1、Overview ................................................................................................
................................ ......................................... 1
1.1 Preface ................................................................................................
................................ .....................................1
1.2 Purpose ................................................................................................
................................ ....................................1
1.3 Safety Instructions ................................................................
....................................................1
2、System
System Brief Description ................................................................
.................................................2
3、System Function................................
..............................................................................................
..............................3
4、System Structure................................
.............................................................................................
.............................4
5、System
System Components ................................................................
.......................................................4
6、Operation method................................
............................................................................................
............................6
6.1 Layout and Description of Operation Panel ................................
..............................................6
6.1.1 Three-levellevel alarm status indication ................................
..................................................6
6.1.2 Work and Fault Indication................................................................
Indication ................................6
6.1.3 Dormant Time................................................................
Time ..................................................7
6.1.4 Watch Mode ................................................................
....................................................7
6.1.5 Reset/Call................................................................
Reset/Call ........................................................8
6.1.6 Dimming and Key ................................................................
............................................8
6.1.7 Key switch ................................................................
.......................................................8
6.2 Operation Settings ................................................................
....................................................9
6.2.1 Dormant time settings and protection ................................
..............................................9
6.2.2 Duty time setting and protection ................................
......................................................9
6.2.3 Reserve duty personnel selection ................................
...................................................9
6.2.4 System self-test................................................................
self ...............................................9
6.3 Alarm mode setting................................................................
setting ...................................................9
6.3.1 Alarm mode setting of 2nd. And 3rd. level................................
.......................................9
6.3.2 Delay the interval time for 2nd and 3rd alarm................................
alarm ................................10
6.4 Infrared and microwave motion detection function................................
function..................................10
6.5 Special Remind................................
.......................................................................................
.......................10
6.6 Bridge navigational Watch Alarm system/Nautical Equipment Fault
Alarm Operation method (Only touch screen version has this function) .......11
6.6.1 Layout and Description of Operation Panel ................................
...................................11
6.6.2 Emergency Call ................................................................
.............................................13
6.6.3 Key Switch................................................................
Switch .....................................................13
7、System
System Maintenance................................................................
Maintenance .....................................................14
8. Guidelines for BNWAS Installation................................................................
Installation ..................................16
9、Accessory................................
................................................................................................
......................................17
Drawing and operating instructions................................................................
instructions .....................................18
1、 Overview
1.1 Preface
The new generation of HAPCON® bridge navigational watch alarm system (HTC-BNW)
has been developed and manufactured according to MSC128.(75) of IMO and IEC62616. It
can be easily used in a variety of ships’ building and old vessels to renew with it’s compact
This operation manual described the standard configuration of bridge navigational watch
alarm system. Specific system may contain more components with extended function, its
1.2 Purpose
The purpose of this manual is designed to help operators on ship to understand the basic
functions and principles of the bridge navigational watch alarm system, so the operators can
PERSONNEL
Repair and maintenance personnel must be trained by our company. The maintenance
personnel should be informed that the possible faults and read the relevant security
ATTENTION
Operators must ensure that equipment should be in normal working status before
Please cutting off the device power supply immediately when equipment is found
1
2、System Brief Description
The bridge navigational watches alarm system can ascertain the status of duty officer and
monitoring the duty officer’s good vigilance. Turn the key switch to start-up system, you have
three selection mode:” Manual off mode”, ” Manual on mode”” Automatic mode”. Under”
Manual off mode”, System does not run in any status; Under ”Manual on mode”, the time
showed on digital tube will be countdown from the initial default of 3 minutes. When the
countdown to zero, operation panel and the light(s) on Reset Board flashing to pre-alarm. It
appearsⅠ-level sound and light alarm if pre-alarm continued up to 15 seconds and Reset
button is not pressed.Ⅱ-level sound and light alarm will appears if Ⅰ-level sound and light
alarm continued up to 15 seconds and Reset button is not pressed. Ⅲ-level sound and light
alarm will appears if Ⅱ-level sound and light alarm continued up to 90 seconds and Reset
button is not pressed,that is, all indicator lights on Reset Board and Extension Alarm Board will
appears sound and light alarm, until the Reset Button is pressed. When the Reset Button is
pressed, the system re-timing and starts the next cycle .Under” Automatic mode”, system
waits for the signals from autopilot and working steering to enable the equipment e, start a new
normal countdown working state. At the same time, the system can receive the signals from
radar, VDR, Electronic Chart and motion detection etc,, the system can reset the dormant
time.
