You are on page 1of 69

Station Protection - Power Transformer Protection

ABB India
Utilities - Automation
Page 1
Station Protection - Power Transformer Protection

n Introduction:
•Transformer is a static device used to transform the
electrical energy from one alternating current circuit to
another without any change in frequency.
• Power Transformer is a vital link in a power
transmission system and distribution

• A Power Transformer is an important and expensive part of a


power network.

• The impact of a transformer fault is more serious than a


transmission line outage.

ABB India
Utilities - Automation
Page 2
Station Protection - Power Transformer Protection

Introduction

• High availability of the power Transformer is therefore very


important in order to prevent disturbances in the power networks
transfer of power.

• Following are important.


• High quality transformer.
• Operating the transformer within specified limits of
temperature and voltage.
• Proper checking and maintaining OLTC.
• Providing suitable protective relays and monitoring devices.

ABB India
Utilities - Automation
Page 3
Station Protection - Power Transformer Protection

Why we need to protect a Transformer?

1. To Protect the Transformer from severe damages.

2. Time required to rectify the Transformer in case


of damages is more and it is very difficult.

3. Operation of a power network,when the power


transformer is out of service is always difficult.

4. A Power Transformer fault therefore often is


a more severe disturbance for the network,than
an overhead line fault which usually can be
repaired rather quickly.
ABB India
Utilities - Automation
Page 4
Station Protection - Power Transformer Protection

TYPE OF FAULTS

1.Incipient faults

2.Internal faults

3.External fault

ABB India
Utilities - Automation
Page 5
Station Protection - Power Transformer Protection

What are the faults which can occur in a


transformer or conditions leading to faults?

1.Insulation Breakdown
2.Phase to phase and Phase to Ground Fault
3.Reduced Cooling
4.Over heating due to overexcitation

5.Oil contamination and leakage

6.Aging of Insulation

7.Turn to Turn Fault


8.OVERLOAD PROTECTION
ABB India
Utilities - Automation
Page 6
Station Protection - Power Transformer Protection

REASONS FOR FAULTS AND ITS EFFECTS.


Insulation Breakdown
Main causes of this are
• Aging of insulation due to over temperature during long time.
• Contaminated oil.
• Corona discharges in the insulation.
• Transient overvoltages due to thunderstorms or switching
in the network.
• Current forces on the windings due to external faults with
high current.
• Insulation Breakdown of the windings will cause short circuits
and /or earth faults.
• These faults causes severe severe damaging on the windings
and the transformer core.

ABB India
Utilities - Automation
Page 7
Station Protection - Power Transformer Protection

REASONS FOR FAULTS AND ITS EFFECTS.


Aging of Insulation

• Aging of insulation is a function of time and temperature.

• Part of the winding operated at highest temperature undergoes


greatest deterioration.

• Improved cooling of transformer helps avoid accelerated


aging of the insulation.

ABB India
Utilities - Automation
Page 8
Station Protection - Power Transformer Protection

Overheating
• The overexcited transformer flux is forced through metal tank
and other unlaminated parts of the transformer and result in
heating up.

• To get correct representation V/Hz relay should be connected


to PT measuring voltage of an untapped transformer winding.

Oil contamination and leakage

• Quality of oil should be checked to ensure dielectric strength


at site.

• Silica gel breather helps avoid moisture.

• Oil level monitored to avoid breakdown of insulation.

ABB India
Utilities - Automation
Page 9
Station Protection - Power Transformer Protection

Reduced Cooling
• Forced cooling systems should be supervised to get alarm.
• Oil temperature should be watched and appropriate action
taken if transformer gets overheated.

ABB India
Utilities - Automation
Page 10
Station Protection - Power Transformer Protection

Turn-to-turn Faults
• Turn to turn faults between a few turns is difficult to detect
by current measuring relays. Fault current is of the order of
rated current when 2 to 4% of the turns are short circuited.

• The current in the short circuited loop is high (50-100 times In)
and causes local damage and release of gas.

• Therefore rate of rise of pressure relay may detect this fault.

ABB India
Utilities - Automation
Page 11
Station Protection - Power Transformer Protection

Phase to phase faults


• Short circuits between the phases will give rise to substantial
fault current only limited by the source impedance and the leakage
impedance of the transformer

Phase to ground faults

• When the faults current flows through earth return path, the fault
is called ground fault.

