
concepts of demand-limiting and
load shifting. The red line represents
the highest electrical power demand
allowed by a controller managed by
the electric utility or the home’s own
insulation baffle energy management system. Notice
that there two peak periods, shown
in gray, that are above this allowed
raised heel
demand. The energy represented
roof trusses
by these peaks has been shifted
to other, lower-demand times, and
shown as the yellow shaded areas.
The yellow areas could represent the
energy used by appliances such as
blown-in insulation washing machines, water heaters or
(R-49+)
dishwashers, electric vehicle chargers
advanced framing techniques perforated
aluminum
or other devices that are automatically
insulated headers soffit turned on during low-demand periods.
11
Figure 2-7
INDOOR AIR QUALITY
The techniques used to reduce space
heating and cooling loads in low-energy
and net-zero homes, especially those
associated with air sealing, greatly
reduce the rate of air leakage relative
to buildings constructed to older
standards. This creates the potential
for poor indoor air quality. The typical
remedy for this is to include mechanical
ventilation systems that can maintain a
healthy exchange of outdoor air with
indoor air.
12
of the moisture in the outgoing This is well-suited to situations where Some building designers currently
(higher absolute humidity) air stream a single chilled water air handler, use carbon accounting software to
is transferred to the incoming (low supplied from an air-to-water or minimize the amount of carbon used
absolute humidity) air stream. In water-to-water heat pump, and in the overall life-cycle of various
summer, some of the moisture in the connected to a forced-air distribution building components.
incoming (higher absolute humidity) system, is used for cooling. More
air stream is transferred to the (lower details on this approach are provided GLOBAL WARMING
absolute humidity) outgoing stream. in upcoming sections. CONSIDERATIONS:
This moisture exchange helps Building design as well as
maintain a comfortable (and healthy) DOMESTIC HOT WATER mechanical system selection is
indoor relative humidity in winter. It CONSERVATION also being influenced by global
also reduces the latent cooling load Another way that building energy warming considerations. The choice
in summer. use can be lowered is through of refrigerants used in devices such
reduced use of domestic hot water. as heat pumps will increasingly be
Both HRVs and ERVs require a For a typical family of 4, the energy impacted by these considerations.
ducting system to distribute the pre- needed for domestic water heating Existing hydrofluorocarbon (HFC)
conditioned air within the building. In can be 25 to 30 percent of the total refrigerants, such as R410a, will
some cases, the ducting system is thermal energy used in an energy- eventually be replaced by refrigerants
specifically designed for ventilation efficient house. For projects aspiring with lower global warming potential.
only. In other systems, the HRV or to net-zero status, it is common to These include carbon dioxide (CO2),
ERV can be interfaced with an existing use low-flow shower heads, washing propane (R-290) and difluoromethane
or new forced-air distribution system. machines that operate with minimal (R-32).
Figure 2-9 if any hot water, and drain heat
recovery devices, such as shown in THE MARKET FOR NET-ZERO
figure 2-9. Demand for net-zero energy buildings
is growing rapidly in North America
EMBODIED ENERGY and globally. It is currently one of
CONSIDERATIONS the fastest growth segments of the
Those who focus on the construction industry. The compound
environmental benefits of net-zero annual growth rate for net-zero
buildings often place increased energy buildings in North America is
emphasis on “embodied energy” and projected to average 15.6 percent
“embodied carbon.” The concept from 2019 through 2024. By 2025,
of embodied energy revolves the projected value of the global net-
around the total life-cycle energy zero building market is over 79 billion
associated with the components in U.S. dollars.
the building, including acquisition
of raw materials, processing those North America leads the world in
materials, transportation, installation, terms of the number of net-zero
maintenance and disposal. The projects currently constructed. The
rationale is to avoid materials and North American market, combined
construction methods that, although with the European Union, represents
they may save a given amount over 95 percent of the global market
of energy during their useful life, for net-zero buildings. Figure 2-10
ultimately require an even greater shows the range of market activity in
amount of energy to produce, install, North America.
maintain and for disposal.
The primary drivers for this market
Embodied carbon is a similar concept. growth are government regulations
Source: Ecoinnovations
The rationale being to select building that seek to reduce global warming
materials and methods so that the based on carbon emissions from
net effect does not add to the carbon fossil fuels. Carbon emissions
content in the earth’s atmosphere. associated with building heating and
13
Figure 2-10
Source: www.teamzero.com
cooling are estimated to be between 40 and 50 percent hydronic systems that are symbiotic to the previously
of the total global emissions, and thus carbon reduction described characteristics of low-energy and net-zero
programs are keenly focused in this area. buildings. Those systems need to be simple, repeatable,
reliable, efficient, and perhaps most important, they need
CREATIVE HYDRONIC SYSTEM DESIGN to provide excellent human thermal comfort. The sections
The rapidly expanding market for net-zero buildings that follow will show how these objectives can be achieved.
presents a unique opportunity for designers to create
14
3. ADVANTAGES OF HYDRONIC SYSTEMS IN LOW-ENERGY & NET-ZERO BUILDINGS
There are many ways to provide space heating, cooling heat production to be dissipated at the same rate it is
and domestic water heating in all-electric net-zero generated. Some degree of discomfort is experienced
buildings. They range from separate systems for each load, when these two rates of heat transfer are not balanced.
to integrated approaches that leverage energy recovery
and energy management to minimize consumption and A healthy adult engaged in light activity generates heat
coordinate the needs of building occupants with the real- at a rate of about 400 Btu/hr. Figure 3-1 shows the heat
time status of the utility grid. transfer processes by which a human adult dissipates this
metabolic heat production.
This section describes the advantages and benefits of
using hydronic-based systems in low-energy and net- Notice that a high percentage of the body’s heat dissipation
zero buildings. It also discusses some of the hydronic comes from thermal radiation to surrounding surfaces.
heating and cooling hardware that’s appropriate for these This has profound implications regarding comfort. It can
applications. Later sections will show specific details and make a person located near a large, cool surface, such
example systems. as a window on a cold winter day, quite uncomfortable,
even if the room’s air temperature is 70°F. The opposite is
SUPERIOR THERMAL COMFORT also true: the gentle warmth emitted by a heated surface,
Although some energy enthusiasts are willing to live in such as a warm floor or ceiling, or a panel radiator, can
buildings that minimize energy use at the expense of widely provide excellent comfort, even when the surrounding air
varying comfort, this is not true for most North American temperature is in the mid-60ºF range.
consumers. History has shown that approaches to space
heating and cooling that require sacrifices in comfort to Designers can assess how different building characteristics
achieve high energy-efficiency targets or absolute minimum influence human thermal comfort using software called the
energy use, usually fail to gain significant market share. CBE Thermal Comfort Tool. It’s freely accessible at https://
The lesson learned: Comfort, has been and remains one of comfort.cbe.berkeley.edu/
the most important underlying factors in establishing and
maintaining a market for building energy systems. Several types of hydronic distribution systems simultaneously
influence air temperature, temperature stratification and
Human thermal comfort is determined by the interaction surface temperatures of rooms in ways that enhance
of processes the body uses to dissipate metabolic heat human physiological comfort. This distinguishes them from
production, as well as the environmental conditions within alternatives such as electric furnaces, ductless mini split heat
the occupied space. These include air temperature, air pumps, or central heat pumps that connect to forced-air
temperature stratification, interior surface temperatures, distribution systems. These air-based delivery systems have
relative humidity and air movement. Comfort is established less influence on interior surface temperatures and can create
when the conditions surrounding the body allow metabolic undesirable drafts or air temperature stratification. As such,
they are not as well-matched to human comfort needs.
Figure 3-1
ACOUSTICAL COMFORT
Most people want their home to be a quiet refuge from
the pace and noise of modern life. They don’t want to
hear sounds emanating from their heating and cooling
systems. Properly designed and installed hydronic systems
Figure 3-2
Courtesy of healthyheating.com
15
using radiant panels or panel radiators can operate with Figure 3-3
virtually no detectable sound within occupied spaces. The
sound produced by the source equipment, such as the
compressor in a heat pump, is either outside the building
or it can be acoustically isolated within a mechanical room.
Courtesy of Thermolec
Most hydronic-based systems also create minimal air
velocity within conditioned spaces. This reduces the
possibility of drafts, which compromise comfort. Lower air
velocity also reduces the dispersant of airborne pollutants
such as viruses, dust, pollen, smoke, volatile organic
compounds and cooking odors.
16
Advantages of electric boilers include: within the building. The temperature of that absorbed heat
• Very small and easy to mount is increased, and it is passed to another water (or antifreeze
• No combustion or venting requirement solution) stream that dissipates it outside the building —
• Some have internal controls that regulate outlet typically to an earth loop.
temperature based on outdoor reset
• Much less expensive than heat pumps of equivalent Figure 3-4 shows an example of a water-to-water heat
heating capacity pump having a nominal heat output of 48,000 Btu/hr.
• Can operate at elevated water temperatures up to
200ºF if necessary Two of the four larger pipes connected to this heat pump
• Minimal servicing requirements go to an earth loop. The other two connect to the hydronic
distribution system. The two smaller pipes near the bottom
Disadvantages include: of the heat pump connect a desuperheater heat exchanger
• Cannot provide cooling within the heat pump to a domestic hot water storage tank.
• Higher operating cost relative to heat pumps of All of these pipes will be insulated and vapor-sealed when
equivalent capacity the installation is completed.
• Typically require minimum 200-amp electric service
entrance Most currently available water-to-water heat pumps can
• High power draw may be beyond what a typical produce water at temperatures up to approximately
emergency generator can supply 125ºF for space heating. They can also produce chilled
water for cooling.
GEOTHERMAL WATER-TO-WATER HEAT PUMPS
To date, most of the North American systems that combine
heat pumps with hydronic distribution have used water-to-
water heat pumps supplied by geothermal heat sources
(e.g., earth loops or water wells). For more information on water-to-water heat
pumps, and how they can be applied in geothermal
In heating mode operation, a water-to-water heat pump applications, see idronics #9.
absorbs heat from a low-temperature geothermal source,
increases the temperature of that heat, and passes it to a Advantages of geothermal water-to-water heat pumps
separate higher-temperature water stream that delivers it include:
using a hydronic distribution system. • Can provide heated water up to 125ºF and chilled
water for cooling
In cooling mode, a water-to-water heat pump absorbs • No visible outdoor equipment or sound
heat from a stream of water that passes through one or • Slightly higher seasonal COP compared to air-source
more air handlers, fan-coils or other cooling terminal unit(s) heat pumps in cold climates
• Can be ordered with desuperheater for domestic
Figure 3-4
water heating
• Longer expected service life (20-25 years) relative to
air-source heat pumps due to their interior location
• No defrost cycle is required (as needed for all
air-source heat pumps)
• No venting or combustion air is required
Disadvantages include:
• Significantly higher installation cost compared to air-
source heat pumps
• Installation is often highly disruptive of existing
landscape
• Not compatible with all installation sites due to lot
size, ground water regulations, presence of rock
ledge, etc.
• Antifreeze solution generally required in earth loops
17
AIR-TO-WATER HEAT PUMPS refrigerant, sealed and leak-tested Figure 3-6a
Low-energy and net-zero buildings before leaving the factory. Installers
equipped with hydronic heating and do not need to add to or adjust any
cooling distribution systems can also part of this refrigeration system. They
be supplied by heat pumps that absorb only need to run supply and return
heat from outside air, even when the piping and electrical power to the
temperature of that air is below 0ºF. This heat pump. This allows the potential
low-temperature heat is combined with for the heat pump to be installed by
electrical energy to produce a stream a contractor who doesn’t have the
of heated water at temperatures up to experience or servicing tools to deal
about 130ºF. Like water-to-water heat with refrigeration systems.
