Five types of Special Purpose
OF THE PHILIPPINES, INC Circuit Breakers
• Instantaneous Trip circuit breakers
Special Purpose Circuit Breaker • Mine Duty Circuit Breaker
• Current-limiting Circuit Breaker
• Molded Case Switch
By: Engr. Roberto C. Ocampo
• Integrally fused circuit breakers
Managing Director
GREENLIGHT POWER INC

greenlight.power@skyinet.net

INSTITUTE OF INTEGRATED
ELECTRICAL ENGINEERS
Instantaneous trip Circuit
OF THE PHILIPPINES, INC Breaker

Instantaneous Trip
Circuit Breaker

By: Engr. Roberto C. Ocampo


Managing Director
GREENLIGHT POWER INC Adjustable Instantaneous trip

greenlight.power@skyinet.net

Instantaneous trip Circuit


Ratings
Breaker
• Motor circuit Protectors • Instantaneous-trip circuit
• Provide adjustable short circuit protection breakers have maximum
but no overload protection continuous current-carrying
• Must not be used as branch circuit capacity
protection because external overload – Prolonged continuous
protection must be used with this breakers currents exceeding this
• Motor Disconnecting means rating may cause damage to
• Also used for welding equipment for short the circuit breaker
circuit protection

1
Ratings Ratings
• Do not carry an interrupting rating • NOTE
– Most often applied with motor starters – Per UL 508-1993 test requirement, after a
– Combination starters are short-circuit tested short circuit has occurred the circuit breaker
with the starter and instantaneous-trip circuit and wires must be capable of continued
breaker installed. service.
– The short-circuit rating that is applied is • UL 508-1993 test is only for one event of short
circuit occurrence. Inspection should be done on
marked on the combination starter as a result the next occurrence.
of this test
– Overload and contactor, or both may require
repair and replacement

Current Limiting Attachment Code Considerations


• Add on current limiting attachment if • Section 430-52
– An instantaneous-trip circuit breaker shall be used
added to the loadside of the instantaneous only if adjustable and if part of a listed combination
trip circuit breaker controller having coordinated motor overload and
short circuit and ground fault protection in each
– Contains specially designed fuses that open conductor and the setting is adjused to no more than
the value in Table 430-152. A motor short-circuit
and limit the current that flows under high- protector shall be permitted in lieu of devices listed in
level fault conditions Table 430-152 if the motor short circuit protector is
part of a listed combination controller having
– Low level currents will be interrupted by the coordinated motor overload protection and short
instantaneous trip circuit breaker without circuit and ground fault protection in each conductor
and it will open the circuit at currents exceeding 1300
opening the current limiting attachment percent of full load motor current.

Code Considerations Code Considerations


• Section 430-52 • Design E motors are energy-efficient
– (FPN) For the purpose of this article, motors
instantaneous-trip circuit breaker may include • Design B energy efficient may have higher
a damping means to accommodate a than 1300% of full load current.
transient motor inrush current without
nuisance tripping of the circuit breaker. • Use of instantaneous trip circuit breakers
in this application is not recommended.

2
Setting of instantaneous-trip Setting of instantaneous-trip
circuit breaker circuit breaker
• How do you set instantaneous trip circuit • What if information on starting current is
breaker for maximum protection? not available?
– Maximum protection can be achieved without – Starting current can be estimated by taking
nuisance tripping if instantaneous trip circuit the motor code from its nameplate and using
breaker is set just above its starting current the code letter to estimate locked rotor current
from NEC Table 430-7(b)
– Starting current in rms amperes will be
approximately two times the locked rotor
current.

INSTITUTE OF INTEGRATED
Energy Efficient Motors ELECTRICAL ENGINEERS
OF THE PHILIPPINES, INC

