Five types of Special Purpose
OF THE PHILIPPINES, INC Circuit Breakers
• Instantaneous Trip circuit breakers
Special Purpose Circuit Breaker • Mine Duty Circuit Breaker
• Current-limiting Circuit Breaker
• Molded Case Switch
By: Engr. Roberto C. Ocampo
• Integrally fused circuit breakers
Managing Director
GREENLIGHT POWER INC
greenlight.power@skyinet.net
INSTITUTE OF INTEGRATED
ELECTRICAL ENGINEERS
Instantaneous trip Circuit
OF THE PHILIPPINES, INC Breaker
Instantaneous Trip
Circuit Breaker
greenlight.power@skyinet.net
1
Ratings Ratings
• Do not carry an interrupting rating • NOTE
– Most often applied with motor starters – Per UL 508-1993 test requirement, after a
– Combination starters are short-circuit tested short circuit has occurred the circuit breaker
with the starter and instantaneous-trip circuit and wires must be capable of continued
breaker installed. service.
– The short-circuit rating that is applied is • UL 508-1993 test is only for one event of short
circuit occurrence. Inspection should be done on
marked on the combination starter as a result the next occurrence.
of this test
– Overload and contactor, or both may require
repair and replacement
2
Setting of instantaneous-trip Setting of instantaneous-trip
circuit breaker circuit breaker
• How do you set instantaneous trip circuit • What if information on starting current is
breaker for maximum protection? not available?
– Maximum protection can be achieved without – Starting current can be estimated by taking
nuisance tripping if instantaneous trip circuit the motor code from its nameplate and using
breaker is set just above its starting current the code letter to estimate locked rotor current
from NEC Table 430-7(b)
– Starting current in rms amperes will be
approximately two times the locked rotor
current.
INSTITUTE OF INTEGRATED
Energy Efficient Motors ELECTRICAL ENGINEERS
OF THE PHILIPPINES, INC
greenlight.power@skyinet.net
3
Magnetic Trip Setting Mine Duy Circuit Breaker
• CFR, Title 30, Section 75.601, Part 75 • Mine-duty circuit breakers offer adjustable
– Circuit breakers providing short circuit magnetic-trip points or at least several
protection for trailing cables shall be set so as settings that comply with the required
to not exceed the maximum allowable maximum allowable trip settings in Table
instantaneous settings specified in this 6.1
section; however, higher settings may be
permitted by an authorized representative of
the Secretary when he has determined that
special application are justified
Testing Requirments
• CFR, Title 30, Section 75.900-2, Part 75
– Circuit breakers protecting low- and medium-
voltage alternating current circuits serving
three phase alternating current equipment
and their auxiliary devices shall be tested and
examined at least once each month by a
person qualified as provided in 75.153.
• Code of Federal Regulation (CFR)
4
Additional Application
Add’l Application Requirement
Requirements
• Mine-duty circuit breakers feeding three • Mine-duty circuit breakers are specified to
phase ac circuits are required to be be equipped with undervoltage release.
equipped with devices to provide The undervoltage release can serve the ff
protection against undervoltage, grounded purposes:
– To trip the circuit breaker during an
phase, short circuits and overcurrent undervoltage or power outage condition
– To provide a tripping mechanism that can be
used with ground-fault or interlock circuits
– To provide an emergency tripping device that
can be activated by a remote switch or push-
button
INSTITUTE OF INTEGRATED
ELECTRICAL ENGINEERS
OF THE PHILIPPINES, INC
UL 489-1991 Definition
• A circuit breaker that does
Current Limiting Circuit Breaker not imply a fusible element
and that when operating
within its current limiting
By: Engr. Roberto C. Ocampo range, limits the let-through
Managing Director I2t to a value less than the
I2t of a ½ cycle wave of the
GREENLIGHT POWER INC
symmetrical prospective
current
greenlight.power@skyinet.net
5
Current Limiting Current Limiting
• Can be reset and service can be restored • If indications are that the fault was a
in same manner as a conventional circuit significant short circuit, the circuit breaker
breaker after clearing a fault should be examined before reenergizing.
• Caution is to be observed such that for • Check for cracks after every trip
every trip of the circuit breaker, it is
important to remove the fault and its cause • Check for operation difficulty
before reenergizing • Check for severe discoloration
• It is also important to document number of
times fault has been experienced.
Application Application
• Current Limiting circuit breakers not only • Used to sufficiently reduce IP and I2t let-
provide high interrupting ratings, but also through to values that lesser rated
limit let-through current and energy to downstream breakers can interrupt
load-side devices and conductors • Used as either an integral or remote main
breaker for lighting panel boards on
systems with high available fault current.
6
INSTITUTE OF INTEGRATED
ELECTRICAL ENGINEERS
Molded Case Switch w/o
OF THE PHILIPPINES, INC Protection
• Standard Molded
Molded Case Switch Case switch have no
thermal and magnetic
tripping element
By: Engr. Roberto C. Ocampo • Non automatic circuit
Managing Director breaker
GREENLIGHT POWER INC
greenlight.power@skyinet.net
Ratings Application
• Withstand rating from 5000 A to 200,000 A • Provide simple and compact disconnecting
and are labeled for use in series with a means.
specific overcurrent protective device or • Meet the requirement of NEC Section 430-
devices specified 109
– The disconnecting means shall be one of the
following types; motor circuit switch rated in
horsepower, a circuit breaker, or molded case
switch, and shall be listed device.
7
INSTITUTE OF INTEGRATED
Application ELECTRICAL ENGINEERS
OF THE PHILIPPINES, INC
greenlight.power@skyinet.net
8
Application Application
• Short time delay characteristics is • When applied on high short circuit current
beneficial if coordination in the capacity systems let through effects the
intermediate current range is desired characteristics of the fused circuit breakers
on downstream equipment must be
• There is a lack of coordination with the considered
load side protective devices when
• Does not necessarily mean that
currents are in the current limiting range of downstream breakers are adequately
the fuse. protected against effect of let through
current
Application Application
• NOTE • NOTE
– Fused circuit breaker do not have any current – Use of this limiters could result in less than
limiting effect until the current associated with ideal coordination with the fused circuit
the fault exceeds the threshnold current of the breaker
limiter – May cause frequent blowing of the limiters
– Manufacturers coordination data should be and in no case should combination of trip
applied carefully to protect standard breakers devices and fuses that are not approved by
downstream the manufacturer be installed.