Professional Documents
Culture Documents
ELECTRICAL ENGINEERS
OF THE PHILIPPINES, INC
SCOPE
• Guidelines and instructions for developing
Acceptance & Maintenance an acceptance and maintenance testing
Requirements program for low-voltage circuit breakers
– Maintenance planning
By: Engr. Roberto C. Ocampo – Establishment of baseline data
– Training Consideration
Managing Director – Safety Consideration
GREENLIGHT POWER INC – Testing Consideration
– Acceptance Criteria
– Documentation Requirements
greenlight.power@skyinet.net
1
Preparation of Maintenance
Procedure
Program
• Prepare Detailed procedure based on • Procedure should provide a step-by-step
– Initial Installation guide to performing the desired level of
– Test Data maintenance
– Manufacturer’s information • Procedure should provide identifiable
– Training guidelines and acceptance criteria
– For licensed electrical practitioner to know
what is and is not acceptable
2
Environmental Conditions Safety
• Frequency of preventive maintenance, • Safety procedure and aspects of the job
inspection and cleaning must be high in should always be considered before actual
order to ensure the integrity of operation. work is performed
• Procedure should be modified if it is not in
accordance with the safety procedure.
• Safety personnel performing maintenance
inspection, testing, and repair should be a
prime requirement in maintenance
program
Safety Safety
• Persons performing periodic maintenance – How????
on LVCBs should be familiar with electrical – Should know where and how the breaker they
system in which the breakers are used. are working on is isolated from energized
portion of the circuit
– How????
– Testing should be performed before
– Require qualified person to memorize the
proceeding with ay maintenance work to
single line diagram.
ensure that all sources of electrical potential
– Require qualified persons to read instruction have been removed
manual of each equipment before working
– Work shall be performed by a licensed
• Prepare examination and don’t allow personnel
until they have perfected the examination. (Kumon electrical practitioner only
Style)
Safety Safety
• LVPBs shall be totally • For racking mechanism or any
disconnected from the components in the breaker cubicle is to be
switchgear bus performed, isolation of the line side stabs
connection before is necessary
performing tests or
checks on the actual
breaker
3
Safety Safety
• If LVPBs are back fed load side stabs • Awareness must be maintained
should be isolated too before working throughout the duration of the testing so
inside the cubicle. that hands and fingers are kept clear of
• Preferred method of isolation is to pinch point on LVPCB
deenergize the circuit remote form the – LVPCBs withdrawn form the cubicle may still
cubicle location have some hazards because of stored energy
mechanism
• If not possible, stabs may be covered
– Warning:
• Extreme caution must be exercised when covering
energized stabs
4
Items to be checked for MCCB Items to be checked for MCCB
• Breaker overheating • Breaker overheating
– Check the breaker for overheating when it is
operating under normal load at a normal
operating temperature
– Check the face of the breaker using the palm
of the hand for 3 seconds. If hand cannot be
maintained the breaker should be removed
from service and checked further to determine
the cause of overheating
• Use thermal imaging equipment to determine
problem
5
Items to be checked for MCCB MCCB Test
• Breaker Testing • Thermal unit Trip test.
– Thermal Magnetic – MCCB is tested by passing 300% of the
– Magnetic/Instantaneous trip units only MCCB’s ampere rating through each pole of
– Electronic Trip Device (ETDs) the MCCB
– Test results should be compared to the
manufacturer’s time current characteristics
– Curves sheets are based upon current in all
poles of the breaker and are utilized for
coordination
6
MCCB Test MCCB Test
• Shunt Trip • Insulation Resistance
– Shunt trip coil can be verified by applying the – All poles should be tested with standard
rated voltage across the coil with the MCCB insulation resistance testing guidelines at
closed. 1000v DC.