Courtesy of SpacePak
pumps, most air-to-water heat pumps
contain refrigerant reversing valves, Because they are located outside in
allowing them to also provide chilled cold climates, nearly all monobloc
water for cooling. air-to-water heat pumps operate with
a mixture of water and antifreeze,
Air-to-water heat pumps eliminate the such as a 30% solution of non-toxic
propylene glycol. This protects the Figure 3-6b
need for geothermal earth loops. This
allows for installation at almost any heat pump from potential freeze
site, and at significantly lower cost damage during a prolonged power
compared to that of geothermal heat outage in sub-freezing weather.
pump systems of equivalent capacity.
Monobloc air-to-water heat pumps also
There are two primary configurations contain significantly less (approximately
for air-to-water heat pumps: half) the refrigerant volume per ton of
• Monobloc heating capacity compared to ductless
• Split system heat pumps, especially when the
latter are installed with the maximum
Figure 3-5 shows an example of a allowable refrigerant line set lengths
monobloc air-to-water heat pump. between the outdoor unit and
multiple indoor units.
The refrigeration system in a
monobloc air-to-water heat pump Figure 3-6 shows an example of a
is completely contained within the split-system air-to-water heat pump.
outdoor cabinet. It is charged with The outdoor unit connects with
the indoor unit using two copper
Figure 3-5 refrigerant lines, the same as used
they are operating. Both are available
with most central air-conditioning
with variable-speed, “inverter-driven”
systems. There is no water in the
compressors that allow them to vary
outdoor unit, which eliminates the
heating and cooling capacity from
need for antifreeze in the system. The
some maximum rated output down
indoor unit contains the refrigerant-to-
to about 30 percent of that output.
water heat exchanger, which serves
This is helpful in situations where a
as the condenser in heating mode
single-zone, chilled-water cooling
and the evaporator in cooling mode.
distribution unit needs to operate at a
relatively small capacity compared to
Split-system air-to-water heat pumps
the heat pump’s full heating capacity.
have comparable performance to
monobloc units. In heating mode,
Courtesy of SpacePak
18
• Not disruptive to landscaping Distribution energy is an even more important consideration
• Low ambient units can operate at sub-0ºF air for cooling systems. Every watt of electrical energy used
temperatures to move cooling effect through a building is a watt added
• Significantly lower installed cost relative to equivalent to the building’s sensible cooling load. For example, a
geothermal heat pumps constant-torque ECM blower motor used in a nominal 3-ton
forced-air heat pump adds about 2,935 Btu/hr (0.24 tons)
Disadvantages include: to the building’s sensible cooling load. An ECM circulator
• Shorter expected service life (15-20 years) due to delivering an equivalent cooling effect using chilled water,
outside installation and operating at an input power of 35 watts, only adds 120
• Slightly higher operating cost relative to geothermal Btu/hr to the sensible cooling load.
water-to-water heat pumps
• Automatic defrost cycles are required Designers should also consider that air-to-air heat pumps
• Monobloc systems require antifreeze in outdoor piping typically require higher air flow rates per unit of heat delivery
• Limited availability of units with desuperheater for compared to fossil-fuel furnaces, and thus their distribution
domestic water heating power requirement is higher, assuming the same blower
• Highly zoned systems will require a buffer tank motor technology in each device.
DISTRIBUTION EFFICIENCY
Professionals who design low-energy and net-
zero buildings apply scrutiny when selecting the
“source equipment” that supplies space heating, Figure 3-7
cooling and domestic hot water. They often limit
selections to state-of-the-art devices with the
highest available thermal efficiencies.
each circulator
requires 75 watts
While this approach is certainly relevant and power input
logical, it is also incomplete. The energy used by
the source equipment, be it a boiler, heat pump
or chiller, is only part of the total energy used by
the system. Regardless of how heating energy
or cooling effect is generated, additional energy
is needed to distribute that thermal energy within
a building. Treating this “distribution energy”
as insignificant or inconsequential is a serious
oversight in the design process, especially when
the objective is to create buildings that minimize
energy use. ⎛ COP1 ⎞ ⎛ COP2 ⎞
⎜⎝ COP − 1⎟⎠ ⎜⎝ COP − 1⎟⎠
The energy required to distribute heat produced by COPnet = 1 2
19
n
q = c ⎡⎣ f c ⎤⎦ A(Tw − TR )
Figure 3-8
8, 24" x 72" x 4" panel radiators TRV
thermostatic
radiator valves
(TRV) on each
radiator
variable-speed
pressure-regulated
circulator
spring
check
manifold station
spare
connection(s)
heat source
buffer
tank
20
idronics 30 formulas
However, this number has little relevance without something Assuming that the high-efficiency circulator operated
to compare it to. To provide such a comparison, consider at approximately 75 percent of design input wattage for
a forced-air delivery system associated with a furnace that 3,000 hours per year, in a location where electricity costs
requires 550 watts while delivering 80,000 Btu/hr to the $0.12/kWhr, the seasonal operating cost of the distribution
building. The distribution efficiency of that system is: system would only be about $2.32. This compares to
a seasonal estimated operating cost of $148 for the
previously described forced-air system operating under the
same assumed conditions.
In this specific comparison, the forced-air system has less MINIMALLY INVASIVE INSTALLATION
than half the distribution efficiency of the hydronic system. A given volume of water can absorb almost 3,500 times
This implies that the forced-air system requires over twice more heat than the same volume of air, assuming both
the electrical power input of the hydronic system to deliver materials undergo the same temperature rise. This allows
the same amount of heat to the load. a given rate of heating or cooling to be conveyed using
small diameter hydronic tubing relative to the size of a duct
The concept of distribution efficiency can be used to compare conveying that same rate of heat transport using air.
⎛ COP1 ⎞ ⎛ COP2 ⎞
hydronic versus forced-air heating systems, as well as
⎜ COP − 1⎟⎠ ⎜⎝ COP − 1⎟⎠
competing hydronic ⎝system 1 designs. 2 For example, consider a heat transfer rate of 12,000 Btu/
COPnet =
⎡⎛ COP1 ⎞ ⎛ COP2 ⎞ ⎤ hr. This would be adequate to heat an area of 1,200 square
Consider, for example,
⎢⎜ the contemporary− 1⎥ “homerun” feet in a low-energy or net-zero house having a design load
⎢
⎣ ⎝ COP1 − 1⎟⎠ ⎜⎝ COP2 − 1⎟⎠ ⎥⎦
hydronic distribution system as shown in figure 3-8. of 10 Btu/hr/ft2 of floor area. If water is used to convey
this heat transfer, and the hydronic distribution system
This system, which would be well-suited for use in low- operated at a typical design load temperature drop of 20ºF,
energy or net-zero homes, uses a high-efficiency variable- the required flow rate is only 1.2 gallons per minute (gpm).
speed pressure-regulated circulator to create flow between This flow rate could be handled by a nominal 1/2-inch PEX
the buffer tank and 8 individually regulated panel radiators. tube. That tube could be easily routed along or through
Under design
idronics 30load
formulasconditions, the water leaving the buffer framing members with virtually no impact on the structure.
tank is maintained at 120ºF, which is well within the operating
range of an air-to-water or water-to-water heat pump. If air is used to provide this same 12,000 Btu/hr heat
q = c ⎡⎣ f c ⎤⎦ A(Tw − TR ) n transport rate, while undergoing a temperature change
Each panel radiator is assumed to be piped with 1/2-inch from 65ºF to 110ºF through the heat source, the required
PEX tubing, 60 feet out and 60 feet back from a manifold flow rate would be 247 cubic feet per minute (CFM).
station. A non-electric thermostatic radiator valve regulates Assuming a typical duct sizing air velocity of 600 feet per
the flow ofq warm
= a × (Twaterwa
− Troom
through
) each panel radiator based minute (FPM), a 9-inch diameter round duct, or a 7-inch
on its setting and the current room temperature. high by 10-inch wide rectangular duct would be needed.
Figure 3-9 shows a scaled comparison of these different
( )
A hydraulic analysis
qhp t of this system, under the stated
V =shows that it could deliver 30,800 Btu/hr to a
delivery “conduits.”
conditions,
500(∆T )
building, with a circulator power input of only 8.6 watts. Figure 3-9
Thus, it would have a distribution efficiency of:
"Conduit" size required for
V=
( q )t = (36,000)10 = 48gallons
hp 12,000 Btu/hr heat transfer rate
500(∆T ) 500(15)
floor framing
21
A 1/2-inch PEX tube could be easily Figure 3-10 over 25 pounds of refrigerant, more
routed through floor framing using than twice the volume of refrigerant
3/4- or 7/8-inch diameter holes. If per ton of capacity compared to a
these holes were drilled near the typical factory-sealed air-to-water or
center of the floor joists, they would water-to-water heat pump.
have no significant impact on the
structure. However, due to their size, Large VRF systems in commercial
the equivalent ducts shown would buildings can contain hundreds of
have to be supported under the floor pounds of refrigerant. A leak in such
framing, potentially compromising a system is a serious safety issue,
the use of the space below. as well as an environmental hazard.
Although the currently popular
Beyond the heat conveyance refrigerant R-410a is not toxic and
consideration is the issue of heat loss non-flammable, it will displace air
and possible insulation requirements. if allowed to accumulate within a
A 9-inch diameter duct has about 14 confined space. Given sufficient
times more surface area compared concentration and the inability to
to a 1/2-inch PEX tube. The 7-inch vacate a space quickly, this could
by 10-inch rectangular duct shown lead to asphyxiation.
in figure 3-9 has about 17 times
more surface area. Assuming the One OSHA material safety data
One nominal 3-ton ductless heat
same insulation requirement, the sheet (MSDS) for R-410a states the
pump system, when applied with
round duct would require about 14 following: “In Case of Spill or Leak
maximum allowable refrigerant piping
times more insulation material, and Use Halogen leak detector or other
lengths, requires approximately twice
the rectangular duct about 17 times suitable means to locate leaks or
the refrigerant volume per ton of rated
more material, per unit of length. check atmosphere. Keep upwind.
capacity compared to that required
If the ducting and hydronic tubing Evacuate enclosed spaces and
by a typical factory-sealed air-to-
operated at the same temperature, disperse gas with floor-level forced-air
water or water-to-water heat pump.
the heat loss (or heat gain in cooling ventilation. Exhaust vapors outdoors.
One 8-ton rated VRF system contains
mode) would be substantially higher
for the ducting. Figure 3-11
REFRIGERANT CONSIDERATIONS:
Nearly all monobloc-style air-to-
water heat pumps and geothermal
water-to-water heat pumps used in
hydronic heating and cooling systems
come with a factory-charged, sealed
and leak-tested refrigeration system.
With proper handling and installation,
the chances of a refrigerant leak
occurring during or after installation
are very small.
22
Do not smoke or operate internal production or import of R-22 was no distribution systems. Monobloc
combustion engines. Remove flames longer allowed in the U.S. air-to-water heat pumps contain
and heating elements.” all refrigerant outside the building.
