You are on page 1of 23

INSTITUTE OF INTEGRATED

ELECTRICAL ENGINEERS
OF THE PHILIPPINES, INC
SCOPE
• Guidelines and instructions for developing
Acceptance & Maintenance an acceptance and maintenance testing
Requirements program for low-voltage circuit breakers
– Maintenance planning
By: Engr. Roberto C. Ocampo – Establishment of baseline data
– Training Consideration
Managing Director – Safety Consideration
GREENLIGHT POWER INC – Testing Consideration
– Acceptance Criteria
– Documentation Requirements
greenlight.power@skyinet.net

Maintenance Program Maintenance Program


• When is the best time to begin planning for • Good practice for the organization that will
maintenance of circuit breaker? be responsible for maintenance to be
• Answer present when the circuit breaker and
– When the equipment is being installed associated equipment is being installed
and checked out.

Maintenance Program Maintenance Program


• This familiarization will help the • Do you want to maintain LVCBs?
maintenance personnel feel more – Proper Training of Personnel
comfortable with the equipment and • Where?
provide information that will save time and – Circuit Breaker Manufacturer
question when maintenance or – Service Organization that are dedicated to
troubleshooting becomes necessary maintenance activities specially of circuit
breakers.

1
Preparation of Maintenance
Procedure
Program
• Prepare Detailed procedure based on • Procedure should provide a step-by-step
– Initial Installation guide to performing the desired level of
– Test Data maintenance
– Manufacturer’s information • Procedure should provide identifiable
– Training guidelines and acceptance criteria
– For licensed electrical practitioner to know
what is and is not acceptable

Documents Needed When it should be done?


• Single line Diagram • Schedule might be based on
• Elementary Control Diagram manufacturers recommendations
• Relay Setting Sheets • May be adjusted based on previous
• Circuit Breaker Manufacturer trip curves experience
• Technical Requirement for specification • May also be based on production
• Vendor Wiring/connection diagram (as demands
applicable)
• LVCB operations
• Personnel Qualifications, certifications and
training (very important) • May be based on environment (important)

Environmental Conditions Environmental Conditions


• Field conditions should be evaluated to • Clean and well conditioned environment
determine the optimum frequency for the may ensure that there will be no adverse
performance of maintenance effects and may ensure that circuit breaker
• Some should require maintenance will operate properly when required
procedures to be performed more frequent • Warning:
basis to ensure proper operation – Dirty , dusty or corrosive atmosphere might
regardless of the environment in which either become inoperative or it may
they are placed malfunction if it should attempt to interrupt a
fault that is well within its capacity

2
Environmental Conditions Safety
• Frequency of preventive maintenance, • Safety procedure and aspects of the job
inspection and cleaning must be high in should always be considered before actual
order to ensure the integrity of operation. work is performed
• Procedure should be modified if it is not in
accordance with the safety procedure.
• Safety personnel performing maintenance
inspection, testing, and repair should be a
prime requirement in maintenance
program

Safety Safety
• Persons performing periodic maintenance – How????
on LVCBs should be familiar with electrical – Should know where and how the breaker they
system in which the breakers are used. are working on is isolated from energized
portion of the circuit
– How????
– Testing should be performed before
– Require qualified person to memorize the
proceeding with ay maintenance work to
single line diagram.
ensure that all sources of electrical potential
– Require qualified persons to read instruction have been removed
manual of each equipment before working
– Work shall be performed by a licensed
• Prepare examination and don’t allow personnel
until they have perfected the examination. (Kumon electrical practitioner only
Style)

Safety Safety
• LVPBs shall be totally • For racking mechanism or any
disconnected from the components in the breaker cubicle is to be
switchgear bus performed, isolation of the line side stabs
connection before is necessary
performing tests or
checks on the actual
breaker

