Functions and Communication

characteristics Compact NS100 to 630

Integration of the circuit breaker or the There are two possibilities for the 100 to 630 A range:
switch-disconnector in a supervison system b communicating auxiliaries
requires either the communicating They replace the standard auxiliaries and connect directly to the Digipact bus.
Three equipment levels:
auxiliaries or the SC150 interface. v communicating auxiliary contacts, comprising:
Compact devices fit perfectly in the SMS - OF (on/off), SD (trip indication) and SDE (fault-trip indication) contacts
Powerlogic electrical installation - electronic module
management system by communicating - prefabricated wiring.
v communicating auxiliary contacts and motor-mechanism module, comprising:
using Digipact protocols. An external - OF (on/off), SD (trip indication) and SDE (fault-trip indication) contacts
gateway offers communication via other - motor-mechanism module (220 V AC) (1)
networks including: - electronic module
b Profibus - prefabricated wiring.
v communicating carriage switches for the chassis, comprising:
b Ethernet - CE / CD (connected/disconnected position) contacts
- electronic module
053172

- wiring connector.
b SC150 interface
Using the SC150 interface, it is possible to integrate a device equipped with non-
communicating auxiliaries into a supervison system.
The SC150 interface is used to connect:
v the auxiliary contacts on the circuit breaker (OF, SD, SDE, SDV, CD, CE)
v the remote-operation system (on, off, reset)
v the communication output for the STR53UE and STR43ME electronic trip units
equipped with the COM option
v an unassigned digital input.

Compact NS equipped with communicating auxiliary contacts


and motor-mechanism module
054481

Withdrawable Compact NS on its chassis equipped with


communicating auxiliary contacts
054516

SC150 indication and control interface

(1) For voltages other than 220 V AC, use a standard motor-mechanism module (non-
communicating) together with an SC150 indication and control interface.

72
Overview of functions
E94526

Software

Communication
interface RS 232C,Ethernet
RS 485

Communication
bus

IN JBus
LIN GER
MERSV
pulsar BBus
com

com error

24V

Data concentrator
OK

error

1 3

DC150
N°1
N°1

Device

SC150 indication and


control interface

act
comp
0NH
NB25 Uimp 8kV.
Ui 750V. Icu
(kA)
Ue
(V) 100
0
220/245
70 2
65
380/41 ed
50 discharg
440 5
10
500/520
660/69
85
compactL
NS250 Uimp 8kV.
O OFF
Ui 750V. Icu(kA)
250 act
0% Icu Ue(V) 150
comp

Compact NS with
Ics=10 220/240 150
0NH
380/415 130
∅5...8 NB25 Uimp 8kV.
cat A
70
440
500
20
100
Ui 750V. Icu

Digipact Bus
600/690 (kA)
NEMA
-2 UNE 0 250
250
D Ue
IEC947 BS CEI cat A TM Icu °C 100
VDE 125/16 (V)
UTE push
to
100%
Ics = 250A/40
VDE 220/245
0 70 2
trip
UTE
947-2UNE NEMA 65
IEC
CEI 380/41 ed
5
BS
50 discharg
Im 10 440 5
10
6 500/520 compactL O OFF

communicating Compact circuit breaker with standard


Ir 85
660/69 NS250 Uimp 8kV.
9
Im
1 Ui 750V. Icu(kA)
7 250
Ir 0% Icu 150

1
.9
.8
8
x 250A I Ics=10
Ue(V)
220/240
380/415
150
130
∅5...8
x 250A auto O push
ON cat A 440
500
70
20
100
600/690
manu OFF -2 UNE
NEMA
0 250 D
push IEC947
VDE
BS CEI
125/16
250
cat A TM Icu °C
100%
UTE push Ics = 250A/40
to UTE
VDE
trip 947-2UNE NEMA

auxiliary contacts auxiliary contacts and motor mechanism.