Today, most residential and light As such, they are more adaptable
ASHRAE Standards 15 and 34 commercial heat pumps and air- to potential use with flammable
set specific limits on how much conditioning systems used in refrigerants. The relatively small
refrigerant a system can contain North America operate on R-410a refrigerant volumes present in these
based on the volume of the smallest refrigerant. However, due to its global heat pumps in comparison to those
interior space into which that warming potential relative to newly present in VRF systems makes the
refrigerant could potentially leak. developed alternative refrigerants, consequences of a leak much less
Under ASHRAE Standard 34, which R-410a is also scheduled to be costly, and less of a safety issue.
applies to systems containing more eliminated from new equipment
the 6.6 pounds of refrigerant, there beginning in January 2023. There Buildings equipped with hydronic
can be no more than 26 pounds of will likely be a multi-year phaseout heating and cooling distribution
refrigerant in the system per 1,000 plan for R-410a similar to that used systems are also minimally
cubic feet of the smallest occupied for R-22. New refrigerants such dependent on evolving refrigerant
space into which refrigerant could as R-32, which has a lower global regulations — provided the source
potentially leak. For institutional warming potential (roughly 1/3 that equipment using these refrigerants
buildings, where occupants might of R-410a), are already being used can meet the capacity and supply
not be able to evacuate without in some new heat pumps systems in water temperatures required by the
assistance, the limit is 13 pounds Europe and Asia. Eventually, propane hydronic distribution system.
of refrigerant per 1,000 cubic feet of (R-290), which has good refrigerant
smallest occupied space. properties and low global warming PIPING FLEXIBILITY
potential, may be accepted for use There are several piping
Ductless heat pumps and VRF as refrigerant in some heat pump configurations that have been used
systems also contain many site- applications where all the refrigerant for hydronic heating and cooling
fabricated joints in refrigeration piping. remains in outdoor equipment. systems over many decades. These
Most of these joints are inside the However, it remains questionable configurations are highly scalable.
building. Figure 3-11 shows both whether a flammable refrigerant, such In smaller systems, the piping is
brazed and compression joints in as propane and to a lesser degree typically sized so that flow velocities
refrigeration tubing that’s a small (R-32), would be allowed in systems don’t exceed 4 feet per second. The
portion of a VRF system installed at a with large refrigerant volumes and orientation of the piping in a closed
multi-story hotel. extensive interior refrigerant piping. hydronic system is largely irrelevant
This situation has the potential to — provided that provisions are
Although field-installed refrigerant severely limit the future service of made to vent air from high points in
piping is leak-tested during the current-generation VRF systems. the system. Piping can be vertical,
installation, the number of connections horizontal, sloped and routed over or
and the conditions under which they Beyond specific refrigerant under obstructions. Different piping
are made inevitably increase the chemistries are potential compatibility materials, such as copper, steel, PEX
possibility of leaks over time. issues related to lubricating oils, and polypropylene, can be combined
and the size/pressure rating of the in the same system when there are
Another consideration is the ongoing refrigerant piping used. The latter advantages in doing so.
evolution of refrigerants based on their consideration is especially relevant
global warming potential. Prior to the to large VRF systems, which can In contrast, the piping requirements
1990s, the most common refrigerant contain thousands of feet of copper for VRF system are much more
used in North American heat pumps tubing selected and sized for specific restrictive. Very specific details are
and central air-conditioning systems current-generation refrigerants and required to prevent oil, which is
was R-22, which, among other their associated lubricants. circulated through the system with
compounds, contained chlorine. refrigerant, from being trapped and
Rising concern over the effects These considerations should be thus unable to flow back to the
of chlorine on atmospheric ozone contrasted with those relevant to compressor. Insufficient oil return
eventually led to a phaseout of R-22. the air-to-water or water-to-water has resulted in compressor failures,
Beginning in January 2020, the heat pumps used with hydronic which can cost thousands of dollars
23
Figure 3-12
air-to-water air-to-water
heat pump heat pump
(outdoor unit) (indoor unit)
ThermoProtec
valve
distribution system
to / from exisiting
(P2)
3/8" & 5/8"
refrigerant line set
(P4)
(P1)
check
valve existing
boiler
Magnetic
dirt separator
to isolate, replace and recommission. $/MMBtu basis compared to heat may not have the heating capacity
Most VRF systems are also limited supplied through other means. or be able to produce suitably high
to copper tubing. water temperatures to meet the
This can be beneficial, especially as a building’s heating load on extremely
VERSATILITY OF HYDRONIC SYSTEMS step in transitioning existing buildings cold days. Making use of an existing
Although it’s likely that heat pumps from fossil fuel to an all-electric boiler can also reduce the cost of
will steadily gain market share against status. An existing boiler can serve as the installation relative to removing
fossil-fuel boilers in the years ahead, an auxiliary heat source as well as a an otherwise functional boiler and
it’s unlikely that the fossil-fuel boiler peak load heat source, in combination replacing it with a heat pump sized to
market will suddenly disappear. with an electrically powered heat cover the building’s design heat load.
Existing fossil-fuel boilers will, in most pump that serves as the primary
cases, remain in operation until they heat source. In such a system, the Figure 3-12 shows a relatively
can no longer be serviced, or until the objective is to provide heat from the simple way to incorporate an
cost of the fuel they require becomes heat pump whenever possible, but existing boiler along with a new air-
significantly more expensive on a also recognize that some heat pumps to-water heat pump.
24
The partial system shown in figure pump would be turned off and the oil-fired boilers can operate with an
3-12 has a split-system air-to-water boiler would supply the load. electrical power demand in the range
heat pump piped in parallel with the of 100 to 400 watts. By comparison,
existing boiler. Each heat source Depending on its heating capacity a residential-sized heat pump may
has its own circulator. There is also relative to the building’s design load have a power demand in the range of
a check valve associated with each and the climate, an air-to-water heat 2,000 to 6,000 watts. The relatively
heat source to prevent flow reversal pump or geothermal water-to-water low power demand of the exiting
when that heat source is off and the heat pump may be able to supply boiler could be supplied by a small
other one is operating. 75 percent or more of the building’s emergency generator. It might also
seasonal space heating energy, even allow the boiler to operate from the
The controls for the system may when connected to a legacy hydronic home’s electrical energy storage
be internal to the heat pump, or distribution system using “high- system — if so equipped. This
possibly external to either heat temperature” heat emitters, such as concept demonstrates a degree of
source, depending on the specific fin-tube baseboard. resiliency that might not be possible
equipment used. The objective of with an electric boiler due to its much
the controls, during heating mode This percentage of total seasonal higher electrical power demand.
operation, is to use heat from the space heating energy can be
heat pump whenever possible, but increased by either reducing the If the building is eventually converted to
invoke operation of the boiler when building’s heating load, or by adding all-electric as part of a net-zero strategy,
necessary to ensure that the load is heat emitters to the system. Both the existing boiler could be replaced by
being met. The boiler would typically of these techniques lower the an electric boiler with minimal piping
be called to operate if the heat pump required water temperature of the modifications. However, this should
is unable to maintain some pre-set distribution system. In some cases, only be done after an evaluation of the
temperature on the supply side of the an air-to-water heat pump can building’s electrical service entrance
distribution system. provide upwards of 95 percent of the to ensure adequate capacity. It might
seasonal space heating energy. also entail an upgrade to the building’s
During cooling mode, the boiler emergency generator if that generator
would remain off. The heat pump is expected to power the electric boiler.
would be operated as necessary
to provide a suitable chilled-water THERMAL STORAGE POTENTIAL
supply temperature to the remainder See idronics #25 for more information Water is one of the best materials
of the system. and details on lowering water available for storing thermal energy.
temperature in existing hydronic This characteristic allows hydronic
One way to maximize the seasonal distribution systems. systems to include thermal energy
COP of a heat pump supplying storage where it provides a benefit.
a hydronic distribution system The boiler shown in figure 3-12 One possibility that’s applicable in
is to regulate the supply water is assumed to be an existing areas where utilities offer time-of-use
temperature based on outdoor reset “conventional” boiler (e.g., one not electrical rates is operating a heat
control. This control strategy, which is intended to operate with sustained pump or an electric boiler during
built into the internal controls of some flue gas condensation). When “off-peak” times when the cost of
modern heat pumps, only allows outdoor reset control is added to electricity is significantly reduced,
the water temperature produced by the system, there will be times when and store some of the thermal energy
the heat pump to be high enough to the water temperature is significantly produced during this period in an
meet the current heating load. During lower than temperatures associated insulated tank for use during “on-
mild weather, the water temperature with the original installation. A Caleffi peak” periods. Another possibility is
supplied by the heat pump would be ThermoProtect mixing valve should to store heat produced by an electric
automatically lowered to maximize be installed to protect the existing boiler or heat pump during “off-peak”
the heat pump’s coefficient of boiler for operating with sustained times in a large, solid, thermal mass
performance (COP). As the load flue gas condensation. such as a thick concrete slab with
increases, the water temperature embedded hydronic tubing. Both of
supplied by the heat pump would The existing boiler can also serve these techniques have been used in
increase, up to a maximum of 125ºF as a low-power-demand backup limited applications to date. They hold
to 130ºF. If higher supply water heat source during a power outage. potential for increased adaptation
temperatures are needed, the heat Most residential-sized gas-fired or as influencing factors such as real-
25
Figure 3-13 ALL LOADS FROM A SINGLE HEAT PUMP
Another unique possibility offered by hydronic systems is
the ability to provide domestic water heating in addition to
space heating and cooling, all from the same heat pump.
In a modern low-energy home, domestic water heating
often represents 25 to 30% of the total thermal energy
used and is therefore a major consideration if attempting to
reach net-zero status. Domestic water heating is typically
not provided by central air-to-air heat pumps or ductless
heat pump systems.
26
Figure 3-14a
Figure 3-14b
evaporator
fan
expansion device
compressor
cooler / drier
air discharge
room temp.
air intake
DHW
outlet
cold
water
condenser
inlet
coils
Figure 3-15
electric electric
energy energy
input 1 input 2
free
heat (space heat)
COP1 COP2
27
Heat pump 1 is absorbing free heat from outside the building, heating heat pump, doesn’t yield the savings often cited for
combining it with heat derived from electricity, and sending heat pump water heaters.
that heat inside the building. Heat pump 2 is a heat pump
water heater. The water heater absorbs heat that was placed When a single air-to-water or geothermal water-to-water
inside the building from heat pump 1, combines it with more heat pump provides space heating, cooling, and domestic
energy
idronicssourced from electricity, and sends combined energy
30 formulas water heating, the heat it absorbs during the domestic
into domestic water within the tank. water heating mode is always coming from a “free” source
(e.g., outside air or heat in the earth). This avoids the
The net COP of this cascading heat pump system can be derating effect just described for a cascading heat pump
determined as follows: installation. An air-to-water heat pump that supplies a year-
⎛ COP1 ⎞ ⎛ COP2 ⎞ round domestic water heating load can typically achieve
⎜⎝ COP − 1⎟⎠ ⎜⎝ COP − 1⎟⎠ annual average COPs in the range of 2.5 to 3.0, depending
COPnet = 1 2 on climate and the temperature to which the domestic
⎡⎛ COP1 ⎞ ⎛ COP2 ⎞ ⎤ water needs to be heated.
⎢⎜ ⎟⎜ ⎟ − 1⎥
⎢⎣⎝ COP1 − 1⎠ ⎝ COP2 − 1⎠ ⎥⎦
Some air-to-water and geothermal water-to-water heat
Where: pumps also can be ordered with a desuperheater heat
COPnet = the overall COP of the two cascaded heat exchanger for domestic water heating. During cooling
pumps mode operation, the heat gathered by the desuperheater
COP1 = the COP off the space heating heat pump (must from the hot refrigerant discharged from the heat pump’s
be > 1.0) compressor is heat that would otherwise be dissipated
COP2 = the COP of the heat pump water heater (must be outside the building (e.g., to outside air or into the earth).
> 1.0) This scavenged heat is truly “free.”