ABB India
Utilities - Automation
Page 12
Station Protection - Power Transformer Protection

Neutral and the effects of Transformer faults


• star connected winding with neutral point earthed through an
impedance

•Primary current is approximately proportional to square


of the short circuited fraction of the winding.
ABB India
Utilities - Automation
Page 13
Station Protection - Power Transformer Protection

Neutral and the effects of Transformer faults


• star connected winding with neutral point solidly earthed

•The reactance decreases rapidly for fault close to neutral.

•Primary fault current for ground fault between 0-40% from


neutral is below 1.5In and therefore O/C relay will not be
able to detect this.

ABB India
Utilities - Automation
Page 14
Station Protection - Power Transformer Protection

Why the Relay Protection?

• To limit the damage to the faulted equipment

• To separate the faulted equiment from the remainder to


the system .So that the system can continue to function

• To minimise the possibility of fire

• To minimise hazard to personnel

ABB India
Utilities - Automation
Page 15
Station Protection - Power Transformer Protection

What are the Protections we need to give to a Transformer?

1.Differential Protection

2.Restricted earth fault Protection


3.Over Flux Protection
4.Over current Protection
5.Over Load Protection
6.Under Impedance Protection
7.Ground Fault Protection
8.Turn-Turn Fault
9.Monitors

ABB India
Utilities - Automation
Page 16
Station Protection - Power Transformer Protection

CHOICE OF PROTECTION

Choice of protection for any given Power Transformer


depends upon a number of factors

• Size

• Importance

•Whether it has ON-Load (or) OFF-Load tap changer

ABB India
Utilities - Automation
Page 17
Station Protection - Power Transformer Protection

DATAs required for selecting the Protection scheme


• Particulars of Transformer
• KVA
•Voltage ratio
•Connection of winding
•Percentage impedance
•Neutral point earthing & value of resistance
•Whether indoor (or) outdoor,dry (or) Oil filled
•With (or) Without conservator
• Length & Cross section of connecting leads between CTs and
relay panels
• Fault level at power transformer terminals
• Network diagram showing position of power transformer
ABB India
Utilities - Automation
Page 18
Station Protection - Power Transformer Protection

General practice of protection of transformer


• Small distribution transformer ( 11kV/415V)
• Only H.V fuses for PH.& E/F. fault protn

• For Important Transformer of about 500KVA


• Over current relays
• Instaneous Earth fault relays

• Transformer in important location rating 500KVA and above


• Restricted Earth Fault relays
• Over current relays
• Buchholz

ABB India
Utilities - Automation
Page 19
Station Protection - Power Transformer Protection

General practice of protection of transformer

• Transformer of about 5MVA and above

• Differential relays
• Restricted Earth Fault relays
• Over current relays
• Over fluxing relays
• Over load relays
• Buchholz

ABB India
Utilities - Automation
Page 20
Station Protection - Power Transformer Protection

DIFFERENTIAL PROTECTION

• Differential protection responds to the vector


difference between two similar quantities

• This protection is generally called as


“ UNIT PROTECTION”

• Most of the Differential relays are Current diffl.


relay

ABB India
Utilities - Automation
Page 21
Station Protection - Power Transformer Protection

DIFFERENTIAL PROTECTION

• BASIC requirement

Differential relay connection must be satisfy

1) the Diffl. Relay must not operate for load (or)


external fault

2) The relay must operate for severe enough


internal fault

ABB India
Utilities - Automation
Page 22
Station Protection - Power Transformer Protection

DIFFERENTIAL PROTECTION

Simplex example of such a arrangement is shown here

ABB India
Utilities - Automation
Page 23
Station Protection - Power Transformer Protection

DIFFERENTIAL PROTECTION

Simplex example of such a arrangement is shown here

Circulating current protection

ABB India
Utilities - Automation
Page 24
Station Protection - Power Transformer Protection

Problem arising in DIFFERENTIAL PROTECTION


applied to Transformer
Simple differential protection. Is inadequate because

• CT. Ratio error during shortcircuit


• Saturation of CT magnetic circuit during short
circuit condition
• Tap changinng
• Mangnetising inrush current

How to Overcome?