3
Safety Safety
• If LVPBs are back fed load side stabs • Awareness must be maintained
should be isolated too before working throughout the duration of the testing so
inside the cubicle. that hands and fingers are kept clear of
• Preferred method of isolation is to pinch point on LVPCB
deenergize the circuit remote form the – LVPCBs withdrawn form the cubicle may still
cubicle location have some hazards because of stored energy
mechanism
• If not possible, stabs may be covered
– Warning:
• Extreme caution must be exercised when covering
energized stabs

Safety Maintenance of MCCBs


• Only method of total isolation for MCCB is • Visual Inspection
to deenergize the source and the load • Cleaning
• Warning • Tightening of connection
– Removal of the MCCB from the Panel must Note:
not be done if the panel remains energized,
unless the breaker is a plug-on or draw-out – Any MCCB found to have a cracked case
type when inspected should be replaced
immediately because of possible interrupting
capability loss

Maintenance of MCCBs Maintenance of MCCBs


• Tracking is an electrical discharge • MCCBs are designed and manufactured to
phenomenon indicated by a leakage path require no INTERNAL maintenance
that is directionally erratic throughout their lifetime
– This phenomenon forms from electrical stress • MCCBs are factory calibrated and sealed
over a long period of time, especially in and should not be tampered
unclean environment and will eventually lead
to flashover • Note
– Removable cover are for installation of
accessories and manufacturer does not mean
that maintenance can be performed on the
MCCB

4
Items to be checked for MCCB Items to be checked for MCCB
• Breaker overheating • Breaker overheating
– Check the breaker for overheating when it is
operating under normal load at a normal
operating temperature
– Check the face of the breaker using the palm
of the hand for 3 seconds. If hand cannot be
maintained the breaker should be removed
from service and checked further to determine
the cause of overheating
• Use thermal imaging equipment to determine
problem

Items to be checked for MCCB Items to be checked for MCCB


• Connection Check
• Connection Check
– Visually check the
– Overheated copper connection can usually be
breaker and bus cable
cleaned and dressed satisfactorily for reuse
connection for
evidence of – Overheated aluminum connection must be
overheating replaced
– Connection must be tightened to proper
torque levels specified by manufacturer after
cleaning and replacement.

Items to be checked for MCCB Items to be checked for MCCB


• Mechanical Operation • Mechanical
– All MCCBs should be exercised (opened and Operation
closed) to ensure proper mechanical – Exercise Circuit
operation. Breaker
– Exercising an aged breaker is particularly
important considering many breakers are
never called upon to operate by an
overcurrent condition
– Exercising can free binding mechanism

5
Items to be checked for MCCB MCCB Test
• Breaker Testing • Thermal unit Trip test.
– Thermal Magnetic – MCCB is tested by passing 300% of the
– Magnetic/Instantaneous trip units only MCCB’s ampere rating through each pole of
– Electronic Trip Device (ETDs) the MCCB
– Test results should be compared to the
manufacturer’s time current characteristics
– Curves sheets are based upon current in all
poles of the breaker and are utilized for
coordination

MCCB Test MCCB Test


• Thermal unit Trip test. • Magnetic unit (Instantaneous) test..
– Curve sheets specify a maximum single pole – The MCCB is tested by passing the magnetic
trip time trip amperes through each pole of the circuit
• If single pole trip time should be used if it is breaker
available. – Circuit breaker should trip within the following
• Not all have single pole trip time for mccb parameters
– 250A or less
• +40% to -25% of the instantaneous current setting
– 400A or greater
• +25% to -25% of instantaneous current settings

MCCB Test MCCB Test


• Shunt Trip
• Magnetic unit (Instantaneous) test..
– Shunt trip devices
– Requires high current test set for all but the
are utilized to trip
smallest frame sizes of MCCBs.
an MCCB via
– Care must be taken when checking the some external
instantaneous unit with high current to insure device operation
that the thermal trip unit is not the cause of (e.g. Ground-fault
the MCCB tripping relay).
– High current should be placed on the MCCB
for very short periods of time with adequate
cool down time allowed between applications.

