Fire protection system

 THE FIRE PROTECTION SYSTEMS SHALL COMPLY WITH THE LATEST EDITIONS OF NFPA LOCAL
CODES.
 SPRINKLER CONTROL VALVE AND WATER FLOW SWITCH SHALL BE INTERFACED WITH FIRE
ALARM SYSTEM.
 ALL VALVES AND FIRE DEPARTMENT CONNECTIONS SHALL BE UL/FM APPROVED AND
COMPLY LOCAL AUTHORITY, SBC, NFPA GUIDELINES.

Sprinklers

 RECESSED PENDENT SPRINKLER HEADS SHALL BE 15 mm ORIFICE, 15 mm NPT WITH K


FACTOR NOT LESS THAN 5.6, QUICK RESPONSE, CHROME FINISH, COMPLETE WITH TWO
PIECES CHROME PLATED ESCUTCHEON PLATE.
 UPRIGHT SPRINKLER HEADS SHALL BE 15 mm ORIFICE, 15 mm NPT WITH K FACTOR NOT LESS
THAN 5.6, QUICK RESPONSE, BRASS FINISH.
 ALL OBSTRUCTIONS TO SPRINKLER DISCHARGE AS PER NFPA-13 SHALL BE PREVENTED.

Piping Network

 ALL FIRE PROTECTION PIPING INSIDE THE BUILDING SHALL BE BLACK SEAMLESS STEEL SCH. 40.
 THE SPRINKLER SYSTEM PIPING SHALL BE SLOPED TOWARDS THE DRAIN POINT.
 AUTOMATIC AIR VENT SHALL BE INSTALLED AT THE TOP OF EACH FIRE WATER SUPPLY RISER.
 ALL OPENINGS IN FIRE RATED WALLS SHALL BE SEALED WITH FIRE AND SMOKE RESISTANT
CAULKING.
 FIRE DRAIN RISER SHALL BE CONNECTED TO THE NEAREST DRAIN POINTS.
 ANY PIPE PENETRATES EXPANSION JOINT SHALL BE PROVIDED WITH FELEXIBLE CONNECTOR.