• Modification of circulating current differantial


relay is necessary to overcome the trouble arising
out of differences in CT ratios for hive value of
ABB India external short circuits
Utilities - Automation
Page 25
Station Protection - Power Transformer Protection

DIFFERENTIAL PROTECTION

Additional restraining (BIAS) coil in the pilot wire is introduced

A.T = I1 N/2 + I2 N/2 = N * ( ( I1 + I2 ) / 2


The relay is now called BIASED DIFFERENTIAL RELAY

ABB India
Utilities - Automation
Page 26
Station Protection - Power Transformer Protection

DIFFERENTIAL PROTECTION

This relay is also called as PERCENTAGE DIFFERENTIAL RELAY

Ratio of differential operating current to average restraining


current is in “Fixed percentage”

I.e ( I1 - I2 ) / ( ( I1 + I2 ) / 2 )= %

This relay has rising pick-up chac. As the magnitude od


through current increases the restraining current increases

ABB India
Utilities - Automation
Page 27
Station Protection - Power Transformer Protection

One more difficulty in DIFFERENTIAL PROTECTION is


magnetising inrush current which is not yet overcome
What is magnetising inrush current?
The shape , magnitude and duration of the inrush current
depend on the following factor

• Size of power transformer


• Source impedance
• Magnetic properties of the core material
• The remanence of the core
• The moment when the Tr. Is switced in.

Inrush current contain a large content of several


HARMONIC
ABB India
Utilities - Automation
Page 28
Station Protection - Power Transformer Protection

One more difficulty in DIFFERENTIAL PROTECTION is


magnetising inrush current which is not yet overcome

The relay filter the harmonic component from the inrush


current and feed it to restraining circuit

• DC or Off_set component
• 2nd Harmonic component
• 3rd Harmonic component
• 5th Harmonic component

Out of all second harmonic is predominant hence most of


the relay used this filter

Now the relays is called HARMONIC RESTRAINT DIFFL.RELAY


ABB India
Utilities - Automation
Page 29
Station Protection - Power Transformer Protection

Current Transformer connection for differential relay

Simple thumb rule

• CTs on “Star” winding of power transformer


should be connected in “Delta”

• CTs on “Delta” winding of power transformer


should be connected in “Star”

ABB India
Utilities - Automation
Page 30
Station Protection - Power Transformer Protection

Variouse vector group

Power transformer are grouped according to the


PHASE DISPLACEMENT

• Group-1 = Yy0 Phase displacement = 0 degree

• Group-2 = Yy6 Phase displacement = 180 degree

• Group-3 = Dy11 (or)Yd11 Phase displacement = -30degree

• Group-4 = Dy1 (or)Yd1 Phase displacement = +30degree

ABB India
Utilities - Automation
Page 31
Station Protection - Power Transformer Protection

How to make required interconnection between the


CTs and Differential relay

• Mark the polarity

• Mark the current flow

ABB India
Utilities - Automation
Page 32
Station Protection - Power Transformer Protection

How to make required interconnection between the


CTs and Differential relay

• Apply thump rule

• Make sure that


secondary current
will circulate
between the CTs
and relay

ABB India
Utilities - Automation
Page 33
Station Protection - Power Transformer Protection

CT. connection for Power transformer of


various vector group

ABB India
Utilities - Automation
Page 34
Station Protection - Power Transformer Protection

CT. connection for Power transformer of


various vector group

ABB India
Utilities - Automation
Page 35
Station Protection - Power Transformer Protection

DIFFERENTIAL PROTECTION
for 3 winding Transformer

Forgoing discussion for making the CT and Relay


interconnection applied to 2 winding transformer

• For 3 winding transformer .It is only necessary to


consider consider 2 winding at a time

I.e. HV & LV - Choose CT connection for HV and


determine CT connection for LV CT.
Then choose other winding w.r.t LV
ABB India
Utilities - Automation
Page 36
Station Protection - Power Transformer Protection

DIFFERENTIAL PROTECTION
for 3 winding Transformer

• 3 WDG. TR with one


power source

• 3 WDG. TR with three


power source

• 3 WDG. TR with
unloaded teritery

ABB India
Utilities - Automation
Page 37
Station Protection - Power Transformer Protection

DIFFERENTIAL PROTECTION
for 2 winding Transformer

ABB India
Utilities - Automation
Page 38
Station Protection - Power Transformer Protection

Interposing CT ( Auxiliary Transformer)

• To compensate for mismatch of line CT (ratio correction

• Phase shift correction

• ICT should be ideally match the relay current under load conditions
corresponding to the maximum MVA rating of Transformer

• Ratio of ICT should be calculated for balanced current when the


Tap-changer is in middle position

ABB India
Utilities - Automation
Page 39
Station Protection - Power Transformer Protection

Interposing CT Calculation
Data required:
Transformer details = KVHV /KVLV, MVA, Delta/Star

CT. details = CTRHV , CTRLV

• Main CT ratio should not be less than max full


load current in each winding

I FLHV = MVA/(1.732*KVHV ) amp; I FLLV = MVA/(1.732*KVLV ) amp;

• If the HV wdg. With -5%tap (center tap) then voltage


to be considered for calculation is( KVHV - 0.05)

I FLHV = MVA/(1.732*(KVHV - 0.05) amp

ABB India
Utilities - Automation
Page 40
Station Protection - Power Transformer Protection

Interposing CT Calculation

Secondary current from


HV line Ct is Isec HV = I FLHV /CTRHV amp;
LV line Ct is Isec LV = I FLLV /CTRLV amp;

• LV ICT should be connected in delta ,Whose secondary


current is divided by 1.732

• IF relay rated current is 1A.


