Professional Documents
Culture Documents
FMEAReport Switchyard BLDG Grounding Sys
FMEAReport Switchyard BLDG Grounding Sys
Task Responsi
FF Mode FF Effect FF Cause Sev Det Occ RPN Task Freq. Active Comment
Category bility
Grounding Rod Broken Unit Derating Broken 4 4 6 96 PM Inspection W26 ELEC Yes -
Grounding Rod Corrosion Unit Derating Electrolytic 4 4 6 96 PM Inspection W26 ELEC Yes -
Grounding Rod Corrosion Unit Derating Weak Acid (contaminant) 4 4 6 96 PM Inspection W26 ELEC Yes -
Grounding Rod
Unit Derating Aging 4 4 4 64 PM Ground Tester W26 ELEC Yes -
Resistance Increase
Grounding Rod
Unit Derating Contamination 4 4 4 64 PM Ground Tester W26 ELEC Yes -
Resistance Increase