IEC
CEI
BS
5
Im 10
6
Ir 9
Im
1
7
Ir
1
.9
.8
8
x 250A I
x 250A auto O push
ON
manu OFF

and motor mechanism Trip unit with the COM option.


push

: hard wire
: communication bus Compact with
communicating SC150
auxiliaries
Device identification
Address b b
Rating - -
Indication of status conditions
OF (on/off) b b
SD (trip indication) b b
SDE (fault-trip indication) b b
CE/CD (connected/disconnected position) b b
Controls
ON/OFF b b
LED reset b b
Protection settings
Reading of the protection settings b
Operating and maintenance aids
Measurements: currents b
Fault readings: type of fault b
Indications: operation counter b b

73
Functions and Communication
characteristics Compact NS630b to 1600
COM option in Compact

The COM option is required for integration For fixed circuit breakers, the COM option is made up of:
of the circuit breaker or switch- b a "device" communication module, installed behind the Micrologic control unit
disconnector in a supervision system. and supplied with its set of sensors (OF, SD, SDE micro-contacts for manually
operated devices; OF, SDE micro-contacts for electrically operated devices) and its
Compact uses the Digipact or Modbus kit for connection to a communicating motor-mechanism module.
communications protocol for full For withdrawable circuit breakers, the COM option is made up of:
compatibility with the SMS PowerLogic b a "device" communication module, installed behind the Micrologic control unit
electrical-installation management and supplied with its set of sensors (OF, SD, SDE micro-contacts for manually
systems. An external gateway is available operated devices; OF, SDE micro-contacts for electrically operated devices) and its
kit for connection to a communicating motor-mechanism module
for communication on other networks: b a "chassis" communication module supplied separately with its set of sensors
b Profibus (CE, CD and CT contacts).
b Ethernet… Status indication by the COM option is independent of the circuit breaker indication
The eco COM is limited to the transmission contacts. These contacts remain available for conventional uses.
of metering data and does not allow the Digipact or Modbus "device" communication module
This module is independent of the control unit. It receives and transmits information
control of the circuit breaker.
on the communication network. An infra-red link transmits data between the control
unit and the communication module.
056431

Digipact "device"
Consumption: 30 mA, 24 V.
communication module.
Digipact or Modbus "chassis" communication module
This module is independent of the control unit. The Modbus "chassis"
communication module makes it possible to address the chassis and to maintain
the address when the circuit breaker is in the disconnected position.
Consumption: 30 mA, 24 V.
Communicating motor-mechanism module
A bus link is used to transmit remote ON/OFF orders to the circuit breaker.
A communicating motor-mechanism module must be used.
The remote-tripping function (MX or MN) is independent of the communication option.
E59437A

Communication Communication
bus bus
056401

Digipact "chassis"
communication module
OF
SD OF
SDE SDE
3 3
1 1 5

I on

tripped

reset
F
0 OF

Modbus "device" Manually operated Electrically operated


056431

fixed device fixed device


communication module

Communication Communication
bus ++ bus ++

CCM
modb
us

2 CCM
modb
us

2
+ +
CE

CE
CD

CD
CT

CT

4 4
C CT C CT
CE CE
CD OF CD
OF
SD SDE
SDE 3 3
1 5
1
E45183

Modbus "chassis"
communication module

Manually operated Electrically operated


drawout device drawout device

1 "device" communication module 4 CE, CD and CT "chassis" sensors


2 "chassis" communication module 5 communicating motor-mechanism module
3 OF, SD, SDE "device" sensors

Note. eco COM


The eco COM Modbus is intended to fit the circuit breaker with a module display
(DMB300, DMC300…).

74
Overview of functions

Compact circuit breakers and switch-disconnectors are compatible with the


E47071

POWERLOGIC System Manager Demo


FileEdit View Setup Control Display Reports Tools Window Help
Sampling Mode : MANUAL 5 seconds Digipact or Modbus COM option.
The COM option may be used with all types of control units to:
Time Event Module b identify the device
Phase A-N Voltage - Harmonics Analysis
b indicate status conditions
Phase 1-N
1,20
Harmonics(RMS)
b control the device.
1,00
Fundamental:
RMS:
H1: 118.09
H2: 0.01
H3: 0.45
H4: 0.03
Depending on the different types of Micrologic (S, A) control units, the COM option
RMS-H:
H5: 0.45
H6: 0.04
H7: 1.27
also offers:
0,80 Peak: H8: 0.05
H9: 0.42
b setting of the protections functions
% Fundamental

