Professional Documents
Culture Documents
UMCEE Presentation 06102015
UMCEE Presentation 06102015
Incentives
System resilience
Copyright 2015 Michael E. Ropp. All rights reserved.
Modern drivers for energy decisions
Sustainability
Diesel
PV
PV
Source: Presentation
Copyrightby Shalom
2015 MichaelGoffri
E. Ropp.to
AllAWEA WINDPOWER 2014
rights reserved.
PV system cost trend
Copyright 2015 Michael E. Ropp. All rights reserved.
Types of DG
Module 1
𝜕Φ
𝐸=−
𝜕𝑡
• All about conductors moving in magnetic fields
• Chief difference between them is in where the magnetic field comes
from
Examples:
• Type I WTs
• Some small hydro plants
Copyright 2015 Michael E. Ropp. All rights reserved.
Doubly-fed induction generator (Type III WT)
≠
Copyright 2015 Michael E. Ropp. All rights reserved.
Impacts of PV on distribution
feeders, Part 1: voltage impacts
Module 2
PV plants push current back upstream, through the feeder impedances. This
reduces the voltage drop, or if current direction reverses anywhere, leads to a
“negative voltage drop”.
Copyright 2015 Michael E. Ropp. All rights reserved.
Voltage rise
• Voltage rise strongly impacted by DG power factor
• Most DG are operated at unity PF, but a DG sourcing VArs can lead to much
larger voltage rise
• Setting a DG to absorb VArs can actually mitigate some problems—more on
this in a minute
• Voltage rise is very location-dependent
• Depends strongly on feeder impedances and load distribution along the
feeder
1.5 At substation
At PV
1.45
1.35
1.3
159 160 161 162 163 164 165 166 167 168
Time (sec)
P
Q
Copyright 2015 Michael E. Ropp. All rights reserved.
Fixed leading PF impact on voltage during
cloud passage
Temporary
overvoltage (TOV)
VBN
VAN
VCN
The VAN and VBN vectors are being held in place by the
generator, but VCN collapses and the result is a big
zero sequence component. This is GFOV.
Copyright 2015 Michael E. Ropp. All rights reserved.
Sequence
networks of a
distribution
feeder with PV,
pre-fault
“DR island systems are parts of electric power systems (EPSs) that
have DR and load, have the ability to disconnect from and parallel
with the EPS, include the local EPS and may include portions of the
area EPS, and are intentional and planned.”
• 5 MW of standby/backup engine-
gensets (diesel)
• Added a 5 MW, 1.25 MWh BIS at
the substation
• Desire to add PV later, perhaps as
much as 25% penetration
Use case #3
Use Case #3
• On- to off-grid transition at 3 s
• BIS hands V/f regulation to diesels at
6.6 s
• BIS transitions from discharging to
charging mode form 15 to 25 s
• Step doubling of microgrid load, at 25
s (using motor-containing dynamic
load model)
• Step halving of microgrid load, at 35 s
The microgrid voltage almost remains within bounds during the entire sequence. The one exception is during the
stepwise doubling of the load. Working with the utility client, it was determined that such a transition was probably
unlikely in the field, so it was decided that this was not a concern.
30% • PV variability impacts mainline gens, but problems can generally still be solved by
gen control adjustments OR LOAD CONTROLS
• Mass tripping events start to become a problem—need FRT in PV inverters (H and L!)
• Minimum diesel loading starts to become a constraint
10%
PV variability disappears into load variability
System impacts
Copyright 2015 Michael E. Ropp. All rights reserved.
Mitigating PV impacts on low-inertia systems
• Use the right inverters!
• Otherwise, should limit PV penetration—actual limit without mitigation is
system-specific, usually ≈ 30%
• Widen frequency trip setpoints in the PV inverters—usually ≈ ± 5% of
nominal frequency
• Carefully tune the generator controls
• The conventional “tune and watch” approach is insufficient
• Consider smaller, modular engine-gensets
• Use of grid support functions in inverters can help—more shortly
• For all of these—need quantitative guidance to set all parameters
Pnom
Frequency
flo1 fhi1 fhi2
The PV inverters curtail their output above a setpoint fhi1 and cut off
completely at fhi2 and at flo1.
Copyright 2015 Michael E. Ropp. All rights reserved.
Can you do PV only (w/o storage)?
• Some customers want to take advantage of incentives available for PV
and want to use that PV as some kind of backup, but they do not
want the expense of storage.
• To do this, one would have to do the following:
• You must have the right inverters—must be able to operate in isochronous
mode.
• You need very fast-acting BEMS/load control. You’d have to make sure that
your facility load is below the available irradiance at all times.
• You will not have power at night, of course.
• For most customers, this doesn’t pencil out.
Voltage (V)
0
-200
-400
-600
-800
6.98 6.99 7 7.01 7.02 7.03 7.04
Time
Copyright 2015 Michael E. Ropp. All rights reserved.
GFOV test feeder