Note: To use this formula, both COP1 and COP2 must be
> 1.0 q = c ⎡⎣ f c ⎤⎦ A(Tw − TR ) n When an air-to-water heat pump is operating in cooling
mode, and the thermostatic control in the domestic water
For example,⎛ if COP
a heat⎞ pump⎛ COPprovides ⎞ space heating to storage tank calls for heating, the heat pump will temporarily
a building while
⎜⎝ COPoperating
1
⎟ ⎜ at a2 COP
⎟ of 4.0, and a heat switch to heating mode, quickly bring the tank temperature
pump q = a × (T within COP
− 1−⎠T⎝room − 1⎠ only absorbed heat
) 2building
COPnetwater
= heater1wa that up to its setpoint, and then switch back to cooling. Later
produced ⎡by⎛ theCOPspace ⎞ ⎛heating
COP2 heat⎞ pump
⎤ while operating sections will show other system configurations that use
at a COP ⎢of⎜ COP
3.0, the
1
net
⎟ ⎜ COP, − 1⎥ as the heat added
defined
⎟ heat pumps to supply domestic hot water as well as space
⎢⎣⎝
to the domestic
V =
( )
water
− 1 ⎝ COP2 − 1⎠ ⎥⎦
q1 hp t⎠divided by the total electrical input to heating and cooling.
enable that heat placement,
500(∆T ) would be:
RESILIENCY
Many professionals who plan buildings or HVAC systems
are being asked to incorporate “resiliency” into their
V=
( q )t = (36,000)10 = 48gallons
hp designs. This term implies an ability for buildings, or systems
500(∆T ) 500(15) within buildings, to withstand unexpected events such as
extended power outages, the effects of climate change or
A net COP of 2.0 means that for every two units of heat interruption of normal supply chains. The objective is to
delivered to the domestic water, one came from a “free” create buildings and systems that are reliable, long-lasting,
q = c ⎡ f c ⎤⎦ A(T
source, ⎣and
− T )n
the wotherR came as electric heating. Although adaptable and easy to repair when necessary.
this net COP is still double the COP of any form of electric
resistance heating (e.g., COP = 1.0), it is far lower than the Although it would be flippant to simply state that any
rated COP of the heat pump water heater operating under the hydronic heating or cooling system is highly “resilient,”
q = a × (Twa − Troom )
assumed condition of absorbing “free” surplus heat. these systems do have characteristics that fit the objectives
In most buildings, there will be times when the heat of resiliency.
absorbed by the heat pump water heater is indeed surplus
V =
( )
heat, andqthushp
t the long term net COP will likely be higher One characteristic is that there are many potential sources
than the above) calculation asserts. Still, the concept of
500(∆T for much of the hardware used in hydronic heating and
“cascading heat pumps” demonstrates that placing a heat cooling systems. For example, the eventual failure of a
pump water heater within the heated thermal envelope of specific make and model of circulator within a hydronic
a low-energy or net-zero building, where the majority of system, or even the inability to obtain a new circulator of
V=
( )
the heat itqhp t
absorbs
=
( is present
36,000 )
10 due to operation of a space
= 48gallons
the same make and model, doesn’t render the system
500(∆T ) 500(15)
28
inoperable for long. Several other makes and models of could take several hours and cost multiple hundreds of
circulators are readily available for replacing the failed dollars. The fan-coil with the cracked condensate pan
circulator. Most of the potential replacements would will likely be discarded, even though the majority of the
have the same flange-to-flange dimension as the original components within it are in working order. This true story
circulator, and could be installed within a few minutes by demonstrates vulnerability rather than resiliency.
any competent heating technician using basic tools. This
same concept holds true for many other components in a Another reason that hydronic systems offer resiliency is
hydronic system, such as pipe, fittings, valves, expansion that water will always be available as the working fluid.
tanks, heat emitters, manifolds, air/dirt separators and It is not subject to evolving global warming directives,
basic temperature controllers, etc. refrigerant phaseouts, manufacturing limitations or
material handling and transportation regulations. Any
This adaptability may not be possible for alternatives water lost from the system due to maintenance or
such as ductless heat pumps or commercial VRF component replacement is easily and inexpensively
systems. Many of these systems have proprietary replaced. The heat source or cooling source within a
controls or other components that must be replaced with hydronic system may change over time, but the physical
exactly the same component obtained from the original properties that enable water to efficiently convey heat or
manufacturer or their authorized agent at whatever cooling effect will not change.
pricing they choose to set. Special tools, software and
training are often required to fully service these systems. Finally, most of the components used in a properly designed,
The eventual discontinuation of proprietary components, installed and maintained hydronic distribution system
or long delays in obtaining them due to supply chain will last for many decades. They will outlast the system’s
disruption, could render the entire system inoperable for initial heat source or cooling source, and perhaps even
extended periods, or even unrepairable. its second or third heat source or cooling source. Simply
stated: Properly executed hydronic systems are long-term
Consider the following (real) scenario: A crack forms in investments rather than “throw away” technology. Contrast
a small plastic condensate collection pan inside a high- this with the typical service life of many modern appliances,
wall fan-coil that’s part of a ductless heat pump (or VRF) such as refrigerators, washing machines and microwaves,
system. This causes condensate to leak from the unit. some of which will not even last ten years under normal
Some makes and models of these fan-coil units do not service. Portions of those discarded appliances will
allow that simple and inexpensive pan to be removed in inevitably end up in landfills.
the field and replaced as a separate component. The entire
wall mounted fan-coil unit must be replaced. Doing so Professionals who plan low-energy and net-zero buildings,
requires the system to be turned off. The refrigerant must or place emphasis on decarbonization, environmentally
be reclaimed and eventually reinstalled using specialized conscious design, and resiliency, should carefully consider
equipment. It also requires the refrigerant piping and wiring these benefits associated with hydronic heating and
to be disconnected and reconnected. The overall process cooling systems.
29
4. KEY DESIGN CONCEPTS
Some of those who design or build low-energy and net- compete for the mechanical system portion of the
zero buildings have preconceived notions about hydronic construction budget.
systems. Their opinion is that such systems are overly
complicated and unnecessary in these contemporary To achieve higher market acceptance, hydronic systems
buildings. for low-energy and net-zero buildings need to be “tailored”
to consumer expectations, load characteristics, desired
In hindsight, the North American hydronics industry environmental ramifications and available utility options.
is largely responsible for cultivating these opinions by The following guidelines are appropriate.
showcasing unique and elaborate installation photos.
Figure 4-1 is an example. Hydronic systems for low-energy and net-zero buildings
should:
This system uses a nominal 5-ton split-system air-to- • Meet owner expectations for installed cost, reliability,
water heat pump as its source equipment. Several of the serviceability, aesthetics, embodied carbon and
ten circulators visible in the photo have high-efficiency recyclability.
ECM motors. The craftsmanship evident by the piping • Provide superior thermal comfort in both heating and
and electrical work is outstanding. This system certainly cooling modes.
combines the concepts of heat pumps and modern • Provide an option for domestic water heating in
hydronic system design, and likely delivers the goals for addition to space heating and cooling.
which it was custom designed. • Recognize the unique load and thermal response
characteristics of low-energy and
Still, this system required hundreds of components to be net-zero buildings.
properly selected, purchased, organized into a coherent • Harmonize with the construction techniques and
design, and at least in part — field assembled. As such, materials used in low-energy and
this image can be overwhelming to architects, general net-zero buildings.
contractors or owners looking for a simple, affordable and • Use simple, repeatable and scalable concepts.
serviceable solution to heating and cooling a home with low • Enhance heat pump performance wherever possible.
space heating and cooling loads. The perceived complexity, • Minimizes electrical power demand (e.g., high
cost or reliability of such a system often dissuades these distribution efficiency).
building professionals or the eventual building owners from • Considers new delivery modes for electricity (e.g.,
using hydronic-based systems. real time pricing, onsite battery storage, load shifting
and demand-limiting possibilities).
The hardware-intensive approach to hydronic heating • Allows continuity of operation under unexpected
and cooling survives as a niche in the market, but mostly conditions (resiliency).
for custom-built new homes with generous construction • Consider use of existing boilers in retrofit projects.
budgets. This niche approach is unlikely to be adapted as
a “go-to” solution by professionals designing low-energy This section will show and describe methods and hardware
and net-zero homes, especially when several alternatives that address these design concepts.
Figure 4-1
HEAT EMITTER OPTIONS
There are dozens of devices and site-constructed
assemblies that can serve as hydronic heat emitters. They
range from concrete slabs with embedded tubing, to fan-
assisted panel radiators, to extended surface-area fin-tube
baseboards. These devices cover a wide range of thermal
mass and supply water temperature requirements. They
also cover a wide range of installation cost and complexity.
30
In the context of low-energy and net-zero buildings, emitters with low thermal mass. This has both desirable
two technical characteristics should be given strong and undesirable implications. For example, a high thermal
consideration: mass heated slab can often maintain reasonable comfort
within a well-insulated building for several hours during
• The thermal mass of the heat emitter(s). a power outage, or during a pre-scheduled time when
• The supply water temperature required by the heat high cost electricity rates apply, and thus an electrically
emitter(s) under design load conditions. powered heat source might be intentionally turned off .
During these times, the slab slowly releases stored heat
The thermal mass of different hydronic heat emitters can without simultaneously receiving heat input. This is a very
greatly influence the comfort achieved and maintained in a desirable characteristic under these circumstances.
low-energy or net-zero building.
However, the same heated slab installed in a building with
Figure 4-2 shows a sampling of thermal masses for several large amounts of solar heat gain or other “unpredictable”
hydronic heat emitters. The numbers in the chart are based internal heat gains can create wide variations in interior
on the “amount” of heat emitter needed to release 1,000 temperature due to its inability to quickly stop emitting heat.
Btu/hr into a room at 70ºF, while operating at an average
water temperature of 110ºF. Note that the thermal mass for Most currently constructed low-energy and net-zero
a heated 4-inch concrete slab is over 100 times that of a buildings have high-performance thermal envelopes,
modern fan-assisted panel radiator. and thus low rates of heat loss. These buildings are
often designed and sited to take advantage of solar heat
Heat emitters with high thermal mass take much longer gains. Given these characteristics, along with the goal of
to adjust to changing load conditions compared to heat maintaining stable comfort, it is typically best to use low
Figure 4-2
31
Figure 4-3
air-to-water heat
air-to-water heat pump
pump water-to-water heatpump
water-to-water heat pump
outside
fan air
evaporator
outside
air
reversing
valve
hot
fluid
evaporator
condenser
condenser
heat to
RV comp. building
circulator warm
TXV fluid
TXV
4.5
3.5
4
3
3.5
2.5 3
COP
COP
2 2.5
2
1.5
1.5
1
1
0.5 0.5
0 0
-10 0 10 20 30 40 50 25 30 35 40 45 50 55 60
thermal mass heat emitters in these buildings. Preferred heat source, the lower the supply water temperature can
options include panel radiators, fan-coils and radiant be, while still maintaining interior comfort, the more efficient
ceiling panels. These emitters can quickly deliver heat the heat pump (measured as the heat pump’s coefficient of
when needed, and just as importantly, they can quickly performance COP).
stop delivering heat when overheating is imminent.
Figure 4-3 shows representative COP characteristics for
Another important consideration is the supply water a low-ambient air-to-water heat pump and a geothermal
temperature required by the heat emitter under design load water-to-water heat pump.
conditions. When heat pumps are used as the system’s
32
Figure 4-4
full full-range
range outdoor reset
outdoor reset limited range outdoor
limited-range outdoor reset
reset
120 120
115 115
fan-coil
radiant floor,
Target supply water temperature (ºF)
Notice that the COP of both heat pumps is strongly load. This helps prevent low-temperature air currents that,
dependent on the water temperature leaving the condenser while able to maintain the space’s setpoint temperature,
(as represented by the three curves on each graph). The could create uncomfortable drafts. Air streams from fan-
lower this temperature, the higher the heat pump’s COP. coils or air handlers capable of operating at low water
temperatures should be carefully designed to mix with
Heat emitters that can meet design heating loads using room air in areas away from where occupants would likely
supply water temperature no higher than 120ºF are be seated. Ceiling diffusers with a wide spread and short
generally well-suited for use with heat pumps. throw, or high-wall diffusers with a long throw and minimal
spread will help in this regard.