CF: H10: 0.01


H11: 1.03
THD: H12: 0.07
0,60 b analysis of the AC-power parameters for operating-assistance and maintenance
OK

0,40
purposes

0,20
Switch-disconnector with Circuit breaker with
0,00
H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 communication bus communication bus
Harmonics
Digipact Modbus Digipact Modbus
Ready ONLINE: DEMO No working system 9:30
Device identification
Address b b S A S A
Rating - - A A
Type of device - -
Type of control unit - - A A
Type of long-time rating plug - - A A
Status indications
OF (on/off) b b S A S A
SD (trip indication) b b S A S A
SDE (fault-trip indication) b b S A S A
CE/CD (connected/ b b S A S A
disconnected position)
Controls
MX/XF ON/OFF b b S A S A
Spring charging - -
Reset of the mechanical - -
indicator
Protections settings
Reading of protections settings A A
Operating and maintenance aids
Measurements
current A A
Fault readings
type of fault A
Note.
S = Micrologic 2.0 and 5.0
A = Micrologic with ammeter
See the description of the Micrologic control units for further details on protection.

75
Functions and Communication
characteristics Compact NS630b to 1600 (cont.)
Compact in a communication network
E94525

Software

Communication
interface RS 232C, Ethernet
RS 485

Communication
bus

IN JBus
LIN GER
MERSV
pulsar BBus
com

com error

24V

Data concentrator
OK

error

1 3

DC150
N°1
N°1

Device

Digipact Bus Modbus Bus

Compact Compact

Devices
Circuit breakers equipped with Micrologic control units may be connected to either
a Digipact or Modbus communication bus. The information made available
depends on the type of Micrologic control unit (S, A) and on the type of
communication bus (Digipact or Modbus).
Switch-disconnectors may be connected exclusively to the Digipact communication
bus.

Communication bus
Digipact bus
The Digipact bus is the internal bus of the low-voltage switchboard in which the
Digipact communicating devices are installed (Compact with Digipact COM,
PM150, SC150, UA150, etc.). This bus must be equipped with a DC150 data
concentrator (see the Powerlogic System catalogue).
Addresses
Addressing is carried out by the DC150 data concentrator.
Number of devices
The maximum number of devices that may be connected to the Digipact bus is
calculated in terms of “communication points”. These points correspond to the
amount of traffic the bus can handle. The total number of points for the various
devices connected to a single bus must not exceed 100.
If the required devices represent more than 100 points, add a second Digipact
internal bus.
Communicating device Number of points
DC150 data concentrator 4
Micrologic + Digipact COM 4
PM150 4
SC150 4
UA150 4

Length of bus
The maximum recommended length for the Digipact internal bus is 200 meters.
Bus power source
Power is supplied by the DC150 data concentrator (24 V).

76
Modbus bus
The Modbus RS 485 (JBus) system is an open bus on which communicating
Modbus devices (Compact with Modbus COM, PM300, Sepam, Vigilohm, etc.) are
installed. All types of PLCs and microcomputers may be connected to the bus.
Addresses
The software layer of the Modbus protocol can manage up to 255 addresses (1 to 255).
The “device” communication module comprises three addresses linked to:
b circuit-breaker manager
b measurement manager
b protection manager.
The “chassis” communication module comprises one address linked to:
b the chassis manager.
The division of the system into four managers secures data exchange with the
supervision system and the circuit-breaker actuators.
The manager addresses are automatically derived from the circuit-breaker address
@xx entered via the Micrologic control unit (the default address is 47).
logic addresses
@xx Circuit-breaker manager (1 to 47)
@xx + 50 Chassis manager (51 to 97)
@xx + 200 Measurement manager (201 to 247)
@xx + 100 Protection manager (101 to 147)

Number of devices
The maximum number of devices that may be connected to the Modbus bus
depends on the type of device (Compact with Modbus COM, PM300, Sepam,
Vigilohm, etc.), the baud rate (19200 is recommended), the volume of data
exchanged and the desired response time. The RS 485 physical layer offers up to
32 connection points on the bus (1 master, 31 slaves).
A fixed device requires only one connection point (communication module on the
device).
A drawout device uses two connection points (communication modules on the
device and on the chassis).
The number must never exceed 31 fixed devices or 15 drawout devices.
Length of bus
The maximum recommended length for the Modbus bus is 1200 meters.
Bus power source
A 24 V DC power supply is required (less than 20 % ripple, insulation class II).

