Professional Documents
Culture Documents
15.1 General 2
15.3 Operation 9
15.3.1 Pitch 9
15.3.2 Load 9
7000 BASIC 15 - 1
15 Pitch and Load Control 4415E001a
The load control system is intended to protect the propulsion plant from
excessive load fluctuations. Such fluctuations might arise, for instance in
heavy seas or when manoeuvring the vessel. Special functions and
programmes are implemented to take care of the system in special
situation, an example may be reduction zone function, load acceptance
programme etc., and these functions are described later in this chapter.
The fuel rack sensor measures the position of the fuel pumps on the
engine. This is highly correlated with the load of the engine.
The engine RPM sensor measure a frequency that are proportional to the
engine rpm.
15 - 2 7000 BASIC
4415E001a Pitch and Load Control 15
If the servo oil pressure is below set level, the pressure switch will stop
the pitch control function. The pressure sensor is set for each installation
and the pressure setting can be find in the sensor list for the system.
The main unit for pitch and load control in the system is the Propulsion
Control Unit (PCU). Here are all control algorithms for these functions
implemented. Also the responsibility system is implemented in this unit
together with the load and pitch control.
3. Pitch order set signal given by the lever position from the lever in the
BCS.
4. Pitch order set signal given by the lever position from the lever in the
ECS.
5. Pitch order set signal given by the lever position from the lever in the
ACS.
6. Pitch order set signal given by the lever position from the lever in the
WCS-P.
7. Pitch order set signal given by the lever position from the lever in the
WCS-S.
The pickup signal from the engine is measured by one of the digital
inputs (X0 to X4) in the PCU-PLC.
7000 BASIC 15 - 3
15 Pitch and Load Control 4415E001a
15 - 4 7000 BASIC
4415E001a Pitch and Load Control 15
The pitch actuator handles the movement of the pitch position from one
set point to another. The actuator is normally fitted on the gearbox and is
interfaced with the manoeuvring system through cables between the
terminal strip in the PCU and the junction box on the pitch actuator.
Indication instrument and display Pitch indication is split into two parts.
Firstly, the pitch is displayed digitally on the main display screen and on
the pitch indicators. The pitch indication instrument on all stations is fed
through a special current loop and are totally separated from the other
indication of the pitch in the main control loop.
7000 BASIC 15 - 5
15 Pitch and Load Control 4415E001a
Position speed
Fig 15-3
The speed according to position is set using the curve in Fig 15-3. The
deviation is the difference between order and feedback. Suppose the
deviation is zero. The pitch lever is moved and the new deviation is
greater than outer dead band. Then the pitch will start moving and will
continue so until the deviation is below inner dead band.
15 - 6 7000 BASIC
4415E001a Pitch and Load Control 15
Load speed
Fig 15-5
a) Centre point
b) 100 % - RedZone
c) Lower outer deadband
d) Lower inner deadband
e) Upper inner deadband
f) Upper outer deadband
g) Extreme overload
If the load is below the centre point a), the load speed is set to maximum
speed.
If the load is between centre point a), and 100 % - RedZone then
loadspeed is calculated according to the left K-Curve. If RedZone is zero
than it is the lower dead band c), that is the right side limit in this
position.
If the load is between the inner dead band d) and e), the load speed is
zero.
If the load is outside the inner dead band d), but inside the outer dead
band c), the load speed is then set to minimum speed if the speed was not
zero last scan. If it was zero then it still will be set to zero.
7000 BASIC 15 - 7
15 Pitch and Load Control 4415E001a
If the load becomes higher then 100% load, overload is calculated which is
load speed inverted.
If the load comes above upper and inner dead band e), then the overload
speed is set to minimum until upper outer dad band f) is reached,
whereas the overload speed is calculated according to the right hand K-
Curve.
Fig 15-8
The RedZone is short for reduction zone. The motivation for introducing
the RedZone is to minimise the small movement of the propeller blades
when the pitch operates near overload condition due to harsh weather
conditions. These small movements tear extra hard on the propeller
sealing because there is not much lubrication during these movements.
The RedZone is updated after a certain interval, the reduction zone time,
which it is possible to calibrate. It stays put, increases or decreases with
reduction zone step after the end of the interval.
If there is heavy load changes and the engine starts to go in and out of
overload the reduction zone increases. Assume that it has increased to 5
%. Then the system will not increase pitch before the load is below 95 %.
15 - 8 7000 BASIC
4415E001a Pitch and Load Control 15
It will reduce the pitch as usual if the engine is overloaded. The reduction
zone will continue to increase because of the hard weather until an
equilibrium position is obtained. If the weather improves the reduction
zone is automatically decreased.
15.3 Operation
15.3.1 Pitch
• Move the order set lever in command ahead to move the ship ahead.
• Move the order set lever in command astern to move the ship astern.
15.3.2 Load
To set the reduction zone function in manual mode, choose the reduction
zone menu on the operator panel and switch to manual. The desired
reduction zone can then be inserted. To put it back to automatic mode,
choose automatic. It is recommended to use automatic mode during
normal operation.
The overload system will automatically make sure the engine is not
overloaded. However it is always wise to manoeuvre the ship more gently.
7000 BASIC 15 - 9
15 Pitch and Load Control 4415E001a
15 - 10 7000 BASIC