Under partial load conditions the water temperature
leaving the heat pump can be reduced based on outdoor Both “full-range” and “limited-range” outdoor reset are
reset control. This maximizes the heat pump’s COP while shown in figure 4-4.
ensuring that comfort is maintained in the building.
For a given rate of heat output and room air temperature,
When panel radiators or radiant ceiling panels are used, the average water temperature at which any hydronic heat
it’s possible to use “full-range” outdoor reset control. emitter needs to operate depends on its surface area.
When fan-coils are used, supply water temperature should The larger the surface area, the lower the average water
generally not be reduced below 100ºF, regardless of the temperature.
33
Figure 4-5
This relationship can be represented by Formula 4-1.
Formula 4-1:
q = c ⎡⎣ f c ⎤⎦ A(Tw − TR ) n
?
Where:
q = heat output of the emitter (Btu/hr)
c = a constant based on the construction or geometry of
q = a × by
the emitter (determined − Troom )
(Twatesting)
fc = flow rate correction factor (determined by testing)
A = surface area of the emitter (ft2)
1/2" drywall
34
Figure 4-7
LOW THERMAL MASS RADIANT PANELS
One radiant panel construction that can be used on ceilings
as well as walls is shown in figure 4-6.
Figure 4-8
( )
qhp t (36,000)10 = 48gallons
V =backside insulation
=
500(∆T ) 500(15)
7/16" oriented strand board
35
Figure 4-9 top-side insulation. The graphite
layers provide lateral heat conduction
between the tubing and panel areas
between the tubing. Although these
panels are relatively light, they still
require support from light gauge
chain or steel cables connected to
structural elements such as bar joints
or concrete slabs.
36
PANEL RADIATORS would require repeated adjustment to keep the radiator’s
Generously sized panel radiators are an excellent heat heat output matched to the room’s heating load.
emitter option for low-energy and net-zero buildings
supplied by hydronic heat pumps. These steel panels A much-preferred approach is to attach a thermostatic
are available in a wide range of sizes from several operator to the radiator’s valve, as shown in figure 4-12.
manufacturers. They have relatively low thermal mass per
unit of heat output, and thus respond quickly to internal This non-electric thermostatic operator continuously
heat gains or temperature changes. They are also relatively senses room temperature and automatically adjusts flow
light and easy to install. through the radiator to maintain the space very close to a
desired comfort level.
One type of panel radiator, often called a “compact” panel,
is supplied with an integral valve, which is mounted at the When the radiators in a hydronic distribution system are
upper right corner of the panel. Figure 4-11 shows an equipped with these operators, each one can automatically
example of this type of panel radiator. and independently adjust its heat output to maintain the
desired comfort level in the space where it’s located. This
Figure 4-11 ability is especially beneficial in low-energy and net-zero
buildings where each room may be subject to different and
variable internal heat gains. Thermostatic operators are
relatively inexpensive, require no wires or batteries, and are
easily installed on the radiator’s integral valve.
37
The heat output of any panel radiator depends on its total Figure 4-15
surface area, the average water temperature at which it
operates, and the room air temperature where the radiator
is installed. Many manufacturers list the output of their panel
radiators at relatively high average water temperature (180ºF
is typical), along with an assumed room air temperature
of 68ºF. This average water temperature is much higher
than can be attained using current-generation air-to-water
or water-to-water heat pumps. However, it is possible to
“derate” the listed output of panel radiators based on lower
average water temperatures, different temperature drops
between supply and return flows, and when necessary,
different room air temperatures. Appendix B summarizes
the EN442 method for adjusting panel radiator outputs
38
fan-coils is relatively low. For example, the fan-coil shown
in figure 4-15 emits sound measured between 25 and 48 Figure 4-16 return duct
decibels (depending on blower speed), and measured enclosure
approximately 8 feet away from the unit. For comparison, a air filter
coil (4-tube pass)
modern refrigerator emits about 50 decibels. blower
39
The heating assembly is called a
Figure 4-18 “homerun” distribution system. Each
of the 5 heated spaces served by
Heating thermostatic operator towel warmer
this assembly has a small diameter
(i.e., 1/2-inch) PEX tube for supply
in shower room
water and another for return water.
TRV All 5 homerun circuits begin and end
capillary
tube
at a manifold station that’s located
in a mechanical room or within a
remote
TRV setting recessed framing cavity. Heated water
dial is supplied to the manifold station by
small area of
floor heating a variable-speed pressure-regulated
TRV circulator. The high-efficiency motor in
TRV
this circulator automatically adjusts its
speed as the thermostatic operators
TRV
on the panel radiators open, close
or modulate the flow through their
associated radiators.
dual
isolation To show versatility, one of the homerun
valves
circuits is routed to a towel warmer
radiator that’s piped in series with a
small area of floor heating. This would
to / from heat source
Cooling
pump). The thermal mass of this tank
allows for very small heat dissipation
ducted air handler (cooling only)
ducted supply air
rates at the heat emitters, when
return air conditions warrant, without short
cycling the heat source.
One system configuration that’s radiators, each equipped with The single-zone cooling assembly
appropriate for residential and small thermostatic operators. Single-zone uses a small air handler (either vertical-
commercial low-energy and net- cooling is provide by a ducted air or horizontal-mounted) combined
zero buildings has multiple zones handler equipped with a chilled- with a ducted forced-air distribution
of heating combined with a single water coil. Figure 4-18 shows two system that supplies several ceiling
zone for cooling. The heating zones component assemblies based on or high-wall diffusers, each with a
could be handled by multiple panel this approach. balancing damper. The chilled-water
40
Figure 4-19 partially cooled &
dehumidified air to cooling coil
centerline
ducted air handler baffle plate
(cooling + ventilation)
ducted supply air
return air
warm exhaust
air to outside
chilled water
blower motor runs at speed supply & return
needed for cooling mode
warm / moist
coil in the air handler cools and dehumidifies the air passing INCORPORATING HEAT RECOVERY VENTILATION
through it. Condensate is collected by the pan under this It is also possible to add a heat recovery ventilator (HRV),
coil and routed to a suitable drain. A horizontal air handler or an energy recovery ventilator (ERV) to the forced-
could be suspended from floor joists or placed on a small air distribution system used for chilled-water cooling, as
platform between trusses and within the building’s thermal shown in figure 4-19.
envelope. A vertical air handler could be located in a small
closet, again within the building’s thermal envelope.
41
The supply and return ducts that lead back to the HRV or of 40,000 Btu/hr and imparting that heat to a hydronic
ERV are connected to the return air duct leading into the distribution system. At the same time, only one of
air handler. Ideally, these ducts are connected opposite the building’s zones is calling for heat, and the rate
from each other with a sheet metal baffle fixed along the of heat transfer to that zone is 3,000 Btu/hr. Assume
centerline of the duct. This placement puts both ducts the water in the heat emitter, the heat pump and the
from the HRV or ERV at the same static pressure point on piping between them totals to 6 gallons. Also assume
the return duct. This minimizes any tendency for induced that the controller operating the heat pump allows a
air flow through the HRV or ERV if it is off, and the air temperature differential of 15ºF between when the
handler is on. The centerline baffle prevents a “short compressor is turned on and when it’s turned off. Under
circuit” of fresh incoming air back into the exhaust stream these conditions, the on-cycle time of the heat pump
leading back to the HRV or ERV. will only be 1.2 minutes! Such a short on-cycle time,
repeated thousands of times per year, would shorten
Operation of the HRV or ERV must be coordinated with the life of the components in the heat pump, especially
the blower in the air handler. For example, in a “ventilation- the compressor and the compressor contactor. This
only” mode, the blower in the air handler would operate situation must be avoided.
at a relatively low speed sufficient to carry the required
ventilation air flow rate, but significantly lower than the The common method of avoiding short-cycling in multi-
required flow rate when the air handler is providing cooling. zone hydronic systems is to incorporate additional
During cooling mode operation, the blower speed would water (and its associated thermal mass) into the system
increase to provide an air flow of approximately 400 CFM using an insulated buffer tank.
per ton (12,000 Btu/hr) of cooling capacity. Modern air
handlers have high-efficiency ECM motors with multiple- Figure 4-20 shows an example of such a tank installed
speed tappings that allow these different air flow rates to between an air-to-water heat pump and a zoned
be achieved. distribution system for a space heating-only application.
The buffer tank is piped in a “3-pipe” configuration.
During winter, it would also be possible to pass a small This allows the distribution system to draw the hottest
flow of warm water through the air handler coil to bring the available water, either directly from the heat pump circuit
incoming ventilation air stream up to room temperature. when the heat pump is operating, or from the upper
The discharge air temperature from the air handler would connection on the buffer tank when the heat pump
be measured and used to modulate a motorized valve is off. Heated water leaving the heat pump doesn’t
that regulates the warm water flow rate through the coil. necessarily pass through the buffer tank before flowing
This option would require additional piping design and to the panel radiators. Return water enters the lower
components to enable warm water flow through the air side connection on the buffer tank. This ensures that
handler’s coil. In cold climates, it may also require the air the thermal mass of the buffer tank is always “engaged”
handler coil to operate with an antifreeze solution. with the flow returning from the radiators, and flow
returning to the heat pump.
This approach eliminates the need to install a separate
ducting system for the HRV or ERV. A variable-speed pressure-regulated circulator provides
flow to six panel radiators using a homerun distribution
BUFFER TANKS system. The latter consists of a manifold station and
There are several ways to zone a hydronic heating or cooling 6 circuits of 1/2-inch PEX tubing. Each radiator has
distribution system. The ease of doing so allows designers an integral valve and is equipped with a thermostatic
to create residential or light commercial systems that might operator, allowing for independent heat output regulation.
have, for example, 3 to 8 zones. Even more zones are
possible when individually controlled panel radiators are Other components in the system include a Dirtmag dirt
used, or for systems in larger commercial buildings. and magnetic particle separator on the flow inlet to the
heat pump, and a Discal air separator on the supply to the
Zoning frequently creates situations where the rate of manifold station.
heat delivery to a zone is much lower than the rate of heat
generation by the heat source. This is especially true when A spring-check valve prevents reverse thermosiphoning from
an “on/off” heat source is providing the heat. the buffer tank through the heat pump when the latter is off.
For example, consider an air-to-water heat pump with a An outdoor reset controller continuously monitors the
single-speed compressor that’s producing heat at a rate water temperature at the mid-height of the buffer tank.
42
Figure 4-20 TRV
TRV
thermostatic
TRV
radiator valves
(TRV) on each
radiator
⎛ COP1 ⎞ ⎛ COP2 ⎞
evaporator
circulator 1 2
COPnet =
⎡⎛ COP1 ⎞ ⎛ COP2 ⎞ ⎤
TXV
⎢⎜ ⎟⎜ ⎟ − 1⎥
⎢⎣⎝ COP1 − 1⎠ ⎝ COP2 − 1⎠ ⎥⎦
rev.
air vent w/ check
heating mode
valve
outside
compressor
spare
spring connections
outdoor check
outdoor reset valve 3-pipe
unit controller buffer
tank
indoor unit
condenser
split-system air-to-water
heat pump
(in heating mode) q = c ⎡⎣ f c ⎤⎦ A(Tw − TR ) n
q = a × (Twa − Troom )
This controller turns the heat pump and its associated Formula 4-2:
circulator on and off as necessary to keep the average
water temperature in the tank close to the target value
V=
(q )t
hp
calculated by the outdoor reset controller. 500(∆T )
The system automatically begins operation when the Where:
outdoor temperature drops below some preset value V = minimum volume of buffer tank (gallons)
known as the “warm weather shutdown temperature.”
t = length of desired
qhp t ( )
qhp = rated heat output of heat pump (Btu/hr)
36,000 10
V = on-cycle (minutes)
=
(
= 48gallons
)
There are no electrical thermostats in this system. All ∆T = temperature swing in buffer
500(∆T ) tank during on-cycle (ºF)
500(15)
room temperature control is regulated by the thermostatic
operators on the panel radiators. For example, assume the minimum desired on-cycle time
is 10 minutes, and the desired temperature change in the
BUFFER TANK SIZING buffer tank during that on-cycle is 15ºF. Determine the
The size of the buffer tank can be calculated based on the minimum buffer tank volume assuming the heat pump’s
desired on-cycle time of the heat pump, the heat pump’s rated output is 36,000 Btu/hr.
rated heating capacity, and the change in buffer tank
temperature during the on-cycle. Use Formula 4-2.
