2 | nVent.com/ERICO
Proven for Critical Applications
nVent ERICO pioneered the development They are renowned for their application
of the Surge Reduction Filter in critical sites, with common application
commencing in the 1980’s, and since then to telecommunications sites, data
tens of thousands have been installed centers, process control plants, defense
in some of the highest lightning areas installations, and airports.
of the world. A policy of continuous
product improvement has seen updated
performance levels, culminating in the
SRF N-Series.
DEFENSE
AIRPORTS
nVent.com/ERICO | 3
SRF N-Series Combined Technology Protection
4 | nVent.com/ERICO
Spark Gap Technology
The SRF N-Series has as its primary be installed in a high lightning area and
surge diversion stage a high-energy withstand those surge currents that can
Spark Gap from each phase to neutral occur from a direct strike to the facility.
and from neutral to ground. These
The design of the Spark Gaps used
devices offer remarkable surge diversion
is such that they have fast operating
capability (rated at 130 kA 8/20 μs, 50 kA
characteristics while extinguishing after
10/350 μs), that allows them to handle
the surge has passed, drawing low levels
partial direct strike lightning currents. The
of follow current even on high prospective
range has been tested to the IEC standard
short circuit current services.
Class I tests to ensure that the filter can
nVent.com/ERICO | 5
Filtering Technology
Surge protection devices may include The SRF N-Series use true series The IEC standard for testing and
a filtering stage to help condition the connected LC filtering. Since the load assessing the performance of Surge
waveshape, thereby providing superior current feeding the equipment to be Protective Devices (IEC 61643-11)
protection for sensitive electronics. protected has to go through the SRF, the defines the let-through voltage of the
This said, it is important to realize that a inductors have to be rated to carry this SPD as the Voltage Protection Level,
number of different topologies of filter load current. As a consequence, the range Up. Under standardized test conditions,
circuit exist, each providing significantly consists of a number of models to suit this is determined for each SPD tested.
different performance. At its simplest, a increasing load currents, with the larger Traditional Spark Gap technologies, while
manufacturer may include a capacitor in current models being physically larger. being rugged, have a relatively high Up,
parallel with the output. This may serve In addition to the heavy duty inductors, usually in the range of 2 kV to 3 kV. Metal
to reduce any fast ringing voltages and the capacitors used in this filter stage are Oxide Varistors (MOVs) perform better at
will also help absorb the energy in a small of a special high reliability type, having clamping the voltage, having typical Up
transient thereby providing a limited level received safety approvals from a number values in the range of 1500 V to 1800 V.
of attenuation. of ratings agencies. When subjected to the same tests, the
SRF N-Series have dramatically lower
A far more effective approach is the Finally, the type of filter needed for a
Up values in the range of 450 V to 650 V.
series LC filter. This type of filter is Surge Reduction Filter is very different to
Of course, the lower the value of Up, the
connected between the surge limiting that used for higher frequency RFI/EMI
(Radio Frequency Interference/Electro- better the SPD prevents damage to the
components and is in series with the
equipment being protected.
supply powering the equipment. It magnetic Interference) filters. These
consists of series inductors and parallel simple filters use small components that
capacitors. Surge protection devices of are effective for higher frequencies but
this nature are often referred to as “two are ineffective against lightning surge
port” devices since they have a distinct frequencies.
input and output side.
6 | nVent.com/ERICO
ARRIVAL OF SURGE
kV
Risetime = 1.2 μs
6 kV
V(t)
50 μs
μs
nVent.com/ERICO | 7
Transient Discriminating Technology
TRADITIONAL TECHNOLOGIES
Conventional SPD technologies utilizing
metal oxide varistors and/or silicon
avalanche diodes to clamp or limit
transient events are susceptible to
sustained 50/60 Hz mains over-voltage
conditions ( TOVs) which often occur
during faults to the utility system. Such Repetitive Clamping Causes SPD
to Heat Up, Possibly Exploding or
occurrences present a significant safety SPD in Causing a Fire
hazard when the suppression device Conduction
attempts to clamp the peak of each half
cycle on the mains overvoltage. This TOV Nominal Clamping
Condition Voltage on 50/60 Hz
condition can cause the device to rapidly
accumulate heat and in turn fail with the Nominal AC Mains
possibility of inducing a fire hazard. Operating Voltage
8 | nVent.com/ERICO
THE CORE OF TD TECHNOLOGY
TRADITIONAL TECHNOLOGY
The secret to nVent ERICO Transient As the explanatory illustration shows,
Discriminating Technology is its active this allows the TD circuit to still remain
frequency discrimination circuit. This operational after TOV events, thus
patented device can discriminate continuing to clamp transients and
Thermal
between a temporary over-voltage ( TOV ) providing a much longer operational life. Disconnector
condition and a very fast transient, which For example, the IEC 61643-11 standard
is associated with lightning or switching- applies a test of 442 Vac from Line to
induced surges. When the transient Neutral for filters with an operating voltage
frequencies are detected, the patented of 230 Vac. While the filter may fail safely
Quick-Switch within TD activates to allow during this test, the N-Series SRFs are
the robust protection to limit the incoming unaffected by this stringent test, and
transient. The frequency discriminating remain completely operational.
