THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO.

NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS


OTHERWISE NOTED.

2. FOR GENERAL NOTES CONCRETE WORKS REFER DWG-


PA-Q30132.001 AND 002.

3. ALL EXPOSED (REACHABLE) CONCRETE SURFACES IN


DIRECT CONTACT WITH GROUND BELOW NATURAL
GRADE LEVEL (NGL) SHALL BE COATED WITH 2

STEEL POLE STEEL POLE COATS OF COAL TAR EPOXY PAINT AS PER APCS-3

OVERHEAD POWERLINE OVERHEAD POWERLINE OF SAES-H-003 PRIOR TO BACKFILLING.

4. ALL CONCRETE SURFACES ABOVE NATURAL GRADE


LEVEL (NGL) SHALL BE PAINTED AS PER APCS-1B
OF SAES-H-003.
NUT NUT
5. ALL EXPOSED CORNERS OF CONCRETE SHALL BE
PROVIDED WITH 25X25MM CHAMFER

6. BACKFILL MATERIAL AROUND & UNDER CONCRETE

300
300
FOUNDATION SHALL BE SELECT FILL. EXCAVATION
100

100
AND COMPACTION SHALL BE IN ACCORDANCE WITH
TOC TOC
SAES-A-114.
200 100

200 100
7. ALL DIMENSIONS SHALL BE FIELD CHECKED AND
VERIFIED PRIOR TO CONSTRUCTION OR FABRICATION.
SEE NOTE-4
8. THIS DRAWING IS PREPARED FOR OVER HEAD POWER
FGL FGL LINE POLE AS PER SAUDI ARAMCO STD. DRAWING NO.
AA-036142-015 REV. 00.

200
9. GALVANIZED STEEL POLE SHALL BE COATED WITH

600
NGL
ANTI-CORROSSION COATING OF COAL TAR EPOXY
AS PER 14-SAMSS-603. COATING SHALL BE APPLIED
FOR THE EMBEDED DEPTH PLUS 300MM ABOVE THE
NGL TOP OF CONCRETE.

10.GROUNDING LUGS WHERE COVERRED FROM CONCRETE


MK-1001 TIES @ 250 C/C

MK-1001 TIES @ 250 C/C


FOUNDATION SHOULD BE WIRED AND GROUNDED FIRST
20-MK-1601 VERTICAL BARS 20-MK-1601 VERTICAL BARS
BEFORE POURED WITH CONCRETE.
2100

2100
11. MARL PAD FOR SABKHA/POOR SOIL SHALL BE
ANTI CORROSION COATING ANTI CORROSION COATING
CONSTRUCTION BEFORE INSTALLATION OF POLE
FOUNDATION. COMPACTION OF THE MARL PAD SHALL
B

B
75 MIN. SIDE 75 MIN. SIDE
BE AS PER SAES-A-114
CLEAR COVER CLEAR COVER
DRILLED HOLE FILLED WITH
(TYP) (TYP) DRILLED HOLE FILLED WITH 12.NUT SHALL BE COVERED DURING COATING WORK.
CONCRETE
A

A
CONCRETE
13.OVER EXCAVATION SHALL BE BACKFILLED WITH
SELECT FILL AND COMPACTED AS PER SAES-A-114.

14.FOR GUY AND ANCHOR DETAILS REFER


A A
A A SA STANDARD DWG. AA-036142 SHT. 014.

CJ CJ 15.FOR LOCATION REFER ELECTRICAL CABLE ROUTING


SEE NOTE-3
DWG. PA-P00002.001 & PA-P30060.001.

BOTTOM POLE SPLIT BARREL OR


16.FOR GENERAL NOTES REFER TO PA-Q30132 FOR
BASE PLATE STRAIGHT SIDED
CONCRETE, PA-M30133 FOR STEEL WORKS.
STEEL DRUM, TAMPED
DOWN AS HOLE. IS DUG 17. FOUNDATION SIZE & TYPE SHALL FINALIZED DURING
C

C
(SEE DETAIL-1) DETAIL DESIGN WITH APPROVED GEOTECHNICAL REPORT.
CAST-IN-PLACE
CONCRETE
CAST-IN-PLACE
WELD
CONCRETE
BOTTOM COVER

BOTTOM COVER
100 MIN.

100 MIN.
D D

STEEL POLE FOUNDATION 1 D E T A I L


STEEL POLE FOUNDATION -

IN NORMAL SAND SOIL SABKHA/POOR SOIL (NOT APPLICABLE)


SH

LEGEND

FGL - FINISHED GRADE LEVEL


(2A+D)
NGL - NATURAL GRADE LEVEL

TOC - TOP OF CONCRETE

CJ - CONSTRUCTION JOINT

FGL - FINISHED GROUND LEVEL


MK-1601
75mm CLEAR VERTICAL BARS
FDN - FOUNDATION
(TYPICAL)

- MARL PAD
MK-1001 TIES D

POLE
FOUNDATION HDG. STEEL POLE - ANTI CORROSION COATING
(2A+D)

REFERENCE DRAWINGS

150
DRAWING CONTROL FOR BI 10-10214-0001 PD-A00001
BLACK STRIPE
PROJECT PROPOSAL NARRATIVE PE-A00002

150
YELLOW STRIPE
D

150
BLACK STRIPE
A S E C T I O N
-
SCALE 1 :20M 0 0.5 1.0 1.5 2.0
SH

150
YELLOW STRIPE

1200
METERS

SCALE: 1 : 20M

300
REVISION VALIDATION

THIS REVISION NO. C IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


MARL PAD PLAN REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

10-10214-0001-001

100
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

200
GMD MAP

POLE FOUNDATION SUMMARY 05/08/22 05/08/22

REV.NO. DATE REVISION DESCRIPTION

FGL C 05/08/22 ISSUED FOR 100% PP REVIEW


NORMAL SOIL SABKHA/POOR SOIL
LENGTH OF POLE JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
METER (FEET) 10-10214-0001 CONSTRUCTION UNTIL CERTIFIED AND DATED
DEPTH (A) DEPTH (B) DEPTH (C) DIA (D) CONC. QTY. DEPTH (A) DEPTH (B) DEPTH (C) DIA (D) CONC. QTY.
3 3

(mm) (mm) (mm) (mm) (m ) (mm) (mm) (mm) (mm) (m )


SAUDI ARABIAN OIL COMPANY
DRAWING TYPE
18.2 (60) 3000 3400 900 1100 3.21 - - - - -
FOUNDATION DETAIL FDN
WARNING SIGN 34.5 kV OHTL FROM AINDAR GOSP-3
GOSP-3 PUMPSTATION & TIE-LINE

AIN DAR SAUDI ARABIA


PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

274 Q PA-Q30129 001 C


Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01