43
idronics 30 formulas
Figure 4-21
DHW
evaporator
outside outside
air air
inside
TXV
air vent
outdoor
rev. reset P&TRV
controller
outside
compressor
outdoor
unit
⎛ COP1 ⎞ ⎛ COP2 ⎞
⎜⎝ COP − 1⎟⎠ ⎜⎝ COP − 1⎟⎠ motorized
1 2 indoor unit diverter
COPnet =
⎡⎛ COP1 ⎞ ⎛ COP2 ⎞ ⎤ N.C. valve
cold water
⎢⎜ ⎟⎜ ⎟ − 1⎥
⎢⎣⎝ COP1 − 1⎠ ⎝ COP2 − 1⎠ ⎥⎦
condenser
N.O.
split-system air-to-water
heat pump
w/ variable-speed compressor
(in heating mode)
q = a × (Twa − Troom )
V=
(q )thp
500(∆T )
Just put the given values into Formula 4-2 and calculate. BUFFER TANKS & VARIABLE-CAPACITY HEAT PUMPS
V=
( q )t = (36,000)10 = 48gallons
hp
Several air-to-water and water-to-water heat pumps
are now available with variable-speed (“inverter driven”)
500(∆T ) 500(15) compressors. These heat pumps can reduce their
output down to 30-40 percent of their rated output. If the
Larger buffer tanks would allow either longer on-cycles, heating requirement of the smallest zone in the system
smaller values of ∆T, or some combination of both. Likewise, is approximately the same as the minimum output of
small buffer tanks would result in shorter on-cycles, the heat pump, one could argue against the need for
assuming the same desired tank temperature swing (∆T).
44
a buffer tank. However, in systems with several small opening resistance to prevent flow migration through
zones, such as individually controlled panel radiators in the chilled-water air handler when the heat pump and
each room, a buffer tank should still be used in heating circulator are off.
mode operation.
A Dirtmag separator is installed on the pipe leading into the
When multiple zones of heating are combined with heat pump. This location is also upstream of the heat pump’s
a single cooling zone, and the system is supplied circulator (whether internal or external). The Dirtmag separator
by a variable-capacity heat pump, it is possible to helps prevent dirt or ferrous metal particles from entering
use a buffer tank in heating mode, but not in cooling either the circulator or the heat pump’s heat exchanger, and
mode. This combination allows the buffer tank to be thus helps maintain peak performance and reliability.
maintained at an elevated temperature year-round to
supply preheating, or possibly all the heating required The system configuration shown in figure 4-21, and in
for domestic hot water. Figure 4-21 shows one possible subsequent details shown in figures 4-22 and 4-23, uses a
system configuration. variable-capacity (“inverter-driven”) heat pump. The internal
controls for this type of heat pump typically allow compressor
This system uses a “reverse” indirect water heater as a speed to be referenced to a user-set outlet water temperature
buffer tank. The heat pump maintains the water temperature in both heating and cooling mode.
in the shell of this tank between some upper and lower
temperature limits, such as 110 and 130ºF. Domestic When the heat pump is used to maintain the buffer tank
cold water passes upward through multiple copper coils within some range of temperature suitable for space heating
inside the tank whenever domestic hot water is drawn and domestic water heating, it should be turned on and off
from a fixture. That water is either partially heated or fully based on the buffer tank temperature, rather than the outlet
heated depending on the temperature of the water in the temperature from the heat pump. This typically requires an
tank shell, the flow rate through the internal coils, and the external controller that can open and close a set of electrical
desired domestic hot-water delivery temperature. contacts based on either a setpoint temperature and
associated differential, or on outdoor reset control.
In cases where the domestic water is only partially heated
as it passes through the coils, it’s possible to include an An example of setpoint control would be as follows:
electric tank-type or on-demand water heater. Figure 4-22 Heat pump = ON when tank sensor temperature drops to
shows piping for the latter. 100ºF or lower.
Heat pump = OFF when tank sensor temperature increases
The water leaving the heat pump in figure 4-21 enters the to 125ºF or higher.
common port of a motorized diverter valve. This valve is
energized when the heat pump operates in heating mode, An example of outdoor reset control, with specific settings,
allowing flow from the common port to the normally closed is shown in figure 4-24.
port, and onward to the buffer tank. When the heat pump
is off, the diverter valve is off, and the normally closed port With outdoor reset, the heat pump is turned on when
is closed. This prevents reverse thermosiphon flow from the sensor in the tank drops to the temperature shown
the buffer tank through the heat pump. It also prevents flow on the dashed green line in figure 4-24. The heat pump
returning from the space-heating load from flowing through continues to run until the sensor reaches the temperature
the heat pump when it is off. on the dashed red line. Outdoor reset controllers can
be adjusted to change the slope of these lines, the
The diverter valve should be selected with a flow coefficient temperature differential between the “on” and “off” lines,
(Cv value) approximately equal to the design flow rate the minimum supply water temperature setting, and in
through the heat pump. This limits the pressure drop through some cases, additional settings. This allows wide flexibility
the valve to approximately 1 psi and reduces circulator power in how the temperature of the buffer tank is regulated.
requirements.
Reducing the tank temperature as the outdoor temperature
Some air-to-water and water-to-water heat pumps are increases allows the heat pump to operate at higher COP.
supplied with an internal circulator, and some require an This is ideal when the system only provides space heating.
external circulator. Figure 4-23 shows pipe detailing for However, in systems that supply both space heating and
both cases. The spring-loaded check valve in the external domestic hot water, this control action decreases the
circulator, or as a separate component when an circulator temperature to which domestic water can be heated by
is present inside the heat pump, provides a slight forward the heat pump, especial during mild weather. This can
45
heating (blue line), or both space heating and domestic hot
Figure 4-22 water (red line). Any temperature boost needed to ensure
a DHW delivery temperature of 120ºF is assumed to be
provided by electric resistance heating. Figure 4-24 plots
seasonal average COP of the system versus the average
temperature at which the buffer tank is maintained by the
tankless electric isolation/
flushing thermostatic heat pump (e.g., based on setpoint control, not outdoor
water heater
valves mixing valve reset control). In this graph, the seasonal COP is for the
entire system, including energy supplied to supplemental
electric heating elements.
CW
DHW
If the heat pump is only used for space heating, and all
domestic hot water is provided by electric resistance
heating, the simulated seasonal average COP for the
system was 2.57.
46
Figure 4-23
spring-loaded
check valve
motorized
B
Inverter-drive diverter
variable valve
AB
capacty A
heat pump
w/ internal
circulator
normally closed
Btu/hr when supplying chilled water Whenever a heat pump (geothermal for operation. The most common
at 45ºF and receiving return water or air-to-water) can provide year- scenario is to prioritize domestic
at 55ºF, the air handler should also round domestic hot water as well as water heating over cooling. This
be able to absorb 22,000 Btu/ cooling, system controls must set is based on the likelihood that the
hr when operating at the average a priority as to which load the heat “call” for domestic water heating
water temperature of 50ºF (e.g., pump services at times when both can be satisfied quickly (perhaps
45ºF in/55ºF out). loads are simultaneously calling 5-10 minutes) during warm weather
47
when the cooling load is active. Once the
Figure 4-24 heat pump off tank that provides domestic hot water (e.g.,
target temperature the buffer tank in figure 4-21) has reached a
set temperature limit, the heat pump turns
heat pump on
off, goes into a typical 3-5 minute time delay
120 to allow for refrigerant pressures to equalize,
then resumes cooling mode operation.
80
70
70 60 50 40 30 20 10 0 5. EXAMPLE SYSTEMS
outdoor temperature (ºF) Previous sections have described the
advantages of using hydronic heating and
cooling in low-energy and net-zero buildings.
Simple and repeatable concepts have been
shown along with a range of appropriate
hardware.
Figure 4-25
48
SYSTEM #1: associated space when operating Each radiator is equipped with a
The system shown in figure 5-1 provides at a supply water temperature of thermostatic operator and supplied by
space heating and domestic hot water. 120ºF, with a 20ºF temperature a pair of 1/2-inch PEX tubes that begin
It uses a monobloc air-to-water heat drop, and thus an average water and end at a manifold station. The latter
pump with a single-speed compressor temperature of 110ºF. During has two additional sets of connection
and a reverse indirect water heater. partial load conditions, the water ports to allow other heat emitters to
The latter serves as a buffer tank and temperature in the buffer tank be easily added in the future.
domestic hot water source. is reduced based on outdoor
reset control. This maximizes the Flow to all radiators is provided by
Space heating is provided by seasonal COP of the heat pump, a variable-speed pressure-regulated
6 individually controlled panel while also ensuring that the supply circulator that operates continuously
radiators. Each radiator is sized water temperature to the radiators during the heating season. The
for the design heating load of its is high enough to maintain comfort. speed of this circulator automatically
TRV
Figure 5-1
TRV
thermostatic
radiator valves
(TRV) on each
radiator
tankless electric
water heater
isolation/
flushing to / from
valves panel rad #6
System operates with propylene
PRV
CW
DHW
air vent
P&TRV
outdoor
temperature
sensor spare
connections
OUTSIDE
outdoor
reset
controller
INSIDE
monobloc flexible
air-to-water heat pump connectors
49
changes as the thermostatic operators on the radiators the temperature setting of the outdoor reset controller to
open, close or modulate flow. If all radiator valves are closed, allow the heat pump to fully heat domestic water to 120ºF.
the circulator goes into a low-power “sleep” mode, typically The on-demand electric water heater could be turned off
drawing less than 10 watts of electrical power. The sleep during this time.
mode ends as soon as a radiator valve begins to open.
To protect the heat pump from freezing, the entire system
The majority of the domestic water heating takes place operates with a 30% solution of non-toxic propylene glycol
whenever hot water demand at a fixture pulls cold water antifreeze.
upward through the copper coils inside the buffer tank. Any
additional temperature rise needed to bring the domestic SYSTEM #2:
water to the desired delivery temperature is provided by an This system adds an electric boiler and associated details
on-demand electric water heater. to system #1. This boiler can provide supplemental heat
input if needed during extremely cold weather. It can also
During late spring, summer and early fall, when space serve as a backup heat source if the heat pump is down
heating is not required, it would be possible to increase for servicing.
TRV
Figure 5-2
TRV thermostatic
radiator valves
(TRV) on each
radiator
tankless electric
water heater
isolation/
flushing to / from
valves
panel rad #6
PRV
CW
DHW
2-stage
motorized
ball valves
outdoor air vent spare
reset connections
controller P&TRV
outdoor
temperature
sensor
OUTSIDE
INSIDE
electric
boiler
monobloc flexible
connectors
air-to-water heat pump
50
A 2-stage controller manages operation of both the heat flow returning from the manifold station from inadvertently
pump and electric boiler. It’s objective is to maintain the passing through either heat source when it is off.
buffer tank at a target temperature based on outdoor reset
control. This controller provides a 10-minute time delay Domestic water is heated the same way it was in system #1.
between activating the heat pump and possibly activating
the electric boiler. This allows time for the heat pump to SYSTEM #3:
stabilize its initial operation and gives the controller time to This system uses a split-system air-to-water heat pump
“decide” if a second stage of heat input is needed. with an inverter drive compressor to provide space heating
and cooling.
