Fault Current Calculation (BASE MVA Method)

Calculating Fault Current From Power Generation From Power Distribution T/C

Fault Level at Incoming Site 360 MVA


Base MVA (For H.T beaker and Transformer Primary side) 4 MVA
Base KV (For H.T beaker and Transformer Primary side) 33 KV
Base KV (For Transformer Secondary,LT Panel,D.B) 0.415 KV

0.000 Ω
Fault Level at Transformer Side
Transformer Rating 4 MVA
Transformer Impedance 6.25 %
Length of Cable from H.T Breaker To Transformer 100 Meter Outdoor 33KV Cable 3cx400Sq.mm
R (T/C) 0.014 PU
X (T/C) 0.014 PU
Z(T/C) 0.020 PU
Z p.u (C) 0.000 Ω
Total Z p.u (D) (Up to Transformer Primary) 0.020 Ω
Fault Level at Transformer Primary Side 202.03 MVA
% Reactance at Base KVA 6.250 %
Z P.U (T/C) 0.063 Ω
Total P.U Impedance up to T/C Secondary 0.082 Ω Total%Z=9.3
Fault Level at Transformer Secondary Side 64.00 MVA
Fault Current at Transformer Secondary 89.04 Kamp