2
3、System Function
Dormant time countdown function. Setting range: 3 mins. to 12mins.
Dimming function.
Radar , electronic charts and other navigational equipments Lose power fault, sound
and light alarm will give out(Only touch screen version of this function)
3
4、System Structure
MOTION SENSOR
HTC-BNW-114 OUTPUT:POWER FAIL/SYSTEM ACTIVE/FAIL/ALARM STAGE
To VDR、GA &PA SYSTEM
INPUT:AUTOPILOT(AUTO-ON)
RADIO、AUTOPILOT、ECDIS(RESET
RESET)
RESET UNIT
HTC-BNW-111
POWER UNIT
HTC-BNW-115
CONTROL PANEL
I/O UNIT
HTC-BNW-110
HTC-BNW-113
PORT、STARBOARD
STARBOARD WING NAVI.DECK
CAPTAIN CHIEF OFF 2ND OFF 3RD OFF OFF’S MESS CONFERENCE ROOM
5、System Components
The model named and defining method
Touch screen
Hapcon marine
automation products
1 IP22
BNWAS 2 IP56
A Panel Mount
110 operation unit
B Wall Mount
111 reset unit
4
Power Protection
Number Name Type Installing mode
source grade
Operation
1 HTC-BNW-110-A1 DC24V IP22 Panel Mount
Unit
Operation
HTC-BNW-110-B1
2 Unit DC24V IP22 Wall Mount
(HTC-BNW-113)
+I/O Unit
Operation
3 HTC-BNW-110-A1-T DC24V IP22 Panel Mount
Unit
Operation
4 HTC-BNW-110-B1-T DC24V IP22 Wall Mount
Unit
Motion
12 HTC-BNW-114 DC24V IP22 Wall Mount
detection
AC220V
13 Power Unit HTC-BNW-115 IP22 Wall Mount
AC110V
5
6、 Operation method
6.1 Layout and Description of Operation Panel
indication
alarm
6
6.1.3 Dormant Time
Unit: minute.
indicator is on.
indicator is on.
Manual/Automatic mode
1、Captain
2、Chief officer
3、Second officer
4、Third officer
7
6.1.5 Reset/Call
8
6.2 Operation Settings
Turn the key from ”OFF” to “ON’, press “+” or“–” to increase or decrease
the setting value of dormant time within 30 seconds. Setting range:3 minutes~
Turn the key from ”OFF” to “ON’, press “MODE” key to switch duty mode
Press and hold “backup” key 3 seconds, reserve person can be switched
once. General backup duty personS are one of Captain, mate, 2nd. officer, 3rd.
officer.
System self -check function can be carried on under any circumstances, press
“RESET/TEST” key, the system begins to self-test, the reset unit and the
extension alarm unit connected to the system will be flashing and the alarm rings.
Pressing the key “RESET/TEST” again, the sound will be mute and light will
not be flashing
System default setting has three level alarm mode. According to the practical
requirements of different vessels, the level mode can be changed to two level
extension alarm mode. That is to say, in two level extension alarm mode, all
extension alarm units will appear sound and light alarm (Except for passenger ships).
Setting method: Generally based on users’ requirements, system had been setting
9
well before delivery from factory. The setting method is not open to users.
6.3.2 Delay the interval time for 2nd and 3rd alarm
System default that the Interval time between 2nd. And 3rd. level is 90 seconds. For
large ships this interval time may be extended to the maximum 3 minutes. Setting
method : Generally based on users’ requirements system had been setting well
before delivery from factory. The setting method is not open to users.