• Design B Energy efficient motors may


exhibit starting currents higher than Mine Duty Circuit Breaker
1300% of their full load current.
– Solution is to use thermal magnetic circuit
breaker that can be applied within NEC Table By: Engr. Roberto C. Ocampo
430-152 and that has an instantaneous trip
Managing Director
level sufficient to the motor starting current
GREENLIGHT POWER INC

greenlight.power@skyinet.net

Mine-Duty Circuit Breaker Mine-Duty Circuit Breaker


• Mine-duty circuit breaker are specifically • Mine-duty circuit breaker
designed for mining duty applications and – Have adjustable instantaneous trip settings
permit the user to comply with mandatory with tighter tolerances, dust shields and
mine-duty standards. gaskets, non moisture-absorbing materials,
– Subjects trailing cables to extreme and heavy duty operating mechanisms, heavy-
frequent flexing, twisting and crushing duty undervoltage release and corrosion
– Electrical faults in trailing cables occur much resistant nameplates
more frequently than normal stationary
– Available with voltage ratings up to 1000 V ac
installation
and 300 V dc.
– Presence of loose coal dust and other
combustible materials makes the occurrence
of fault very hazardous

3
Magnetic Trip Setting Mine Duy Circuit Breaker
• CFR, Title 30, Section 75.601, Part 75 • Mine-duty circuit breakers offer adjustable
– Circuit breakers providing short circuit magnetic-trip points or at least several
protection for trailing cables shall be set so as settings that comply with the required
to not exceed the maximum allowable maximum allowable trip settings in Table
instantaneous settings specified in this 6.1
section; however, higher settings may be
permitted by an authorized representative of
the Secretary when he has determined that
special application are justified

Testing Requirments
• CFR, Title 30, Section 75.900-2, Part 75
– Circuit breakers protecting low- and medium-
voltage alternating current circuits serving
three phase alternating current equipment
and their auxiliary devices shall be tested and
examined at least once each month by a
person qualified as provided in 75.153.
• Code of Federal Regulation (CFR)

Testing Requirments Circuit Breaker Location


• CFR, Title 30, Section 75.900-2, Part 75 • MCCB used to protect underground
– …In performing such tests, actuating any of circuits are required to be located in areas
the circuit breaker auxiliaries or control that are accessible for inspection and
circuits in any manner which causes the
circuit breaker to open, shall be considered a testing and have a safe roof
proper test. All components of the circuit
breaker and its auxiliary devices shall be
visually examined and such repairs or
adjustments as are indicated by such tests
and examinations shall be carried out
immediately.

4
Additional Application
Add’l Application Requirement
Requirements
• Mine-duty circuit breakers feeding three • Mine-duty circuit breakers are specified to
phase ac circuits are required to be be equipped with undervoltage release.
equipped with devices to provide The undervoltage release can serve the ff
protection against undervoltage, grounded purposes:
– To trip the circuit breaker during an
phase, short circuits and overcurrent undervoltage or power outage condition
– To provide a tripping mechanism that can be
used with ground-fault or interlock circuits
– To provide an emergency tripping device that
can be activated by a remote switch or push-
button

INSTITUTE OF INTEGRATED
ELECTRICAL ENGINEERS
OF THE PHILIPPINES, INC
UL 489-1991 Definition
• A circuit breaker that does
Current Limiting Circuit Breaker not imply a fusible element
and that when operating
within its current limiting
By: Engr. Roberto C. Ocampo range, limits the let-through
Managing Director I2t to a value less than the
I2t of a ½ cycle wave of the
GREENLIGHT POWER INC
symmetrical prospective
current
greenlight.power@skyinet.net

Current Limiting Current Limiting Circuit Breakers


• Available from 15 A to 1200 A • Same as conventional thermal-magnetic
• Rated up to 600 Volts circuit breaker or electronic trip circuit
• Interrupting ratings up to 200,000 rms breaker
symmetrical Amps • Designed so that high-speed contact
• Completely clear the faulted circuit within separation is achieved under high-level
the first half cycle fault condition
• High speed contact separation is achieved
from different manufacturers technology

5
Current Limiting Current Limiting
• Can be reset and service can be restored • If indications are that the fault was a
in same manner as a conventional circuit significant short circuit, the circuit breaker
breaker after clearing a fault should be examined before reenergizing.
• Caution is to be observed such that for • Check for cracks after every trip
every trip of the circuit breaker, it is
important to remove the fault and its cause • Check for operation difficulty
before reenergizing • Check for severe discoloration
• It is also important to document number of
times fault has been experienced.