Communication interface
The Modbus bus may be connected to the central processing device in any of
three manners:
b direct link to a PLC. The communication interface is not required if the PLC is
equipped with a Modbus port;
b direct link to a computer. The Modbus (RS 485) / Serial port (RS 232)
communication interface is required;
b connection to a TCP/IP (Ethernet) network. The Modbus (RS 485) / TCP/IP
(Ethernet) communication interface is required.

Software
To make use of the information provided by the communicating devices, software
with a Modbus driver must be used.

Micrologic utilities
This is a set of Modbus drivers that may be used with a PC to:
b display the variables (I, U, P, E, etc.) with the RDU (Remote Display Utility)
b read/write the settings with the RSU (Remote Setting Utility)
b remotely control (ON / OFF) the device with the RCU (Remote Control Utility)
These utilities are available on request.

System Manager Software (SMS)


SMS is a power management software for the control and monitoring of LV and MV
electrical installations.
The SMS family includes a number of products for all types of applications, from
standalone systems to networked power management of multiple buildings.
SMS can communicate with all intelligent devices of the electrical installation
including:
b Power Meter and Circuit Monitor products
b LV circuit breakers and switch-disconnectors
b Sepam units.

77
Functions and Communication
characteristics Compact NS1600b to 3200
COM option in Compact

The COM option is required for integration For fixed circuit breakers, the COM option is made up of:
of the circuit breaker or switch- b a "device" communication module, installed behind the Micrologic control unit
and supplied with its set of sensors (OF, SD, SDE micro-contacts).
disconnector in a supervision system.
Status indication by the COM option is independent of the circuit breaker indication
Compact uses the Digipact or Modbus
contacts. These contacts remain available for conventional uses.
communications protocol for full
Digipact or Modbus "device" communication module
compatibility with the SMS PowerLogic This module is independent of the control unit. It receives and transmits information
electrical-installation management on the communication network. An infra-red link transmits data between the control
systems. An external gateway is available unit and the communication module.
Consumption: 30 mA, 24 V.
for communication on other networks:
b Profibus
E59438
b Ethernet… Communication
bus
056431

Digipact "device"
communication module.

OF
SD
SDE
2

1 OFF
OFF

COM
module
056431

Modbus "device"
communication module 1 "Device" communication module
2 OF, SD, SDE "device" sensors

78
Overview of functions

Compact circuit breakers and switch-disconnectors are compatible with the


E47071

POWERLOGIC System Manager Demo


FileEdit View Setup Control Display Reports Tools Window Help
Sampling Mode : MANUAL 5 seconds Digipact or Modbus COM option.
The COM option may be used with all types of control units to:
Time Event Module b identify the device
Phase A-N Voltage - Harmonics Analysis
b indicate status conditions
Phase 1-N
1,20
Harmonics(RMS)
b control the device.
1,00
Fundamental:
RMS:
H1: 118.09
H2: 0.01
H3: 0.45
H4: 0.03
Depending on the different types of Micrologic (S, A) control units, the COM option
RMS-H:
H5: 0.45
H6: 0.04
H7: 1.27
also offers:
0,80 Peak: H8: 0.05
H9: 0.42
b setting of the protections functions
% Fundamental

CF: H10: 0.01


H11: 1.03
THD: H12: 0.07
0,60 b analysis of the AC-power parameters for operating-assistance and maintenance
OK

0,40
purposes

0,20
Switch-disconnector with Circuit breaker with
0,00
H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 communication bus communication bus
Harmonics
Digipact Modbus Digipact Modbus
Ready ONLINE: DEMO No working system 9:30
Device identification
Address b b S A S A
Rating - - A A
Type of device - -
Type of control unit - - A A
Type of long-time rating plug - - A A
Status indications
OF (on/off) b b S A S A
SD (trip indication) b b S A S A
SDE (fault-trip indication) b b S A S A
Protections settings
Reading of protections settings A A
Operating and maintenance aids
Measurements
current A A
Fault readings
type of fault A
Note.
See the description of the Micrologic control units for further details on protection.