Bridge navigational watch alarm system can be optional to equip with infrared and
microwave motion detector. When detected OOW activities, dormant time will be
automatically reset.
To ensure the safety of the system settings (protection set to the dormant time and
duty mode), usually the captain keeps the key and he is the only person who lets the
10
6.6 Bridge navigational Watch Alarm system/Nautical Equipment Fault Alarm Operation
main interface
Press
Navigational Watch
Alarm
state displays
interface.
When the system screen appears in the main interface of nautical equipment alarm failure, the
system will automatically be changed over to nautical equipment alarm system interface. When
the bridge navigational watch alarm dormant time is over by then, the system will automatically
11
Brigational Watch Alarm System Operational Interface
System self-test:Pressing “test” key, system sound and light alarm will give
Sound mute and not flashing: When the new nautical equipment appears fault,
the green lamp is changed to red lamp and flashing meanwhile the sound
alarm giving out. Pressing ACK key to mute the sound and red lamp stops
flashing.
12
6.6.2 Emergency Call
call function.
Only inputting the correct password and confirmed, the dormant Time and watch mode
After dormant time and watch mode settings finished, pressing the "Save" key, and then
13
7、System Maintenance
Test
Press “Reset/Test” key for 2 seconds at the same time, all digital tube will be lighting and
flashes, all connected horns will be alarming; all connected indicated light will be flashing.
Troubleshooting
Check whether the system activation on duty-----the system in active the countdown
will work ,just as the key of system is “on” and the model set on hand, then the
system work
Reset unit----each reset unit of signal shall short circle. The system can be take six
manually reset unit input, check the six terminals of I/O control on ST2, make sure the
the line number 1# an line number 4#(on terminals is I and p+) is short circle
Motion reset unit----same as reset unit, check the motion reset unit line number 1#
and line number 4#(on terminals is i9 and p+)is short circle, close loop.
General problem of the extension/reset unit is alarm indicator light not work and buzzer
not sound, this is usually due to a faulty wiring,check the line number is carefully.
The alarm indicator light not work testing both ends 24v voltage input, 24V whether at
Emergency call
Only the system on duty activation can be emergency call, emergency call is all
System alarm
Usually means the operation panel and host communication failures, sometimes
is operation panel internal line fault. Self-test will be alarm ouput and panel shows”
E1”.check carefully the line between operation panel and host connecting.
When the system self-check test, normal operation panel display system version and
14
software version, such as respectively show "the A8" "C3", self-test process take turns
show. When there is "1", "2", "3", "4 ", "5", "6 ", code, means the system access
corresponding reset eunit 1 road, the 2 road is breaks down, then to check the
corresponding reset unit connection, view each reset unit line 1 # and 4 # whether short
carcle . Operation panel display "E1" means system failure, this code can viewon
operation manual
If there is fault of motion fault ,the motion doesn’t work, In addition to check the wiring
outside, please report to the manufacturer repair or replacement spare, motion detection
factory has tested before send out,you do not need to repair it..
If the system appears the other problems that cannot be solved, please contact us.
021-58380732-8030
Email: shhtop@126.com
15
8. Guidelines for BNWAS Installation
(1) Reset devices:
(i) At least one reset device should be provided near each conning position in the
wheelhouse. More reset devices may be provided to the workstations for navigation,
manoeuvering and monitoring in order for safe and effective operation, if desired.
A reset function may be initiated by motion sensors and navigational equipment such as
Where it is easy to reset a first stage alarm by a reset device located nearby in the
(i) A visualindicator and first stage audible alarm are to be provided in the wheelhouse.
When they are combined with a reset device, individual visual indicators and first stage
(ii) A visualindicator and first stage audible alarm are to be provided in the bridge wings.
Where a reset device is not provided in the case of l(ii) above, the following functions are
required:
(3) Second stage audible alarms and Third stage audible alarms
(i) Second stage audible alarms should be located in the Captain's bedroom and Deck
officer cabins.