6
MCCB Test MCCB Test
• Shunt Trip • Insulation Resistance
– Shunt trip coil can be verified by applying the – All poles should be tested with standard
rated voltage across the coil with the MCCB insulation resistance testing guidelines at
closed. 1000v DC.
• Shunt trip device should trip the mechanical latch – Resistance values of less than 1MΏ should
that trips the MCCB be considered inadequate and the cause
• Be careful not to maintain the voltage across the should be investigated
shunt trip coil if it is not rated for continuous
potential. – Insulation should be performed between the
line and load side terminals with the MCCB
open, between adjacent poles, and pole to the
ground part of MCCB

MCCB Test MCCB Test


• Contact Resistance • Rated Load Test
– Contact resistance should be measured using – A rated load hold-in test can be run if there is
ohmmeter capable of measurement into the some doubt of the MCCB’s ability to carry
micro-ohm range (ducter) rated load
– Not practical for smaller sized MCCB where – All three pole of MCCBs in free air are
the test lead clip is larger than the MCCB’s connected in series with jumper of a short
terminal length and adequate capacity. Apply rated
load for min of 30 min should not cause the
breaker to trip

Maintenance of LVPCBs Maintenance of LVPCBs


• Maintenance performed on LVPCBs • WARNING/CAUTION
should follow the manufacturer’s – A thorough inspection should be performed
inspection and maintenance instruction every time after the LVPCB has interrupted
whenever possible – Why?
• Inspection should follow a maintenance • Very seldom that a LVPCB will trip because of
overload in the main switchgear normally there is a
schedule established for the particular site short circuit fault
• First inspection should occur based on
manufacturers prescribed period

7
Maintenance Inspection Maintenance Inspection
Procedure Procedure
1. Operate the LVPCB several times to 3. Remove and inspect the arc chutes for
make certain that the circuit breaker any cracking, breakage, or extensive
operates freely burning that would indicate a need for
a) Operate both manually and electrically to be replacement
sure all electrical components function
properly
2. Clean all dust and dirt from the LVPCB.

Maintenance Inspection Maintenance Inspection


Procedure Procedure
4. Check the condition of contacts, both 5. Check the latch mechanisms and their
moving and stationary, and ensure engagements, both open and closed
proper contact penetration. 6. Check the lubrication and lubricate as
necessary per the manufacturer’s
instruction
7. Check operation of manual tripping
devices

Maintenance Inspection
LVPCB Tests per pole
Procedure
8. Test LVPCB to ascertain that it performs • Long-time delay overcurrent that protects
on the representative time-current against overload conditions
coordination curves • Short-time delay overcurreint that protects for
lower order fault current conditions
• Instantaneous-trip operation that provides circuit
protection for short circuit or higher order fault
current conditions
• Ground fault protection that provides circuit
protection for a ground fault conditions

8
LVPCB Tests per pole LVPCB Manufacturer’s Tests
• Ground fault trip should be disabled during • Manufacturers provide test units for use on
the single-pole high current their ETDs
• This test equipment are normally
secondary injection test to measure all
verifications on the Electronic Trip Device

Documenting Maintenance Documenting Maintenance


Results Results
• Good maintenance records when properly • Example
documented and analyzed will save you – User may want to know why the malfunction
time, money, aggravation and even your occurred, how long repairs will take and what
like or life of your personnel will be done to prevent the breaker trip from
happening again.
• Example
– Unexpected breaker trips can result in lost
• Keeping proper records can help to
production for the user. In most cases the loss address these concerns more efficiently
in production is more than the amount of the
breaker.

Documenting Maintenance Documenting Maintenance


Results Results
• A particular breaker may trip under test at – If this conditioned are not noticed or worst not
a higher current or longer time than it did tested, the wire and equipment that the
initially installed and after repeating the breaker was intended to protect could be
seriously damaged if the breaker will not trip
test a second time the breaker performs during a fault.
closer to its setting
– May cause fire, serious injury or death.
• Solution
– Breaker may either need to be exercised
more frequently or be consulted with the
manufacturer