Motorized ball valves are installed in the piping for each
heat source. They open when their associated heat source Space heating is provided by a combination of panel
is on and close at all other times. These valves prevent radiators and low-thermal mass radiant ceiling panels,
reverse thermosiphon flow from the buffer tank through the all operating at the same supply water temperature and
piping of either heat source when that heat source is off. connected as a homerun distribution system. A variable-
They also prevent reverse flow through one heat source speed pressure-regulated circulator provides flow to this
when the other heat source is on. Finally, they prevent distribution system and automatically adjusts its flow rate
TRV with
capillary
dual isolation valve on each
tube
panel radiator
TRV
TRV
evaporator
outside outside
air air
variable-speed 1/2" PEX, PE-RT or
pressure-regulated PEX-AL-PEX tubing
INSIDE
circulator
TXV
spare
rev. connections
OUTSIDE
valve
heating mode
compressor
mainfold station
outdoor
reset
outdoor unit controller
outdoor
temperature motorized
sensor indoor unit diverter
valve
A
AB
condenser
51
and power input as the thermostatic valves on the radiators (e.g., magnetite). The manifold station includes additional
and radiant ceiling panel circuits open and close. connections that allows more heat emitters to be easily
added in the future.
The 3-way motorized diverting valve opens between the
AB and A ports when the heat pump operates in heating SYSTEM #4
mode, and closes between these ports at all other times. This system shows one way to add domestic water heating
This prevents reverse thermosiphoning between the buffer to system #3. It uses an external stainless steel brazed-
tank and heat pump when it’s off. plate heat exchanger mounted close to the buffer tank
to transfer heat into cold domestic water whenever the
During cooling mode, the motorized valve routes flow demand for domestic hot water reaches 0.7 gpm or higher.
between its AB and B ports. The heat pump’s compressor This threshold is determined by a flow switch mounted
speed automatically adjusts to maintain a chilled-water in the cold water pipe leading into the heat exchanger.
outlet temperature of 50ºF to the air handler. The temperature of the domestic water leaving this heat
exchanger depends on the buffer tank temperature, which
The system includes a Dirtmag separator to ensure that itself is regulated by outdoor reset control. In most cases,
the heat pump condenser and the circulators supplying this temperature will be lower than the desired DHW
the heat pump remain clean of dirt and magnetic particles delivery temperature. This system uses a standard tank-
TRV with
capillary
dual isolation valve on each tube
panel radiator
TRV
TRV
evaporator
outside outside
air air
variable-speed 1/2" PEX, PE-RT or
pressure-regulated PEX-AL-PEX tubing
INSIDE
circulator
TXV
on/off spare
rev. circulator connections
OUTSIDE
valve
heating mode
relay
refrigerant line set
compressor
stainless
outdoor steel
temperature motorized heat
sensor diverter exchanger
indoor unit CW
valve
A
AB domestic
water flow
condenser
B switch
52
type electric water heater to boost the preheated water to its SYSTEM #5:
final delivery temperature. This tank could also provide 100 A low-energy or net-zero home could also be fully heated
percent of the DHW load if the heat pump is down for service. by an electric boiler. An ideal application would be a home
with a high-performance thermal envelope in a cold climate
that doesn’t require cooling, and where electrical rates are
relatively low. In this scenario, the electric boiler may have a
lower life-cycle cost compared to a heat pump.
See idronics #29 for more information on sizing heat
exchangers for domestic water heating applications.
TRV
Figure 5-5
thermostatic
radiator valves
(TRV) on each
radiator
dual isolation valve on
each panel radiator
TRV TRV
electric SEP4
boiler (insulated)
heated basement
floor slab
spring
check
3-way outside
motorized temperature
mixing valve sensor
53
The system shown in figure 5-5 shows one example of To avoid this undesirable temperature depression, the
how an electric boiler can be configured to supply a heated system needs to operate in one of two possible control
floor slab in the basement and three panel radiators on the configurations.
home’s main floor.
Configuration #1: Provide ALL of the following requirements:
Although electric boilers can operate at elevated
temperatures without a decrease in efficiency, there are • Operate the boiler and its circulator continuously during
advantages associated with sizing the panel radiators the heating season, with the water temperature based
for a relatively low water supply temperature, such as on full outdoor reset control. The outdoor reset settings
120ºF, under design load conditions. Doing so allows the should allow the panel radiators to maintain room comfort
possibility of using a heat pump as a future heat source on a design load day. Most modern electric boilers have
without having to add heat emitters or increase the size internal controllers that allow for outdoor reset control.
of existing emitters. It also allows the radiators to have a
higher percentage of radiant versus convective heat output, • Operate the panel radiator circulator and the floor-heating
which improves comfort. Heat loss from the distribution circulator continuously during the heating season.
piping is also reduced when the system operates at lower
water temperatures. • Configure the mixing valve controller for outdoor reset
with settings sufficient to maintain the basement comfort
All-electric boilers require a minimum sustained flow rate level on a design load day.
whenever they operate. In this system, that flow is provided
by a dedicated low-power ECM circulator that operates • Equip the mixing valve controller with indoor temperature
continuously during the heating season. feedback, which eliminates the need for a thermostat in the
basement.
The SEP4 hydraulic separator and the short/generously
sized headers ensure that all three circulators are • Do not make frequent adjustments (such as nighttime
hydraulically isolated from each other. It also provides air, setback) to the desired basement air temperature.
dirt and magnetic particle separation for the system.
Configuration #2: Provide ALL of the following requirements:
The three panel radiators are supplied by a homerun
distribution circuit powered by a variable-speed pressure- • Operate the boiler and its circulator continuously at
regulated circulator. Each panel radiator is equipped with a a setpoint temperature high enough to allow the panel
dual isolation valve and a thermostatic operator. The latter radiators to maintain room comfort on a design day. A
allows each radiator to adjust its heat output to meet the suggested not-to-exceed temperature is 120ºF.
desired comfort level in the space served by that radiator.
• Install the boiler “return” temperature sensor — supplied
The floor-heating circuits in the basement are supplied with the mixing valve controller — on the outlet of the
through a 3-way motorized mixing valve, which reduces SEP4 hydro separator, and set the minimum boiler return
the supply water temperature relative to that supplied to temperature setting on this controller 2ºF lower than the
the panel radiators. supply water temperature required by the panel radiators
on a design day. This allows the controller to partially
The boiler piping, SEP4 hydro separator, and surrounding close the mixing valve’s hot port as necessary to prevent
metal piping should be insulated to minimize heat loss to a temperature drop that would otherwise limit the output
the building’s mechanical room. from the panel radiators.
This system combines a very high thermal mass heat emitter Control configuration #1 reduces piping heat losses, but
(e.g., the heated basement slab), with other very low thermal also counts on “consistent” operation of the basement
mass heat emitters (e.g., the three panel radiators). This floor-heating subsystem (e.g., not making frequent changes
combination sets up the possibility that the high mass slab can in the desired room temperature setting for the basement).
absorb much of the heat supplied by the boiler, especially if that
slab is warming from a cool starting condition. This transient Control configuration #2 allows for frequent changes in
condition can significantly depress the water temperature in the desired temperature setting for the basement. It also
the entire system and not allow the panel radiators to properly ensures that the panel radiators will have sufficient supply
heat their associated spaces. In effect, the slab’s mass will water temperature to maintain comfort in their associated
“dominate” where heat from the boiler is going. spaces. However, this configuration will result in higher heat
54
losses from the distribution piping. If used, it is essential to and ultimately to a homerun distribution system supplying
insulate all metal piping and piping components within the panel radiators. An alternative high-thermal mass floor-
mechanical room. heating distribution system is also shown.
Either control configuration is possible. The choice will likely The controls for this system turn on the electric boiler and
be based on how the air temperature of the basement will its circulator at the start of each off-peak period. The boiler
be (or won’t be) changed. and its circulator remain on until the thermal storage tank
temperature reaches 180ºF. Space heating can take place
SYSTEM #6: during this time, with excess boiler output routed into
Another possible application for an electric boiler in a thermal storage.
low-energy or net-zero house is when the local utility
offers time-of-use electrical rates, and the boiler can In this system, the panel radiators are sized to deliver design
be combined with thermal storage. The objective is to load output at a relatively low supply water temperature
operate the electric boiler as much as possible during of 110ºF. Doing so allows for the thermal storage tank to
times when low-cost “off-peak” rates apply, and keep be “discharged” to a relatively low temperature while still
the boiler off when possible during times when “on- supplying adequate heating capacity to the radiators.
peak” rates apply.
The amount of heat stored in the tank is 8.33 Btu/gallon/
Time-of-use rate structures vary among utilities. Most ºF. Thus, a 119-gallon tank undergoing a temperature
provide their lowest rates from late night to early morning. discharge from 180 to 110ºF would release 8.33 x 119
Some utilities also offer off-peak rates on weekends and x (180-110) = 69,390 Btus. This could represent several
holidays. hours of heating in a low-energy or net-zero home,
especially during partial load conditions.
One example of a time-of-use rate structure would be:
The 3-way motorized mixing valve blends hot water
• Between 11:30 PM and 7:00 AM weekdays, and between from the thermal storage tank, or coming directly from
11:30 PM Friday and 7:00 AM Monday, electricity is priced the electric boiler, with cooler water returning from the
at $0.05/kWhr. radiators to achieve a target supply water temperature to
the radiators. That target temperature is based on outdoor
• Between 7:00 AM and 11:30 PM weekdays, electricity is reset control. The latter allows the tank to supply the
priced at $0.20/kWhr. radiators down to the minimum water temperature that can
still maintain comfort in the building. On partial load days,
The feasibility of an off-peak thermal storage heating system that temperature could be in the range of 80ºF. The lower
depends on the utility rate structure, the building load, the this temperature can be, the greater the amount of heat the
thermal mass available for storing heating, and to some tank can deliver to the load on each discharge cycle.
extent, the willingness of the occupants to “cooperate”
with the system’s operating objectives. Buildings with If the tank cools to the point where the radiators can no
high-performance thermal envelopes can use smaller and longer maintain comfort, as determined by some minimum
less expensive thermal storage systems. Owners willing to tank temperature, the electric boiler is enabled to operate
reduce room temperatures, if necessary, during the final regardless of which electrical rate is in effect. Boiler
hours of an on-peak rate period will also help the system operation during on-peak periods should be minimized
minimize operating cost. to keep overall operating cost low. This situation would
typically occur during early evening hours, when the output
Low-energy or net-zero buildings with grid-connected/net- of a solar electric system is low or zero, and internal loads
metered solar photovoltaic systems are good candidates in the building tend to diminish.
for this type of system. The solar electric system is likely to
produce most of its output during times when on-peak utility The alternative concrete slab floor-heating system adds
rates apply. This solar-derived electricity would minimize substantial thermal mass to the system, extending its
the need for higher priced on-peak electricity from the utility ability to maintain comfort in the building for longer periods
grid, especially in situations where the electric boiler might when on-peak electrical rates are in effect. For example, a
have to operate during on-peak times. 4-inch-thick concrete slab can store 9.8 Btu/square foot/
ºF of temperature change. A 6-inch-thick slab can store
Figure 5-6a shows a possible system configuration in which 14.7 Btu/square foot/ºF of temperature change. Thus, a
an electric boiler supplies heat to a thermal storage tank, 1,500-square-foot slab, 4 inches thick, and undergoing
55
an average temperature drop of only 3ºF, can release solar heat gain, or where a large number of occupants or
44,100 Btus. other heat-generating activities may be present at times.