In case where there are three deck officers on board ,one deck officer for duty may be
selected from the main panel and the alarm in the Captain's bedroom may be changed to a
(ii) Third stage alarms should be located in the officer's Mess room,Saloon,Recreation
(4) BNWAS should be supplied by both an AC source (Main and Emergency source) and a
16
(5) BNWAS for ships constructed on or after 1July 2011 are to connected with the following
(6) With respect to small ships, BNWAS installations may be designed according to relaxed
requirements in cases where such requirements are specified by the Flag State.
9、Accessory
17
Number Type Dwg. №. Page Page №.
1 Contents HTC-BNW-OUT 1 1
2 BNW Syatem Drawing HTC-BNW-SYS 1 1
3 110-113 Conecting Drawing HTC-BNW-EXL 1 2
4 Function Schematic Diagram HTC-BNW-EXL 3 3-5
5 The General Device Drawing of BNW HTC-BNW-OUT 1 6
6 Sub Device Installing Dimension and Internal Detailed Drawing HTC-BNW-OUT 7-20
14
7 Electrical Schematic Diagram HTC-BNW-EXL 7 21-27
Title:
The Contents for BNW
Customer Drawing
.
HTC-BNW-SYS Title:
The Layout of BNWS
Title:
110-113 Wire Connection
张伟
To connect BNW110
main controller
unit
reserved
Auto steer
main power system failure
supply inputinput
output
reserved input (dry contact)
power supply failure
Backup power alarm output (Dry
supply input contact)
the third
stage
extending
alarm(dry 3 channels motion
contact) detection
to connect
BNW110
main
controller
unit
reserved
auto steer
input
Type: HTC-BNW-111 Type: HTC-BNW-111 Type: HTC-BNW-111 Type: HTC-BNW-111 Type: HTC-BNW-112 Type: HTC-BNW-114-B1
Product No.: HTC-BNW-111-B1 Product No.: HTC-BNW-111-B1-F Product No.: HTC-BNW-111-A1-F Product No.: HTC-BNW-111-B2 Product No.: HTC-BNW-112-B1 Product No.: HTC-BNW-114-B1
Title:
The General Drawing of
BNW Parts 张伟
Outline Dmensions(W×H×D) 400× 360× 185
Installation Dmensions with Accessory 4-Φ6.5:380×320
Installation Dmensions Without Accessory 4-Φ6.5:380×280
Case Material ABS(RAL7035)
Shielding Shell Material
Weight 10Kg
Protection Grade IP22
Power Supply
Current Consumption appr. 1500mA
Compass Safety Distance >50cm
TYPE Title:
Main control+ unit
TYPE:HTC-BNW-113-B1 张伟 潘明艳 尹顺利 董良斌
2011-8-22 2012-4-10 2012-4-10 2012-4-10 7/32
Dmensions(W×H×D) 100× 210× 55
Installation Dmensions(Fixed Holes) 4-Φ4.2:68×190
+1 +1
Panel Cut-Out 80 × 160
Case Material ABS(RAL7035)
Weight 0.35Kg
Protection Grade IP22
(hole dimension)
1 2 3 4
TYPE Title:
Rest Unit
TYPE:HTC-BNW-111-A1 张伟 潘明艳 尹顺利 董良斌
2011-8-22 2012-4-10 2012-4-10 2012-4-10
Dmensions(W×H×D) 80× 160× 55
Installation Dmensions(Fixed Holes) 4-Φ4.2:68×148
Case Material ABS(RAL7035)
Weight 0.35Kg