9
Documenting Maintenance Documenting Maintenance
Results Results
• Records need to be taken properly to take • Information should be reasonably detailed
advantage of documentation – Example: A statement such as “checked
• Documentation should be done every time breaker” does not provide enough detail. A
better record would state “checked breaker
it is necessary to inspect or investigate a
because of reported overheating” or
problem on a particular piece of equipment “overheating when I arrived-found no
problem”
– Proper documentation will help analyze and
correct the problem more effeciently

Testing Program Testing Prerequisites


• Test procedures are done to provide 1. Review the past data record sheet and
instructions for performing and verify that previous deficiencies will not
documenting the results of test on LVCBs. affect the test.
• Acceptance criteria and source of that 2. Verify that the components to be tested
criteria are entered on the test data record has been released to the testing
sheets immediately following the organization by the operation
specification criteria organization

Testing Prerequisites Testing Prerequisites


3. Record the current revision numbers 5. Verify that no temporary modifications
and/or dates of implementing references will affect the performance of this
used on the test data cover sheet procedure
4. Verify that the test procedure and the 6. Notify the shift supervisor prior to
official test data recording sheet contain commencement, stopping, or restarting
the latest revision. this test

10
Testing Prerequisites Initial Conditions
5. Notify the QA/QC of the intention to 1. Verify that work clearance tags or
commence testing, as applicable permits are hung on equipment to be
tested as well as on any related
equipment or devices as required to
support this test

Initial Conditions Initial Conditions


2. Place warning signs and barriers around 3. Ensure that the test equipment has a
equipment to be tested valid calibration status (if applicable).
Record test equipment description,
control number, and calibration due on
test data cover sheet.

Precautions Precaustions
1. Carefully store all equipment parts 3. Use caution
removed during the performance of this when working
test so that they can be easily found in or around
the circuit
2. Avoid exposing equipment to moisture, breaker
dust, dirt, or other hazardous conditions cubicles, and
be aware of
energized
terminals and
space heaters

11
Precaustions Precaustions
3. Use caution when working in or around 5. During testing keep hands and fingers
the circuit breaker cubicles, and be clear of moving parts. Serious injury
aware of energized terminals and space could result from crushing forces that are
heaters present during power circuit breaker
operation
4. All tests shall be made only on circuit
6. Use only manufacturer’s recommended
breakers that are de-energized and lubricants on breakers. Don not use
isolated, so that no accidental contact is lubricants on contact faces or on
made with any live parts Electronic Trip Devices

Test Equipment Test Equipment


1. Megaohmeter 2. Digital
Multimeter

Test Equipment Test Equipment


3. Digital Low Resistance Ohmeter 4. Circuit Breaker Test Set

12
Test Equipment Test Equipment
5. Psychrometer
6. Variable Voltage Source, AC or DC as
– An instrument that required
uses the difference in 7. Appropriate gauges and tools per
readings between two
thermometers, one
manufacturer’s maintenance manual
having a wet bulb and
the other having a dry
bulb, to measure the
moisture content or
relative humidity of air.

Personnel Orientation Personnel Orientation


• Lead test engineer shall ensure that • Lead test engineer shall also ensure that
personnel performing this test have been the personnel have been trained in safety
trained with respect to the operation of the precautions, data collecting techniques,
electrical system, operation of test and actions to be taken in the event that
equipment and the electrical equipment to abnormal or unexpected conditions occur
be tested

TEST INSTRUCTIONS Visual Inspection


• MCCBS 1. Determine ambient temperature. Record
on data record sheet
2. Check that the MCCB is free of visual
defects, chipping, cracks, breaks, burns,
signs of overheating and deterioration.
Record this on the data record sheet.

