Fault Current Calculation (BASE MVA Method)

Calculating Fault Current From Power Generation From Power Distribution T/C

Fault Level at Incoming Site 360 MVA


Base MVA (For H.T beaker and Transformer Primary side) 4 MVA
Base KV (For H.T beaker and Transformer Primary side) 33 KV
Base KV (For Transformer Secondary,LT Panel,D.B) 0.415 KV

Fault Level at HT Sub Station Side

P.U Reactance at Incoming of H.T Breaker [Z p.u(A) ] 0.011 Ω


Fault Level at Transformer Side
Transformer Rating 4 MVA
Transformer Impedance 6.25 %
Length of Cable from H.T Breaker To Transformer 50 Meter Outdoor 33KV Cable 3cx400Sq.mm
R (T/C) 0.014 PU
X (T/C) 0.014 PU
Z(T/C) 0.020 PU
Z p.u (C) 0.000 Ω
Total Z p.u (D) (Up to Transformer Primary) 0.031 Ω
Fault Level at Transformer Primary Side 129.41 MVA
% Reactance at Base KVA 6.250 %
Z P.U (T/C) 0.063 Ω
Total P.U Impedance up to T/C Secondary 0.093 Ω Total%Z=9.3
Fault Level at Transformer Secondary Side 42.82 MVA
Fault Current at Transformer Secondary 59.58 Kamp