Protection Grade IP22
1 2 3 4
TYPE Title:
Reset Unit
TYPE:HTC-BNW-111-B1 张伟 潘明艳 尹顺利 董良斌
2011-8-22 2012-4-10 2012-4-10 2012-4-10
Outline Dmensions(W×H×D) 80× 184× 87
Installation Dmensions(Fixed Holes) 4-Φ4.2:68×172
Case Material ABS(RAL7035)
Weight 0.35Kg
Protection Grade IP56
1 2 3 4
Title:
Reset Unit
TYPE:HTC-BNW-111-B2 张伟 潘明艳 尹顺利 董良斌
2011-8-22 2012-4-10 2012-4-10 2012-4-10
(Φ4.2Hole Dimension)
Outline Dmensions(W×H×D) 82.5× 103.5× 76
Installation Dmensions(Fixed Holes) 4-Φ4.2:70×50
Case Material ABS(RAL7035)
Weight 0.2Kg
Protection Grade IP22
(Φ4.2hole dimension)
U:600V Ith 10A NC
NC
1 2
TYPE Title:
Reset Unit
张伟 潘明艳 尹顺利 董良斌
TYPE:BNW-111-B1-A 2011-8-18 2012-4-10 2012-4-10 2012-4-10
(Φ4.2 hole dimension) Outline Dmensions(W×H×D) 82.5× 103.5× 68.5
Installation Dmensions(Fixed Holes) 4-Φ4.2:70×50
Case Material ABS(RAL7035)
Weight 0.2Kg
Protection Grade IP22
1 2
TYPE Title:
Reset rewinding Buzzer
TYPE:HTC-BNW-111-B1-F 张伟 潘明艳 尹顺利 董良斌
2011-8-22 2012-4-10 2012-4-10 2012-4-10
Outline Dmensions(W×H×D) 40× 40× 53
Installation Dmensions(Fixed Holes) Φ22.5
Weight 0.05Kg
Protection Grade IP22
1 2
NC
TYPE Title:
Reset Button
TYPE:HTC-BNW-111-A1-F 张伟 潘明艳 尹顺利 董良斌
2011-8-22 2012-4-10 2012-4-10 2012-4-10
Outline Dimensions(W×H×D) 24× 24× 50
Installation Dimensions(Fixed Holes) Φ22.5
Weight 0.05Kg
Protection Grade IP22
1 2
TYPE Title:
Buzzer
TYPE:HTC-BNW-111-A1-F 张伟 潘明艳 尹顺利 董良斌
2011-8-22 2012-4-10 2012-4-10 2012-4-10
Outline Dimensions(W×H×D) 100× 195× 75
Installation Dimensions(Fixed Holes) 4-Φ4.2:68×155
+0.5 +0.5
installing dimension 81 × 141
Case Material ABS(RAL7035)
Weight 0.35Kg
Protection Grade IP22
Tone tuning
ST1 SW1
1 LAP
2
3
4
TYPE Title:
Extending Alarm Unit
张伟 潘明艳 尹顺利 董良斌
TYPE:HTC-BNW-112-A1 2011-8-22 2012-4-10 2012-4-10 2012-4-10
Outline Dimensions(W×H×D) 81× 149× 75
Installation Dimensions (Fixed Holes) 4-Φ4.2:60×134
Case Material ABS(RAL7035)
Weight 0.35Kg
Protection Grade IP22
Tone tuning
ST1
1
SW1
LAP
2
3
4
TYPE Title:
Extending Alarm Unit
TYPE:HTC-BNW-112-B1 张伟 潘明艳 尹顺利 董良斌
2011-8-22 2012-4-10 2012-4-10 2012-4-10
Outline Dmensions(W×H×D) 81× 195× 75
Flush mounted Installation Dimensions(Fixed Holes) 4-Φ6:152×76
+1 +1
Flush mounted Installation Dimensions(Cut out) 136 × 136
Wall mounted Installation Dimensions(Fixed Holes) 2-Φ6:L=87
Case Masterial ABS(RAL7035)
(Φ6 Flush mounted hole) Weight 1Kg
Protection Grade IP22
Note:Any installation can be selected from Flush mounted mode and Wall mou
(Φ6
pattern
15m
2.7m 9.6m
Wiring terminals
3.3m 13.5m
TYPE Title:
Motion detection Unit
张伟 潘明艳 尹顺利 董良斌
TYPE:HHTC-BNW-114-A1 2011-8-22 2012-4-10 2012-4-10 2012-4-10
Outline Dimensions(W×H×D) 125× 75× 44