The ratio required for the ICT is
HV side ICT ratio - ICT HV = IsecHV / 1 amp
LV side ICT ratio - ICT LV = IsecLV / 0.577 amp;

ABB India
Utilities - Automation
Page 41
Station Protection - Power Transformer Protection

Differential protn. Applied to a 2 wdg. Transformer


showing use of ICT

ABB India
Utilities - Automation
Page 42
Station Protection - Power Transformer Protection

Differential protn. Applied to a 3 wdg. Transformer


showing use of ICT

ABB India
Utilities - Automation
Page 43
Station Protection - Power Transformer Protection

AUTO TRANSFORMER

Auto transformer are some time used to couple EHV power netrwok
Differential relay as discussed can be applied
• If one neutral CT is used

ABB India
Utilities - Automation • Scheme response to E/F only
Page 44
Station Protection - Power Transformer Protection

AUTO TRANSFORMER
• If CTs are fitted in each phase at the neutral winding

Drawback
1) Does not respond for turn to turn fault
2) Does not response for any fault in teritery winding

• Scheme response to Ph/F & E/F


ABB India
Utilities - Automation
Page 45
Station Protection - Power Transformer Protection

E/F (or) Ground Fault protection


power transformer with impedance grounded (or) solid
grounded neutrals can be equipped with different type
GROUND FAULT RELAY to protect the grounded winding

• Residually connected E/F relay


• E/F relay connected in neutral to ground
• Combined E/F and Ph/F relay
• Restricted Earth Fault relay
# High impedance
# Low impedance
• Residual Volatge relay

ABB India
Utilities - Automation
Page 46
Station Protection - Power Transformer Protection

E/F (or) Ground Fault protection


• E/F relay connected in • E/F relay in neutral to earth
residual circuit circuit

UNRESTRICTED EARTH FAULT PROTECTION

• Ias+Ibs+Ics = 0 = Irs • In = Ia + Ib +Ic = 0

ABB India
Utilities - Automation
Page 47
Station Protection - Power Transformer Protection

REF. protection
• CTs in phase and neutral shall be
dedicated for the relay

• CT must have exactly the same


turns ratio

• NO turns correction are allowed

• Metrosil should be connected


across the relay

• Secondary circuit of the CTs have


to be grounded at only one point
• REF protection for STAR winding
ABB India
Utilities - Automation
Page 48
Station Protection - Power Transformer Protection

REF. protection
• When the fault occur very near the neutral point of the TR. ,the
voltage available for driving E/F current is small. Hence fault
current would be low

• If the relay is to sense such a faults , it has to be too sensitive


and would therefore operate for spurious signals,external faults
and switching surges

• The practice is to set the relay such that it operate for E/F
current of the order of 15% of rated winding current. Such a
setting protects restricted protection of winding.

Hence the name is called


Restricted Earth Fault protection
ABB India
Utilities - Automation
Page 49
Station Protection - Power Transformer Protection

REF. protection
• REF for Delta • REF for unearthed Star
connected winding connected winding

I.e. neutral is not earthed


ABB India
within the protected zone
Utilities - Automation
Page 50
Station Protection - Power Transformer Protection

REF. protection
Connection of REF for delta connected winding
& grounding Transformer

ABB India
Utilities - Automation
Page 51
Station Protection - Power Transformer Protection

Combined differential and REF. protection


with SCT

ABB India
Utilities - Automation
Page 52
Station Protection - Power Transformer Protection

Combined differential and REF. protection


with ICT

ABB India
Utilities - Automation
Page 53
Station Protection - Power Transformer Protection

Combined differential and REF. protection


with in zone Earthing Transformer

ABB India
Utilities - Automation
Page 54
Station Protection - Power Transformer Protection

Combined differential and REF. protection


with in zone Earthing Transformer

ABB India
Utilities - Automation
Page 55
Station Protection - Power Transformer Protection