79
Functions and Communication
characteristics Compact and the MPS100
Micro Power Server

The MPS100 Micro Power Server: Micro Power Server makes data collection easy
b notifies maintenance staff when for monitoring Masterpact / Compact circuit breakers
any preset alarm or trip is activated Now, more than ever, there is a need to monitor electrical distribution systems in
industrial and large commercial applications. The key to managing all equipment,
by the Micrologic trip unit, automatically maximising efficiencies, reducing costs and increasing up time is having the right
sending an e-mail and/or SMS tools.
b data logs are periodically forwarded Micro Power Server MPS100 is designed to withstand harsh electrical
by e-mail environments and provide a consistent flow of easy to interpret information.
b the e-mails are sent via an Ethernet local
area network (LAN) or remotely Micro Power Server is designed for unattended operation
via modem. within the main LV switchboard
The MPS100 is a self-contained facility information server that serves as a stand-
E90463

alone device for power system monitoring.


It is used to transfer power system information via a standard web browser over
an Ethernet local area network (LAN) or via modem, making it possible to view
power system information on a PC with an Ethernet connection.
In either capacity, the Micro Power Server functions as a web server for Micrologic
trip unit and Power Meter (PM500) supervision, automatically notifying (e-mail
E91685-60

and/or SMS) maintenance staff when any preset alarm or trip is activated in
the Micrologic trip unit.

Benefits
b view your main LV switchboard without installing software on your local PC,
MPS100 Micro Power Server.
eliminating the need for a dedicated PC with specific software
b Micro Power Server allows centralised monitoring, so you no longer waste
056993

precious time walking around the facility to collect data


b view your main LV switchboard via a modem connection (GSM or switched
network), avoiding the need for a LAN
b maintenance people are automatically notified at any time, wherever they are,
so you do not have to stay in front of a monitor all day long
b data logs can be periodically forwarded by sending e-mails to the relevant people
(maintenance, accounting, application service provider) automatically
b possibility to monitor/notify six external events (limit switches, auxiliary
switches...)
b back-up of Micrologic trip unit settings in the memory of the MPS100, so you
know where to retrieve it when necessary.

Main LV switchboard.
DB100435

Monitoring of your main LV switchboard via a standard web


browser.

80
Typical architecture
056993-34

E95414

It is possible to combine the different types of architecture.

Supported Modbus devices


E89544-14

b Micrologic trip units


b Power Meters (PM500).
Maximum recommended connected devices is 10.
062052-15

Features
b access to the power system via a standard PC web browser
b real-time data displayed with an intuitive and user friendly interface
Micrologic trip unit. Power Meter PM500. (dashboard)
b Ethernet Modbus TCP/IP connectivity directly to the LAN or via modem (Point to
Point Protocol services)
E95405R

b SMTP (Simple Mail Transfer Protocol) client (capacity to send e-mail)


Main switchboard at b local logging of data such as energy, power, current…
Plaza hotel. b set-up and system configuration through MPS100 embedded HTML pages
Air conditioning breaker b user interface translatable in any language, factory settings in English and
tripped on ground fault French
Ig = 350 A. b 6 inputs/2 outputs (no-volt contact)
06:37 on 10/12/2002
b DHCP (Dynamic Host Configuration Protocol) client.

Technical characteristics
Power supply 24 V DC ±15 %, consumption = 250 mA
Operating temperature 0 to +50 °C
Rugged compact metal housing 35 x 218 x 115 mm (H x W x D)
Additional information available at: http://194.2.245.4/mkt/microser.nsf
User name: MPS, Password: MPS100

Part numbers
Micro Power Server MPS100 33507
Short Message Service (SMS).
24 V DC power supply PS080