Installation Dimensions(Fixed Holes) 2-Φ5:L=45
Case Material ABS(RAL7035)
Weight 0.2Kg
Protection Grade IP22
12
1 2 3 4
Wiring terminals
TYPE Title:
Motion Detecting Unit
张伟 潘明艳 尹顺利 董良斌
TYPE:HTC-BNW-114-B1 2011-8-22 2012-4-10 2012-4-10 2012-4-10
Outline Dimensions(W×H×D) 160× 260× 94 Input Power Supply AC220V DC24V
Installation Dimensions(Fixed Holes) 4-Φ8.5:140×210 output power capacity appr. 100VA
Case Material AL(RAL7035) Compass Safe Distance >50cm
Weight 5.5Kg
Protection Grade IP22
TYPE Titles:
Power Supply Unit
TYPE:HTC-BNW-115 张伟 潘明艳 尹顺利 董良斌
2011-8-22 2012-4-10 2012-4-10 2012-4-10
Cable Length 0.5m Terminals Definition Shown in figure
Cable Type 7× 0.5mm (7 cores shielding cable)
TYPE Title:
Connecting Cable WS02-2
张伟 潘明艳 尹顺利 董良斌
2011-8-22 2012-4-10 2012-4-10 2012-4-10
control box
navigation
failure alarm
备用 备用
comprehensive
alarm board
Title:
wiring diagram for
navigation failure alarm
control box
port starboard BCC left BCC right Chart radio spare spare
area space
Title:
wiring diagram of manual
reset unit
control box
Revision
Sheet of
:
comprehensive
alarm board
Title:
wiring diagram for main
and backup power supply
Mode 2
X-Brand S-Brand
Radar Radar
Bridge
Console
Nav Lookout
Console Console
IP56 IP56
Radio space
Chart Space
HTC-BNW-OUT
Title:
The General Layout of
BNWAS( V2)
Mode 3
Bridge
Console
Nav lookout
Console Console
IP56 IP56
Chart Space
HTC-BNW-OUT
Title:
The General Layout of
BNWAS
Mode 4
X-Brand S-Brand
Radar Radar
Bridge
Nav. Console
Lookout
Console Console
IP56 IP56
Radio Table
Chart Table
HTC-BNW-OUT
Title:
The General Layout of
BNWAS ( V2)
HTC-BNW-SERIES BNWAS VDR Signal Communication Agreement
Data Format
Data Content Description Condition Describe
$ Start Code
B
N
W
, Delimiter
1 Key Switch 0:Off、1:ON
, Delimiter
0 Setting Time Alarm Setting Time(min)
8 (08=8 minutes)
, Delimiter
1 Operation Mode 0: Manual Off、1: Manual On、2: Auto.
, Delimiter
Selection Of Extension 0:Captain、1:Chief officer、2:2nd. officer、3:3rd.
3
Alarm officer
, Delimiter
1 Actived State 0 :stop、1: Active
, Delimiter
1 Reset Actions 0:No Input、1:Input
, Delimiter
1 Emergency Call 0:No Input、1:Input
, Delimiter
1 System Fault 0: Normal、1: Alarm Output
, Delimiter
0: No Alarm、1: Visual warning、2: First Stage
Working Mode Of
0 Alarm、3: Second Stage Alarm、4: Third Stage
Extension Alarm
Alarm
, Delimiter
Main Power Supply
2 0: Normal、1: Alarm Output
Failure
, Delimiter
Emergency Power
0 0: Normal、1: Alarm Output
Failure
, Separator
* End code
H
H
0x0D<CR> enter
0x0A<LF>
Data Exa. $BNW,1,08,1,3,0,0,0,0,0,0,1, * 51
Display Panel
1st.Stage Alarm
+ Manual on
Mode
Auto
2nd.Stage Alarm
3nd.Stage Alarm
Min.