13
Visual Inspection Visual Inspection
3. Mount MCCB onto a surface that is or 5. Make a circuit continuity check with a
can be grounded (ground plate). Record digital low resistance ohmmeter on each
on data record sheet pole with the circuit breaker in the closed
4. Perform several mechanical on-off position.
operations

Primary Circuit Insulation Primary Circuit Insulation


Resistance Resistance
• Note: 1. Short all auxiliary
– Apply megohmmeter voltage for a period of leads on the MCCB
1min or until reading is stable for test voltage together and connect
selection to cubicle frame. This
– Acceptance criteria for insulation resistance would include leads
should be obtained from manufacturer’s from auxiliary contacts
instruction book or from the shunt trip
– Record test voltage and acceptance criteria coil. Record on data
on data record sheet
record sheet

Primary Circuit Insulation Primary Circuit Insulation


Resistance Resistance
2. With the MCCB open, jumper the line- 4. Apply the test voltage to the line-side
side terminals together. Jumper the terminals and record the megohmmeter
load-side terminals together. Ground reading on the data record sheet
load-side terminals to cubicle. Record 5. Remove the ground from the load-side
on data record sheet terminals and put it on the line-side
3. Connect the megaohmmeter to the line- terminals. Record on data record sheet
side terminals and the cubicle. Record
on data record sheet.

14
Primary Circuit Insulation Primary Circuit Insulation
Resistance Resistance
6. Connect the megohmmeter to the load- 8. Remove the line and load-side jumpers
side terminals and the cubicle. Record and ground. Record on data record
on data record sheet sheet
7. Apply the test voltage to the load side 9. Operate the MCCB to the closed position
terminals and record the megohmmeter 10. Apply megohmmeter phase-to-phase.
reading on the data record sheet Record on data record sheet

Primary Circuit Insulation


MCCB Overcurrent Trip Test
Resistance
11. Apply megohmmeter phase-to-ground. • CAUTION
Record on data record sheet – Care should be taken to limit the maximum
12. Remove test equipment, shorts, and trip time to prevent damage to the MCCB
ground installed for from the cubicle.
Record on data record sheet.

MCCB Overcurrent Trip Test MCCB Overcurrent Trip Test


1. Obtain the desired time range for the 2. Make certain that the time delay tests are
type and rating of the circuit breaker made in open air at an ambient
being tested from the applicable breaker temperature of 25OC (if possible) with
setting sheet. If the breaker setting breakers allowed to adjust to that
sheet is not available use the temperature before starting overcurrent
manufacturer’s curve to obtain the tests
correct time range at 300% of the
breaker’s rated circuit. Record on data
record sheet

15
MCCB Overcurrent Trip Test MCCB Overcurrent Trip Test
3. Conductor leads should be of the same 5. Close the breaker and apply 300% of
size as specified in UL 489-1991, and breaker-rated continuous current to each
properly secured. pole of the circuit breaker. Repeated test
4. The test equipment must be capable of on any pole should be spaced by at least
holding the current constant over the 20 min; tests on adjacent poles must be
entire test time with as little variation as spaced by at least 5 min. Record test
possible. current on data record sheet

MCCB Overcurrent Trip Test MCCB Shunt trip Device


6. Record the breaker trip time for each 1. Obtain the percentage shunt-trip coil
pole on data record sheet voltage (%TCV) and the minimum trip
voltage (MTV) from the MCCB
manufacturer. Calculate the MTV if only
%TCV is obtained. Enter on data record
sheet
2. Apply the MTV to the shunt trip coil and
observe the MCCB trips, record on data
record sheet.

Instantaneous Overcurrent Trip


Run-Up Method
Test
Methods of test • Test set current control is set at a point
1. Run-up method equal to 70% of expected tripping current
2. Pulse Method when energized.
• After power is turned on, the current can
then be increased from 70% value to a
tripping current without excessive delay
which could cause the thermal unit to trip

16
Instantaneous Overcurrent Trip
Pulse Method
Test
• Test set must be equipped with a pointer stop 1. When MCCB to be tested has an
ammeter. adjustable instantaneous trip, adjust to
• The current applied in short pulses of 5-10 MAX setting. Pulse the test setting to
cycles duration obtain desired magnetic overcurrent
• The current is increased on each succeeding (MOC). Record MOC from breaker
step until the MCCB trips
setting sheet on data record sheet.
• Caution
– Do not exceed the max. current values of
manufacturer’s time-current curve for the MCCB
magnetic coil

Instantaneous Overcurrent Trip Instantaneous Overcurrent Trip


Test Test
2. Obtain the MCCB maximum (plus 3. Alternately decrease magnetic-trip
TOLERANCE) and minumum (minus adjustment and pulse test set to obtain
TOLERANCE) tolerances from the MOC. Record the actual MOC trip
MCCB manufacturer. Typical values for obtained on the data record sheet
the MOC setting of the MCCB 4. Perform steps 1) through 3) for each pole
to be tested.