• Shunt trip device should trip the mechanical latch – Resistance values of less than 1MΏ should
that trips the MCCB be considered inadequate and the cause
• Be careful not to maintain the voltage across the should be investigated
shunt trip coil if it is not rated for continuous
potential. – Insulation should be performed between the
line and load side terminals with the MCCB
open, between adjacent poles, and pole to the
ground part of MCCB
7
Maintenance Inspection Maintenance Inspection
Procedure Procedure
1. Operate the LVPCB several times to 3. Remove and inspect the arc chutes for
make certain that the circuit breaker any cracking, breakage, or extensive
operates freely burning that would indicate a need for
a) Operate both manually and electrically to be replacement
sure all electrical components function
properly
2. Clean all dust and dirt from the LVPCB.
Maintenance Inspection
LVPCB Tests per pole
Procedure
8. Test LVPCB to ascertain that it performs • Long-time delay overcurrent that protects
on the representative time-current against overload conditions
coordination curves • Short-time delay overcurreint that protects for
lower order fault current conditions
• Instantaneous-trip operation that provides circuit
protection for short circuit or higher order fault
current conditions
• Ground fault protection that provides circuit
protection for a ground fault conditions
8
LVPCB Tests per pole LVPCB Manufacturer’s Tests
• Ground fault trip should be disabled during • Manufacturers provide test units for use on
the single-pole high current their ETDs
• This test equipment are normally
secondary injection test to measure all
verifications on the Electronic Trip Device
9
Documenting Maintenance Documenting Maintenance
Results Results
• Records need to be taken properly to take • Information should be reasonably detailed
advantage of documentation – Example: A statement such as “checked
• Documentation should be done every time breaker” does not provide enough detail. A
better record would state “checked breaker
it is necessary to inspect or investigate a
because of reported overheating” or
problem on a particular piece of equipment “overheating when I arrived-found no
problem”
– Proper documentation will help analyze and
correct the problem more effeciently
10
Testing Prerequisites Initial Conditions
5. Notify the QA/QC of the intention to 1. Verify that work clearance tags or
commence testing, as applicable permits are hung on equipment to be
tested as well as on any related
equipment or devices as required to
support this test
Precautions Precaustions
1. Carefully store all equipment parts 3. Use caution
removed during the performance of this when working
test so that they can be easily found in or around
the circuit
2. Avoid exposing equipment to moisture, breaker
dust, dirt, or other hazardous conditions cubicles, and
be aware of
energized
terminals and
space heaters
11
Precaustions Precaustions
3. Use caution when working in or around 5. During testing keep hands and fingers
the circuit breaker cubicles, and be clear of moving parts. Serious injury
aware of energized terminals and space could result from crushing forces that are
heaters present during power circuit breaker
operation
4. All tests shall be made only on circuit
6. Use only manufacturer’s recommended
breakers that are de-energized and lubricants on breakers. Don not use
isolated, so that no accidental contact is lubricants on contact faces or on
made with any live parts Electronic Trip Devices
12
Test Equipment Test Equipment
5. Psychrometer
6. Variable Voltage Source, AC or DC as
– An instrument that required
uses the difference in 7. Appropriate gauges and tools per
readings between two
thermometers, one
manufacturer’s maintenance manual
having a wet bulb and
the other having a dry
bulb, to measure the
moisture content or
relative humidity of air.
13
Visual Inspection Visual Inspection
3. Mount MCCB onto a surface that is or 5. Make a circuit continuity check with a
can be grounded (ground plate). Record digital low resistance ohmmeter on each
on data record sheet pole with the circuit breaker in the closed
4. Perform several mechanical on-off position.
operations
14
Primary Circuit Insulation Primary Circuit Insulation
Resistance Resistance
6. Connect the megohmmeter to the load- 8. Remove the line and load-side jumpers
side terminals and the cubicle. Record and ground. Record on data record
on data record sheet sheet
7. Apply the test voltage to the load side 9. Operate the MCCB to the closed position
terminals and record the megohmmeter 10. Apply megohmmeter phase-to-phase.
reading on the data record sheet Record on data record sheet
15
MCCB Overcurrent Trip Test MCCB Overcurrent Trip Test
3. Conductor leads should be of the same 5. Close the breaker and apply 300% of
size as specified in UL 489-1991, and breaker-rated continuous current to each
properly secured. pole of the circuit breaker. Repeated test
4. The test equipment must be capable of on any pole should be spaced by at least
holding the current constant over the 20 min; tests on adjacent poles must be
entire test time with as little variation as spaced by at least 5 min. Record test
possible. current on data record sheet
16
Instantaneous Overcurrent Trip
Pulse Method
Test
• Test set must be equipped with a pointer stop 1. When MCCB to be tested has an
ammeter. adjustable instantaneous trip, adjust to
• The current applied in short pulses of 5-10 MAX setting. Pulse the test setting to
cycles duration obtain desired magnetic overcurrent
• The current is increased on each succeeding (MOC). Record MOC from breaker
step until the MCCB trips
setting sheet on data record sheet.