- 1
3
2
4
Buck-up
Parameter setting area
Watch Active
Dimmer Key
Functional Operation Buttons
The main power supply is not input, the main power failure light is The emergency power supply is not input, the emergency power failure
flashing and the buzzer sound; light is flashing and the buzzer sound;
Reset Reset
Test Test
Press to halt noise & light alarm
Press to halt noise & light alarm
Watch Active
Watch Active
Main Pwr Fault
Main Pwr Fault
Emerg Pwr Fault
Emerg Pwr Fault
System Fault
System Fault
Press this button to stop the noise alarm and indicator LED light off, Press this button to stop the noise alarm and indicator LED light off, the
buzzer silencer. emergency power alarm indicat LED flicker disappear, buzzer silencer.
Backup duty select operation
Press Back-up button to select the Backup duty, reserve select 1 to 4 corresponds to an extension of 1 to 4 alarm output
port; (in any state can select to Backup duty)
Buck-up Buck-up
1 2 Buck-up 1 2 Buck-up
3 4 3 4
Buck-up Buck-up
Auto Auto
1 2 Buck-up 1 2 Buck-up
3 4 3 4
Watch Mode
Watch Active Manual off
Mode
Buck-up Main Pwr Fault Manual on
Auto ON
Emerg Pwr Fault
1 2 Buck-up
System Fault OFF
3 4
Manual off
3:2nd officer 4:3rd officer Key switch
Mode
Manual on
Auto
Key switch in the ON, the watch alarm system to work according to
1 2 Buck-up
shift patterns Status: In manual mode off duty, the duty alarm
3 4 system does not work;
Buck-up
Watch Mode
Watch Active Manual off
Mode
Manual on
Main Pwr Fault
Auto ON
Emerg Pwr Fault
1 2 Buck-up
Watch Mode System Fault OFF
3 4
Manual off
Mode
Manual on 1:Captain 2:Chief officer
Auto 3:2nd officer 4:3rd officer Key switch
1 2 Buck-up
3 4
+
PRE-alarm Watch Active
Alarm system is activated duty work, the emergency call function to start.
EMERG
CALL
Press more than 2 seconds
1st.Stage Alarm
Watch Active
Reset
PRE-alarm
1st.Stage Alarm
Watch Active
State in an emergency call, press the reset button or other input reset signal
back to the normal state;
Reset unit detects Main power alarm
Note: This feature is only comes BNW111 detection system reset unit or part of the
mobile detection unit for access to the situation, the other unit does not detect external
reset input, and do not take on this port; if BNW111 unit does not need access, we
should enter the port Line 1 # and 4 # line shorted;
When the
external reset Dormant Time
unit open or Watch Active
+
Watch Active
missed, the Main Pwr Fault
system fault Main Pwr Fault
LED flashes Emerg Pwr Fault
and the Emerg Pwr Fault
location of
digital System Fault
Min.
- System Fault
window
displays the
port number
and flashing
failure; when The main power supply is not input, the main power
there are failure light is flashing and the buzzer sound;
multiple faults
exist, the
alternate port
Reset Reset
Test Test
Press to halt noise & light alarm Press to halt noise & light alarm
After the
muffler system
failure Dormant Time Watch Active
indicator light
+
Watch Active
given plain, Main Pwr Fault
digital display
Main Pwr Fault
interface Emerg Pwr Fault
window back Emerg Pwr Fault
to sleep time;
muffler fixed System Fault
Min.
- System Fault
After self-test
again or a new Watch Active
fault occurs, the Dormant Time
system fault Main Pwr Fault
LED flashes and
digital window
Watch Active
Reset
Test
Troubleshooting Press to halt noise & light alarm
Dormant Time
Watch Active
+
Watch Active
Main Pwr Fault
Main Pwr Fault
Troubleshootin Emerg Pwr Fault
g off Emerg Pwr Fault
automatically
after system System Fault
Min. - System Fault
fault LED
digital display
interface
window back Press this button to stop the noise alarm and
to sleep time. indicator LED light off, buzzer silencer.