Instantaneous Overcurrent Trip Installation of Draw-out MCCB


Test cubicle
5. Indicate on the data record sheet the 1. Ensure that the MCCB is in the Open
final setting for each pole adjustment of Position. Record on data record sheet
the instantaneous trip device • Caution
6. Remove MCCB from grounding plate – Before installing MCCB cubicles into their
installed and record on record sheet respective compartments, ensure that there
are no protruding metal screws or sharp
7. Enter data record sheet the completion
edges which would damage adjacent cable
of step insulation and that the terminations on the
MCCB have the correct bolts and washers
properly installed

17
Installation of Draw-out MCCB Installation of Draw-out MCCB
cubicle cubicle
2. Align properly and install the draw-out 3. Install control transformer fuses
MCCB cubicle in appropriate 4. Reterminate wires that have been lifted.
compartment. Record on data record Record on data record sheet
sheet 5. Verify cubicle ground continuity to
ground bus. Record on data record
sheet

LVPCB Visual Inspection


1. Record ambient temperature on the data
WARNING record sheet
Due to extreme crushing forces 2. Remove LVPCB from its compartment.
present during the open and close Record on data record sheet
cycles of the LVPCB, care must be 3. Ensure the breaker to be tested is in the
taken to keep hands and fingers OPEN and SPRINGS DISCHARGED
away from the moving parts of the position. Record on data record sheet
breaker

Visual Inspection Visual Inspection


3. Ensure the breaker to be tested is in the 3. Ensure the breaker to be tested is in the
OPEN and SPRINGS DISCHARGED OPEN and SPRINGS DISCHARGED
position. Record on data record sheet position. Record on data record sheet

18
Visual Inspection Visual Inspection
4. Remove the ETD from the breaker. 6. Inspect wiring termination for tightness.
Record on data record sheet (if required Record on data record sheet
to facilitate testing) 7. Measure resistance of trip coil (TC),
5. Mark the phase identification on each of close coil (52X), and control relay (52Y)
the arc chutes and remove from the using a digital multimeter. Record on
breaker. Record on data record sheet data record sheet

Visual Inspection Breaker Mechanical Operation


8. Check contact 1. Contact adjustment (for butt-type
contacts only). Record on data record
sheet
2. Manual slow close. Record on data
record sheet.
3. Primary trip latch adjustment. Record on
data record sheet.

Breaker Mechanical Operation Insulation Resistance


4. Tripper bar adjustment. Record on data 1. Connect all wires of the ETD wiring
record sheet harness together and to ground
5. Shunt-trip device adjustment. Record on 2. Place the charging motor disconnect
data record sheet. switch in the OFF position to isolate the
6. Shut trip device adjustment. Record on charging motor
data record sheet
7. Magnetic latch device trip adjustment.
Record on data record sheet.

19
Insulation Resistance Insulation Resistance
3. Close the LVPCB: Perform an insulation • NOTE
resistance test at 1000 Vdc for 1min or – Apply megohmmeter voltage for a period of
until the stable reading is observed. Test 1 min or until reading is stable.
each pole phase-to-ground, Record on – Acceptance criteria for insualtion resistance
should be obtained from the manufacturer’s
data record sheet instruction book
4. Remove shorting connection from the – Typical minimum criteria are 50 to 100MΏ or
ETD wiring. Record on data record greater.
sheet – Record test voltage and acceptance criteria
ondata record sheet