Application Application
• Current Limiting circuit breakers not only • Used to sufficiently reduce IP and I2t let-
provide high interrupting ratings, but also through to values that lesser rated
limit let-through current and energy to downstream breakers can interrupt
load-side devices and conductors • Used as either an integral or remote main
breaker for lighting panel boards on
systems with high available fault current.

Series Rating Series Rating


• Defined in UL as utilizing circuit breaker or • Important that series ratings are not limited
fuses with current limiting capability in to current limiting circuit breaker
series with lesser-rated downstream • Selectivity will not be provided above any
breakers current level at which the circuit breaker
• Combination must be tested to verify that trip characteristic curve overlap
the current limiting circuit breaker will • For continuity of service is desired, series
protect the downstream device under the connected ratings are not recommended
test conditions

6
INSTITUTE OF INTEGRATED
ELECTRICAL ENGINEERS
Molded Case Switch w/o
OF THE PHILIPPINES, INC Protection
• Standard Molded
Molded Case Switch Case switch have no
thermal and magnetic
tripping element
By: Engr. Roberto C. Ocampo • Non automatic circuit
Managing Director breaker
GREENLIGHT POWER INC

greenlight.power@skyinet.net

Molded Case Switch with


Ratings
Magnetic Protection
• Molded Case switch with magnetic trip do not • Have maximum continuous-current rating
provide overcurrent protection which if exceeded for long periods of time
• Non adjustable magnetic trip element serves to may cause damage to the switch due to
protect the switch against the damaging effects overheating
of high level fault currents • Must be protected by an overcurrent
• Automatic switch will provide the second level of protective device of an equivalent or lower
isolation while the standard switch does not current rating
have to be reclosed and may be desirable in • Should not be used in excess of their
some logic system withstand rating

Ratings Application
• Withstand rating from 5000 A to 200,000 A • Provide simple and compact disconnecting
and are labeled for use in series with a means.
specific overcurrent protective device or • Meet the requirement of NEC Section 430-
devices specified 109
– The disconnecting means shall be one of the
following types; motor circuit switch rated in
horsepower, a circuit breaker, or molded case
switch, and shall be listed device.

7
INSTITUTE OF INTEGRATED
Application ELECTRICAL ENGINEERS
OF THE PHILIPPINES, INC

• Capable of making and breaking load


currents up to six times their marked rating Integrally Fused Circuit
• These switch can be applied where Breaker
horsepower ratings are required.
By: Engr. Roberto C. Ocampo
Managing Director
GREENLIGHT POWER INC

greenlight.power@skyinet.net

Integrally Fused CB Integrally Fused CB


• Available in both molded case and power • The limiters in these device are designed
circuit breaker to open and need replacement only after a
• The provide high interrupting capability high level fault
through the use of specially designed • Circuit breaker portion is interlocked so
current limiting fuses (limiters) that when any one of the limiter opens CB
• Assembled into the housing of the circuit will trip
breaker or in a fuse truck for LVPCB • Provided with an interlock to prevent
closing with a missing limitier

Integrally Fused CB Application


• MCCB construction provides an added • Fused circuit breaker should be selected
housing and are separated and sealed trip so that overcurrent and low magnitude
unit of the circuit breaker for easy access faults are cleared by thermal or long
time/short time tripping action
• PCB, the limiters are mounted on the rear
• Intermediate level short circuits are
of the Circuit Breaker frame or in a
cleared by short time delay magnetic or
separately mounted fuse truck instantaneous tripping action
• High level short circuit are cleared by
current limiting fuse and instantaneous trip

8
Application Application
• Short time delay characteristics is • When applied on high short circuit current
beneficial if coordination in the capacity systems let through effects the
intermediate current range is desired characteristics of the fused circuit breakers
on downstream equipment must be
• There is a lack of coordination with the considered
load side protective devices when
• Does not necessarily mean that
currents are in the current limiting range of downstream breakers are adequately
the fuse. protected against effect of let through
current

Application Application
• NOTE • NOTE
– Fused circuit breaker do not have any current – Use of this limiters could result in less than
limiting effect until the current associated with ideal coordination with the fused circuit
the fault exceeds the threshnold current of the breaker
limiter – May cause frequent blowing of the limiters
– Manufacturers coordination data should be and in no case should combination of trip
applied carefully to protect standard breakers devices and fuses that are not approved by
downstream the manufacturer be installed.