circuit that controls the Quick-Switch The SRF N-Series (incorporating TD
helps ensure that the SPD device is Technology) is especially recommended ACTIVE TD TECHNOLOGY
immune to the effects of a sustained 50 for any site where sustained over-voltages
or 60 Hz TOV. This allows the device to are known to occur, and where failure
keep operating, in order to help provide of traditional SPD technologies cannot TD
safe and reliable transient protection, even be tolerated.
Quick
Switch
after an abnormal over-voltage condition
has occurred.
Thermal
Effectively, TD Technology allows the SPD Disconnector
to have two clamping levels – one well
above the peak of a TOV (up to twice its
nominal AC voltage!), and the other much
lower, to effectively and swiftly clamp
lightning transients.
TD TECHNOLOGY SOLUTION
TD Technology clamps
time after time!
TD technology
clamping
nVent.com/ERICO | 9
Combining Technologies Into
The Ultimate AC Surge Protector
DEVELOPMENT OF SURGE
REDUCTION FILTERS THE KEY BENEFITS OF COMBINED TSG & TD TECHNOLOGY
nVent ERICO strives to employ the most ARRIVAL OF SURGE PRIMARY DIVERSION STAGE RESIDUAL WAVEFRONT
up to 500 microseconds for long tail pulses up to 500 μs. This efficient inductor to
and determines how much energy the determines how much be utilized, greatly
energy the inductor reducing the size and
inductor will have to store before reaching
must store before weight of the filter, in
saturation and becoming ineffective. becoming saturated.
μs
addition to providing
improved all-around
The secondary TD Technology diverter
performance.
adds additional protection, and is
particularly useful for clamping transients
generated within the facility.
10 | nVent.com/ERICO
WHAT BENEFITS FLOW FROM THE IEC 61643-11 SURGE Finally, the filters are tested on AC
THIS TECHNOLOGY? PROTECTIVE DEVICES supplies able to deliver the full rated
STANDARD prospective short circuit current for safe
The combination of Spark Gaps and behavior during various internal short
series filtering provides the benefits of This standard (previously IEC61643-1) is circuits and even short circuits across the
high surge capability, low let-through the international standard for testing of output terminals. Some manufacturers
voltage and considerably reduced rate of surge protection devices (SPDs). It has resist testing to this standard because it is
voltage rise (dv/dt). Additional benefits of evolved over the years to become the difficult to pass. Our product compliance
reduced size, weight and heat dissipation benchmark for ensuring performance is your assurance for safe and reliable
also result. and safety of SPDs. The SRF N-Series site protection.
is in complete compliance with the
In keeping with the role of the SRF
latest version of this standard, and a
N-Series to protect highly critical
Declaration of Conformity is available.
facilities, the design of these filters
The standard mandates severe tests
has been simplified to feature direct
for safety and performance, testing
connection from input to output.
such aspects of the SPD’s ability to
Avoiding unnecessary series overcurrent
withstand multiple standardized surge
protection improves the overall reliability
impulses, measurement of the voltage
of the system.
clamping level of the SPD to those surges,
Overall operational status can be safe behavior during various failure
determined from the front door mode simulations, and sustained TOV
indication LED. Further LEDs within the situations. In addition, series connected
unit identity the correct functioning of devices, such as the SRF N-Series, are
the individual surge protection elements. put through load current tests at the rated
Remote indication of the status is easily load current, and also at severe overload
accomplished by connection to the currents to ensure safety and correct
remote status relay contacts within functioning.
the unit.