Close Coil and Trip coil minimum


Main Contact Continuity Test
voltage operation test
1. With breaker closed, using a digital low- 1. Slowly adjust the dc power supply output
resistance ohmmeter read the resistance voltage to 100 V dc. Record on data
across the main contacts (line-to-load) record sheet
on each phase. Record on data record 2. Close breaker using the close push
sheet button. Record on data record sheet
2. Open the breaker 3. Adjust the dc power supply output
voltage to 70 V dc. Record on data
record sheet

Close Coil and Trip coil minimum Close Coil and Trip coil minimum
voltage operation test voltage operation test
4. With charging motor switch in the OFF Note
position. Trip the breaker. Record on • DC control voltages for the LVPCB are
data record sheet assumed to be 125 V dc
5. Adjust the dc power supply output • Adjust dc power output voltage to
voltage to 125 V dc. LVPCB specified control voltage and
minimum trip voltages if using other than
125 Vdc

20
Time delay Trip Test Time Delay Trip Test
• Note
WARNING – Use the breaker setting sheet to set the test
If test has to be terminated in an set points on the ETD for long-time delay,
short time delay, and instantaneous and
emergency situation, depress ground fault trips.
output switch, then move test set
incoming circuit breaker to OFF
position

Time Delay Trip Test Time Delay Trip Test


1. Replace the arc chutes and the ETD in 2. Perform the following steps in
the breaker. Record on data record accordance with breaker test set manual
sheet. and verify that the trip times are in
accordance with the manufacturer’s
instruction manual. Record each step on
data record sheet
a) Long-time delay trip test
b) Short time delay trip test
c) Instantaneous trip test
d) Ground fault trip test

Time Delay Trip Test Restoration


3. Verify that the ETD for the breaker has 1. Remove test cable and modification, as
been tested and the final settings have necessary. Record on data record sheet
been made in accordance with the 2. Ensure that all equipment used during
breaker setting sheet. Record on data the performance of this test has been
record sheet disconnected and removed, and that the
surrounding area has been cleaned.
Record on data record sheet

21
Restoration Restoration
3. Ensure that all data record sheets and 5. Ensure that work clearances are
tables are complete. Each data blank released, as necessary. Record on data
shall be filled out or marked N/A when record sheet
not applicable. Record on data record
sheet 6. On the data record sheet, enter the
initials, signature and printed name of the
4. Record and identify any attachment used
for the conduct of this test on the first individuals signing or initialing steps in
page of the data record sheet. Record on the performance of this tests. Record on
data record sheet data record sheet

Restoration Restoration
7. Verify electronic-trip setting is as per low 9. Ensure LVCB is completely
voltage circuit breaker setting sheet and reassembled. Record on data record
is sealed with lead seal (if available). sheet
Record on data record sheet 10. Make sure LVCB is left in the OPEN
8. Verify that calculations, if any, are position. Record on data record sheet
entered in the test data record sheet with
the acceptance criteria. Record on data
record sheet

Breaker Primary Circuit to Bus Breaker Primary Circuit to Bus


Connection Connection
1. With the LVPCB control power circuit 2. Rack the LVPCB to the DISCONNECT
de-energized, rack the LVPCB into the position. Record on data record sheet
connect position. Record on data record
sheet

22
Breaker Primary Circuit to Bus Breaker Primary Circuit to Bus
Connection Connection
3. Verify the primary circuit connections. 3. Verify the primary circuit connections.
Make up evenly observing the tracks in Make up evenly observing the tracks in
the lubrication. Record on data record the lubrication. Record on data record
sheet sheet

Breaker Primary Circuit to Bus


FAILURES DETECTED
Connection
• NOTE • Should the LVCB fail any of the test in the
– If an uneven primary contact makeup is sequence, the tests should be stopped at
displayed, adjust the contact fingers to that point and the failure noted on the data
achieve a satisfactory contact marking record sheet
• Similarly, test should not be performed in
any other sequence, because the order of
testing is to protect all concerned.

FAILURES DETECTED
• Insulation test is a definite first for many
reasons for both the equipment and most
importantly for the personnel performing
the test work.

23

You might also like