A word of caution is appropriate. High-thermal mass It is also critically important to insulate all piping and
distribution systems, although good at storing heat, and components in areas of the system that are subject to high
thus allowing buildings to “coast” through several hours water temperatures. Be sure that all components used are
without heat input from source equipment, are not well- rated to handle the highest water temperatures that might
suited to buildings where significant and unanticipated be present. The system shown in figure 5-6a also uses
internal heat gains might occur. This type of system should several spring-loaded check valves to limit heat migration
not be used in buildings that are designed for significant within the system.
TRV
Figure 5-6a
thermostatic
radiator valves
(TRV) on each
radiator
dual isolation valve on
each panel radiator
TRV TRV
outside
temperature
sensor
3-way
motorized
insulated mixing 1/2" PEX, PE-RT or
mechanical valve PEX-AL-PEX tubing
room piping
spring check
PRV
electric
boiler thermal
storage spare
tank connections
56
Figure 5-6b
outside ASSE 1017
temperature thermostatic
sensor mixing valve
DHW CW
3-way
spring motorized
insulated to / from
check mixing
mechanical low temperature
valve
room piping heat emitters
T&P
spring check
controller
PRV inner
SS
electric
tank
boiler
spare
spring connections
check
The thermal storage tank, piped as shown in figure a reasonable distribution temperature by the time it leaves
5-6a allows the electric boiler to operate at or above its the inner tank. If the minimum tank temperature will be
minimum flow rate, even when only a “trickle” of hot water lower, some type of auxiliary electric water heater (tankless
is passing into the 3-way mixing valve. It also provides or tank-type) could be added to boost the domestic water
hydraulic separation between the boiler circulator and the to its final desired temperature.
distribution circulator.
An ASSE 1017-listed thermostatic mixing valve, installed
Another variation on the system is shown in figure 5-6b. as shown in figure 5-6b, is critically important to ensure
that the domestic water leaving the tank doesn’t exceed
This system uses a “tank-in-tank” reverse indirect water 120ºF.
heater for thermal storage. Heat added to this tank by the
electric boiler can be used for either space heating or for
domestic water heating. The latter occurs within the inner SYSTEM #7:
stainless steel tank. This system provides multi-zone heating using a
combination of low-temperature, low-thermal mass panel
If the temperature in the tank shell is maintained at or radiators and radiant panels. It also provides a single zone
above 120ºF, the domestic water should be fully heated to of chilled-water cooling, and domestic-water heating. A
57
variable-capacity geothermal-sourced water-to-water heat individually isolated and flushed. Since the manifold station
pump serves as the primary heating and cooling source. is inside the building, it is possible to install the entire earth
loop without having to thermally fuse the HDPE pipe.
The heat pump is supplied from a closed earth loop system
consisting of four buried HDPE earth loop circuits piped in The earth loop subsystem includes an expansion tank as
parallel. All the earth loop circuits begin and end at a Caleffi well as a Caleffi Discaldirtmag separator, which removes
GeoCal manifold station, which allows each circuit to be air, dirt and magnetic particles from the earth loop fluid.
Figure 5-7
remote
setting
thermostatic dial
radiator valves
(TRV) on each
radiator TRV
variable-speed
inverter drive
compressor
electric water heater
spare
connections
heating mode
outdoor
reset
controller
variable-capacity buffer
motorized
water-to-water tank
diverter
heat pump
valve
A
AB
swing check
Caleffi
geothermal
HDPE earth loop tubing
manifold
station upper holes
(flow going to earth loops)
mechanically tightened
sealing collar
lower holes
(flow returning from earth loops)
core-drilled holes in wall
58
During heating mode, the heat pump maintains the buffer SUMMARY:
tank temperature based on outdoor reset control. This Demand for net-zero buildings is rapidly increasing across
keeps the water in the buffer tank just warm enough to North America and globally. The majority of buildings
ensure that comfort is maintained, while also maximizing designed to operate on a net-zero energy basis use
the heat pump’s COP. electrically powered heat sources and cooling sources
in combination with site-generated electricity from solar
All heat emitters are connected to a single homerun photovoltaic systems. Heat pumps of several types are
distribution system supplied from the buffer tank. Flow commonly used for heating and cooling. Among these are
through the heat emitters is controlled by a variable-speed air-to-water and water-to-water heat pumps, both of which
pressure-regulated circulator. All heat emitters are sized to are ideally suited to hydronic system applications.
meet the design loads of their associated building spaces
using a supply water temperature no higher than 120ºF. By combining modern heat pump technology with hydronic
heating and cooling distribution systems, designers can
Single-zone cooling is provided by a chilled-water air achieve benefits not possible with forced-air distribution
handler. The inverter-driven heat pump varies its cooling systems. These include superior comfort, radiant as well
capacity as necessary to maintain a chilled-water outlet as convective heat delivery, high distribution efficiency,
temperature of 45ºF. minimally invasive installation, the ability to heat domestic
water, the ability to coordinate with time-of-use electrical
Domestic water is heated by the heat pump’s desuperheater rates, adaptability of the distribution system to future
whenever the heat pump’s compressor is on. A small heating and cooling sources, and a long service life.
stainless steel circulator within the heat pump moves cool
domestic water from the lower portion of the tank-type The legislative, cultural and economic incentives that
water heater through the desuperheater and back to the encourage beneficial electrification and decarbonization,
tank. Any final temperature boost needed is provided by and the accompanying demand for low-energy and net-
an electric resistance heating element in the upper portion zero buildings, collectively represent one of the biggest
of the tank. opportunities set before the North American hydronics
market in decades. The concepts and details presented in
this issue serve as building blocks that creative designers
can assemble into systems that meet this demand and are
precisely tailored to the needs of each building.
Additional information on geothermal heat pump
systems is available in idronics #9.
59
APPENDIX A: CALEFFI HYDRONIC COMPONENTS
CALEFFI HYDRONIC COMPONENTS
NA551 Discal NA551 Discal
5517 ASME / CRN ASME / CRN 5020 5023 501
Discal 551 Minical Valcal Maxcal
551 Discal 553 5350
rotating Discal
collar Compact AutoFill AutoFill 573
AutoFill
Combo
132 132
127 FlowCal 127 FlowCal+ 121 FlowCal QuickSetter QuickSetter
5599 HydroLink
5599 HydroLink
60
APPENDIX B: CALEFFI PLUMBING COMPONENTS
5213
521 MixCal 520 AngleMix 521 MixCal 5212 Point-of-Use 5231 5231 6000 LegioMix 6000 LegioMix 6000 LegioMix
w/ Gauge w/ Gauge w/ Checks SinkMixer Mix Valve MixCal MixCal+
520 TankMixer Control
574 RPZ
130 142 NA5026 Backflow
Flo-Set Flo-Set PlumbVent Preventer
127 FlowCal 127 FlowCal+ 132 QuickSetter+
circulator w/
isolation flanges
4-way motorized
mixing valve
circulator w/ union
internal check
valve
& isolation pressure
flanges gauge
closely-spaced tees
variable-speed reversible water-to-water
pressure-regulated heat pump
circulator
monobloc air-to-water heat pump split-system air-to-water heat pump
diverter tee
heating mode
globe valves
pressure
ball valve relief valve
reversing
valve
pressure &
swing check valve temperature (P4)
relief valve
evaporator
condenser
spring-loaded
check valve
TXV
panel radiator
w/ isolation valve
purging valve
& TRV
hose bib
drain valve
horizontal
air handler
diaphragm
expansion
tank
brazed-plate
heat exchanger
indirect water heater wood-fired boiler pellet boiler
61
∆ Td = ⎢⎜ ⎟⎠ − Tair ⎥
⎣⎝ 2 ⎦
average water temperature in the radiator and the room air in=Appendix
112
temperature 180 - 68 = 112ºF. This temperature difference,
idronics 30 formulas
(Tin − Tair )
idronics 30 formulas in Appendix B
(T − T ) ( 92 − 65 ) = 0.54
u =(T out− T air) = 1.3
u =Q =(outTQin − ⎛⎜Tair∆ )=d ⎞( 92
air T
=
− 65
(1159500
) =⎛) 37.33
− 65 0.54 ⎞
1.3
= 2277
Btu
62
( in Tair⎝ 112
eT − 112
) (⎠115 − 65 ) ⎝ 112 ⎠
⎟ ⎜ ⎟
hr
∆ Td =
(Tin − Tout ) = (115 − 92 ) = 23 = 23
= 37.33º F
(T − T ) (115 − 92 ) 23 23
∆ Td = ⎛ Tinin− Tairout⎞ = ⎛ 115 − 65 ⎞ = ⎛ 50 ⎞ =ln(1.85185) = 37.33º F
ln
ln ⎜ ⎛ Tin − Tair⎟ ⎞ ⎜⎝ ⎛ 115 − 65⎟⎠ ⎞ ln ⎜ ⎛ 50⎟⎠⎞ ln(1.85185)
⎝lnT⎜out − Tair ⎠ ⎟ ln ⎜⎝9292− −6565 ⎟⎠ ln⎝ ⎜⎝27
27 ⎠
⎟
⎝ Tout − Tair ⎠
1.3
⎛ 30.83 ⎞
2500 = Q112 ⎜
⎛ ∆ T ⎞ 1.3
1.3
⎛ 37.33 ⎞
1.3
1.3 Btu ⎝ 112 ⎟⎠
temperatureQofe Q
=180ºF ⎛ ∆d T⎟a
Q=112Q⎜ and = 9500
d ⎞room ⎜ ⎛ 37.33
⎟ ⎞ ==2277
temperature of Btu
68ºF. This can be solved for the necessary output at the ∆Td =
⎝ 112
⎜⎝ ⎠ ⎟⎠ = 9500 2277
⎝ ⎜⎝112 ⎠ ⎟⎠ hrhr
112 112
e 112
112ºF
Solution: Start with Formula B4: Q112 =
( 2500 ) = 13, 374
Btu
1.3
⎛ 30.83 ⎞ hr
(T (T− T−airT) =) ( 90( 90− 70
u =u = out
) )= 0.44
− 70
⎜⎝
112 ⎠
⎟
) ) = 0.44
out air
=
(Tin(T− T−airT) ) (115
in air (115− 70
− 70
At this point, the designer can look through a table of radiator
Since u < 0.7 use Formula B3 to get ∆Td: ratings based on an average water temperature of 180ºF
and a room air temperature of 68ºF to find one or more panel
∆ T∆d T=d =
(115(115− 90 ) ) = =30.83º
− 90
30.83º
FF radiators that can output approximately 13,400 Btu/hr.
115
⎛ ⎛ 115
− 70
− 70
⎞ ⎞
ln ⎜ln ⎜ ⎟ ⎟
⎝ 90⎝ 90 − 70
− 70 ⎠ ⎠
Based on data from one manufacturer, a radiator with three
Next, set up Formula 1 with all the known information, water plates, a height of 24 inches, and length of 48 inches
including the required heat output at the lower water has an output of 13,664 Btu/hr, which is very close to
temperature (e.g., 2,500 Btu/hr): calculated output at ∆Td = 112ºF. A radiator with three water
1.3 plates that is 20 inches high and 64 inches long has a listed
⎛ 30.83 ⎞ output of 15,829 Btu/hr — more than enough.
2500 = Q112 ⎜
⎝ 112 ⎟⎠
Q112 =
( 2500 ) = 13, 374
Btu
1.3
⎛ 30.83 ⎞ hr
⎜⎝ ⎟
112 ⎠
63
www.caleffi.com
QUICKSETTER™
FAST, EASY AND
ACCURATE BALANCING
The Caleffi QuickSetter’s built-in visual flow meter simplifies balancing by allowing the contractor to adjust flow
while viewing flow rate directly on the valve itself. There is no need for time-consuming differential pressure
instruments that traditional static balancing valves require. Zone balancing is fast, easy, and accurate with
QuickSetter. CALEFFI GUARANTEED.