Differential protection
with in zone Earthing Transformer & no E/F relay

ABB India
Utilities - Automation
Page 56
Station Protection - Power Transformer Protection

Earthing Transformer protection

ABB India
Utilities - Automation
Page 57
Station Protection - Power Transformer Protection

Over Current protection


Through faults are not detected by differential protection
of Transformer.If the through fault persists of longer
duration, the TR. Gets damaged by Thermal stresses.
Through faults are detected by O/C relays

• Protection against Phase fault


• Below 5MVA , Main protection against shortcircuit
• Above 5MVA, Backup protection for sustained
through fault

ABB India
Utilities - Automation
Page 58
Station Protection - Power Transformer Protection

Over Current protection


While selecting O/C protection of TR. Following aspects
need consideration

• Magnetising Current inrush

IDMT relays are not affected by the current inrush as they


have enough time lag
Inst. O/C relays should be HIGH-SET to avoid mal operation

• Fault currents on pri. Side and sec. Side of power


transformer are different for Ph-Ph fault

Lower value should be selected for setting of O/C.

ABB India
Utilities - Automation
Page 59
Station Protection - Power Transformer Protection

Over Current protection


While selecting O/C protection of TR. Following aspects
need consideration

• Pri. Fault current should be considered while


setting O/C

Setting of IDMT relays is generally 125% of Tr. Rating to


take care of normal O/L . Enough time delay should be
provided as per the application

• Same set of CTs should not be used for Diffl. And O/C. protn.

• Setting of Inst. O/C relay on pri. Side should be more than


asymmetrical value of fault current for 3 ph. Fault on sec.side of
Tr. (which generally adequate for mag. Inrush. current
ABB India
Utilities - Automation
Page 60
Station Protection - Power Transformer Protection

Under impedance protection


O/C relays are not always suitable as Back-up relays for
system Transformer connecting two networks (or) in
network with a large difference between maximum and
minimum short circuit fault MVA

Back-up protection must be able to see a fault at any one


of the voltage system and it must also be able to operate
for minimum short circuit MVA

• In such a case we use Under impedance relay as Back-up

Reach is independent of the magnitude of short circuit current

ABB India
Utilities - Automation
Page 61
Station Protection - Power Transformer Protection

Under impedance protection

BUS1

BUS2
ZONE-3 ZONE-2

ZONE-1

ABB India
Utilities - Automation
Page 62
Station Protection - Power Transformer Protection

Over load protection


• The permissible O/L and their duration depends upon
• Type of cooling
• Insulation class of transformer

• Higher O/L are permissible for a shorter duration

Over load % 125 150 175 200 300


Duration (Mts) 125 45 15 10 1

• Hence S/S Tr. O/L protn is arranged to initiat ALARM

• for unattended station O/L protn is arranged to TRIP CB.


After a requiste time delay
ABB India
Utilities - Automation
Page 63
Station Protection - Power Transformer Protection

Over Fluxing protection


(High magnetic flux protn)
• Over fluxing causes
• Over heating of core
• Insulation failure
• The magnetic flux in the Tr. Core is a function of V/F

• The resistance & capacitance are connected to sec.


Voltage of VT. The voltage drop acoss the resistance is a
function of V/F.
• V = line to earth voltage
• F = frequency

This voltage is fed to “Voltsper herz” relay and provided with


enough time lag.
ABB India
Utilities - Automation
Page 64
Station Protection - Power Transformer Protection

Neutral displacement protection

• Also called as Residual voltage relay

ABB India
Utilities - Automation
Page 65
Station Protection - Power Transformer Protection

Monitors:

1. Gas Detector Relay

2. Temperature Monitoring

3. Oil Level Monitor

Protective relays limit the damage in case of fault


and monitors to prevent the fault. Therefore fast
and reliable protective relays should be used.

ABB India
Utilities - Automation
Page 66
Station Protection - Power Transformer Protection

6.Monitors
• Monitors are very important devices which detect faults and
abnormal service conditions which may develop into fault.

Gas Detector Relay


• During fault, arching occurs releasing gas.

• Gas collected in alarm device gives alarm.

• Can detect a slowly developing fault before it becomes


more serious.
• Trip devices responds to the high flow of oil which occurs
during the sudden occurrence of a serious fault.

ABB India
Utilities - Automation
Page 67
Station Protection - Power Transformer Protection

Any Questions?

ABB India
Utilities - Automation
Page 68
Station Protection - Power Transformer Protection

ABB India
Utilities - Automation
Page 69

You might also like