nVent.com/ERICO | 11
Surge Reduction Filter N-Series, Single Phase
FEATURES
• High-performance protection
incorporating Spark Gap and Transient
Discriminating ( TD) technologies
• High surge rating ideal for exposed
critical service entrance applications
• Reduces let-through voltages and
rate-of-voltage rise (dv/dt) and helps
provide optimum protection for D
electronic equipment
• Extreme reliability and simplified
design with direct connection from
input to output H
SPECIFICATION
12 | nVent.com/ERICO
Part Number SRF163N SRF1125N
Mounting Wall mount
AS1768 Ratings
Part Number SRF163N SRF1125N
Max Continuous Operating Voltage 310 VAC
Maximum Surge Current, L-N 130 kA 8/20 μS
50 kA 10/350 μs
Maximum Surge Current, N-PE 130 kA 8/20 μS
50 kA 10/350 μs
Voltage Protection Level, L-N 150 V @ 3 kA 8/20 μs 250 V @ 3 kA 8/20 μs
200 V @ 20 kA 8/20 μs 350 V @ 20 kA 8/20 μs
IEC 61643-11 Annex A specifies Max Continuous Operating Voltage (Uc) as 255 VAC.
IEC 61643-11 test procedure limits maximum Impulse Current (Iimp) to 10kA due to internal product safety fusing.
IEC 61643-11 recommends a maximum preferred value for Nominal Discharge Current (In) of 20 kA.
IEC 61643-11 Temporary Overvoltage tests are passed in withstand mode.
Upstream overcurrent protection not exceeding Rated Load Current (IL) shown above must be installed ahead of the surge reduction filter.
nVent.com/ERICO | 13
Surge Reduction Filter N-Series, Three Phase
FEATURES
• High-performance protection
incorporating Spark Gap and Transient
Discriminating ( TD) technologies
• High surge rating ideal for exposed
critical service entrance applications
• Reduces let-through voltages and
rate-of-voltage rise (dv/dt) and helps
provide optimum protection for
electronic equipment
• Extreme reliability and simplified D
design with direct connection from
input to output
• Comprehensive front panel status and
internal diagnostic LEDs
H
SPECIFICATION
14 | nVent.com/ERICO
Part Number SRF363N SRF3125N SRF3250N SRF3500N SRF3800N
Enclosure Rating IP 65 IP 32
Mounting Wall mount
Status Indication Front panel LED
Internal diagnostic primary and secondary protection LEDs
Change-over contact (Form C dry), 250 VAC/30 VDC/5 A, 4 kV isolation
Depth (D) 200 mm 300 mm
Height (H) 500 mm 800 mm 1,000 mm 1,200 mm
Width (W) 400 mm 600 mm 800 mm
Unit Weight 17.7 kg 21.6 kg 41.7 kg 76.6 kg 97.2 kg
Complies With IEC 61643-11 Class I, Class II
®
AS1768 Ratings
Part Number SRF363N SRF3125N SRF3250N SRF3500N SRF3800N
Max Continuous 310 VAC
Operating Voltage
Maximum Surge Current, 130 kA 8/20 μs
L-N 50 kA 10/350 μs
Maximum Surge Current, 130 kA 8/20 μs
N-PE 50 kA 10/350 μs
Voltage Protection Level 200 V 300 V 300 V 300 V 300 V
(L-N) @ 3 kA 8/20 μs @ 3 kA 8/20 μs @ 3 kA 8/20 μs @ 3 kA 8/20 μs @ 3 kA 8/20 μs
250 V 380 V 500 V 550 V 550 V
@ 20 kA 8/20 μs @ 20 kA 8/20 μs @ 20 kA 8/20 μs @ 20 kA 8/20 μs @ 20 kA 8/20 μs
IEC 61643-11 Annex A specifies Max Continuous Operating Voltage (Uc) as 255 VAC.
IEC 61643-11 test procedure limits maximum Impulse Current (Iimp) to 10kA due to internal product safety fusing.
IEC 61643-11 recommends a maximum preferred value for Nominal Discharge Current (In) of 20 kA.
IEC 61643-11 Temporary Overvoltage tests are passed in withstand mode.
Upstream overcurrent protection not exceeding Rated Load Current (IL) shown above must be installed ahead of the surge reduction filter.
nVent.com/ERICO | 15
Our powerful portfolio of brands:
nVent.com/ERICO
WARNING: nVent products shall be installed and used only as indicated in nVent’s product instruction sheets and training materials. Instruction sheets are available at nVent.com/ERICO and from your nVent customer service representative. Improper
installation, misuse, misapplication or other failure to completely follow nVent’s instructions and warnings may cause product malfunction, property damage, serious bodily injury and death and/or void your warranty.
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.
Erico-SB-E1289B-E139LT17WWEN-EN-1805