Communication and alarm system description
Dormant Time
Watch Active
System Fault
Min.
-
Reset
Press Test to halt noise & light alarm
Dormant Time
Watch Active
System Fault
Min.
- After the muffler system
failure indicator light given
plain, digital window
display failure to retain No.:
E1 and plain
communication failure does
not rule out, has been
shown in this interface;
Watch Active
System Fault
Min. - 或
System Fault
Min. -
Internal communication system failure, system After the muffler system failure indicator
failure indicator light flashes, while the digital light given plain, digital window display
window display fault No.: E1 and flashes; failure to retain No.: E1 and plain;
Troubleshooting communication failure does not rule out, has
been shown in this interface;
Dormant Time
+
Watch Active
System Fault
Min.
-
+ Manual off
Manual on
Mode
Auto
Min. - 1
3
2
4
Buck-up
Reset
ON
EMERG Reset
CALL Test
OFF
The key switch from OFF to ON
after the rotation, 30s can be
within + or - keys to adjust duty
sleep time. (Sleep time in between
3 to 12 minutes) Turn this switch from OFF to ON The key switch from OFF to ON
after the rotation, 30s carried out
ON within the duty to press the mode
button mode selection operation.
OFF
Dormant Time
Dormant Time Watch Mode
+ +
Manual off
Manual on
Mode Mode
Auto
Min. - Min.
- 1 2 Buck-up Manual off
3 4 Manual on
Auto
1:Captain 2:Chief officer
3:2nd officer 4:3rd officer
+ Mode
Reset
ON
Dormant Time EMERG Reset
CALL Test Manual off
+ OFF Manual on
Auto
Min.
-
Mode
Dormant Time
+ Manual off
Manual on
Mode
Auto
Min.
- 1
3
2
4
Buck-up
Reset
ON
EMERG Reset
CALL Test
OFF
Status of extension alarm Emergency call operation
Tips: In the active work, the emergency call feature can be activated.
EMERG
Press CALL more than 2 seconds
Alarm Ext. Dormant Time
Pre-alarm
1st.Stage Alarm
+
2nd.Stage Alarm
3nd.Stage Alarm
Min. - Alarm Ext. Dormant Time
Pre-alarm
1st.Stage Alarm
Watch Active
Pre-alarm
1st.Stage Alarm
+
2nd.Stage Alarm Press to reset
3nd.Stage Alarm
Min. - Reset
Delay 90s
+
Pre-alarm Watch Active
1st.Stage Alarm
State in an emergency call, press the reset button or other input reset
signal back to the normal state;
2nd.Stage Alarm
3nd.Stage Alarm
Min. -
3rd. stage alarm status
Pre-alarm
1st.Stage Alarm
+
2nd.Stage Alarm
3nd.Stage Alarm
Min. -
A reset signal input back to normal working condition.
System self-test operation
Reset
System power on press Test more than 2 seconds to stert self-test
Pre-alarm
1st.Stage Alarm
+ Manual off
Manual on
Mode Watch Active
3nd.Stage Alarm
Min. - 1
3
2
4
Buck-up
System Fault
Delay 1.5s
+
Pre-alarm Manual off Watch Active
Mode
Manual on
1st.Stage Alarm Main Pwr Fault
Auto
3nd.Stage Alarm
Min. - 1
3
2
4
Buck-up
System Fault
Delay 1.5s
+
Watch Active
Mode
Manual on
1st.Stage Alarm Auto Main Pwr Fault
3nd.Stage Alarm
Min.
- 1
3
2
4
Buck-up
System Fault
Delay 1.5s
+
Pre-alarm Manual off Watch Active
Mode
Manual on
1st.Stage Alarm Main Pwr Fault
Auto
3nd.Stage Alarm
Min.
- 1
3
2
4
Buck-up
System Fault
Digital window displays the main control unit BNW110 program version number: (A2)