• Caution
– Do not exceed the max. current values of
manufacturer’s time-current curve for the MCCB
magnetic coil
17
Installation of Draw-out MCCB Installation of Draw-out MCCB
cubicle cubicle
2. Align properly and install the draw-out 3. Install control transformer fuses
MCCB cubicle in appropriate 4. Reterminate wires that have been lifted.
compartment. Record on data record Record on data record sheet
sheet 5. Verify cubicle ground continuity to
ground bus. Record on data record
sheet
18
Visual Inspection Visual Inspection
4. Remove the ETD from the breaker. 6. Inspect wiring termination for tightness.
Record on data record sheet (if required Record on data record sheet
to facilitate testing) 7. Measure resistance of trip coil (TC),
5. Mark the phase identification on each of close coil (52X), and control relay (52Y)
the arc chutes and remove from the using a digital multimeter. Record on
breaker. Record on data record sheet data record sheet
19
Insulation Resistance Insulation Resistance
3. Close the LVPCB: Perform an insulation • NOTE
resistance test at 1000 Vdc for 1min or – Apply megohmmeter voltage for a period of
until the stable reading is observed. Test 1 min or until reading is stable.
each pole phase-to-ground, Record on – Acceptance criteria for insualtion resistance
should be obtained from the manufacturer’s
data record sheet instruction book
4. Remove shorting connection from the – Typical minimum criteria are 50 to 100MΏ or
ETD wiring. Record on data record greater.
sheet – Record test voltage and acceptance criteria
ondata record sheet
Close Coil and Trip coil minimum Close Coil and Trip coil minimum
voltage operation test voltage operation test
4. With charging motor switch in the OFF Note
position. Trip the breaker. Record on • DC control voltages for the LVPCB are
data record sheet assumed to be 125 V dc
5. Adjust the dc power supply output • Adjust dc power output voltage to
voltage to 125 V dc. LVPCB specified control voltage and
minimum trip voltages if using other than
125 Vdc
20
Time delay Trip Test Time Delay Trip Test
• Note
WARNING – Use the breaker setting sheet to set the test
If test has to be terminated in an set points on the ETD for long-time delay,
short time delay, and instantaneous and
emergency situation, depress ground fault trips.
output switch, then move test set
incoming circuit breaker to OFF
position
21
Restoration Restoration
3. Ensure that all data record sheets and 5. Ensure that work clearances are
tables are complete. Each data blank released, as necessary. Record on data
shall be filled out or marked N/A when record sheet
not applicable. Record on data record
sheet 6. On the data record sheet, enter the
initials, signature and printed name of the
4. Record and identify any attachment used
for the conduct of this test on the first individuals signing or initialing steps in
page of the data record sheet. Record on the performance of this tests. Record on
data record sheet data record sheet
Restoration Restoration
7. Verify electronic-trip setting is as per low 9. Ensure LVCB is completely
voltage circuit breaker setting sheet and reassembled. Record on data record
is sealed with lead seal (if available). sheet
Record on data record sheet 10. Make sure LVCB is left in the OPEN
8. Verify that calculations, if any, are position. Record on data record sheet
entered in the test data record sheet with
the acceptance criteria. Record on data
record sheet
22
Breaker Primary Circuit to Bus Breaker Primary Circuit to Bus
Connection Connection
3. Verify the primary circuit connections. 3. Verify the primary circuit connections.
Make up evenly observing the tracks in Make up evenly observing the tracks in
the lubrication. Record on data record the lubrication. Record on data record
sheet sheet
FAILURES DETECTED
• Insulation test is a definite first for many
reasons for both the equipment and most
importantly for the personnel performing
the test work.
23