Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2020.2980585, IEEE
Transactions on Sustainable Energy
1949-3029 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Canberra. Downloaded on April 27,2020 at 14:28:36 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2020.2980585, IEEE
Transactions on Sustainable Energy
Frequency
Order Mechanical
Pump Sub-penstock Fixed Turbine Distribution + + Frequency Power
Variable T Σ Penstock Pump
Unit Speed SM Runner Function Controller Speed
SM Speed Main Shaft
Shaft Penstock Shared Flow
Pump Pressure
Power Order Turbine Flow Turbine
Lower Lower Gate
P T/P Mechanical
Reservoir Reservoir Governor
Gate Ref
Valve
Value
Penstock Turbine
Power
1949-3029 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Canberra. Downloaded on April 27,2020 at 14:28:36 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2020.2980585, IEEE
Transactions on Sustainable Energy
1949-3029 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Canberra. Downloaded on April 27,2020 at 14:28:36 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2020.2980585, IEEE
Transactions on Sustainable Energy
1949-3029 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Canberra. Downloaded on April 27,2020 at 14:28:36 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2020.2980585, IEEE
Transactions on Sustainable Energy
TABLE I
DETAILS FOR IEEE 14-BUS SYSTEM
Parts Location Online/Capacity Dynamic Model
GENROU EXAC1
Gas Turbine 1 Bus 1 swing/615 MW
GAST
GENROU EXAC1
Gas Turbine 2 Bus 2 100/615 MW
GAST
GENSAL IEEET1
Q-PSH Bus 3 -100/150 MW GEWTG EWTGFC
EPCTRB
GEWTG EWTGFC
Wind Turbine Bus 6 100/150 MW
WNDTGE
Synchronous GENROU EXAC1
Bus 8 0/25 MW
Condenser GAST
Bus 2-
Load 259 /259 MW None
6, 9-14
Measurements All Bus None FMETR
(b)
Fig. 8. whole system responses (a) and details two parts power output (b) in
B. Q-PSH System Response under Frequency Event Pumping mode
In this section, the performance of Q-PSH system is validated
and analyzed both in pumping mode and HSC mode. In order adjustable-speed pump not only provides virtual inertial
to find out the improvements of Q-PSH system when it works response, but also participates in the primary frequency
with wind power generation. Two frequency events caused by response. And because of the full-size converter, the pump
the ramp up of wind generation (Bus 6) and the loss of gas responds quickly.
turbine (Bus 2) are applied separately in each case. 2) Frequency Event Case in HSC Mode
1) Frequency Event Case to Q-PSH in Pumping Mode In this HSC mode validation case. The Q-PSH is initialized
As introduced previously, in the pumping mode, the as pump part absorbing 120 MW and turbine part generating 20
adjustable speed pump is in service, whereas the conventional MW. The frequency event caused by the wind turbine (Bus 6)
synchronous generator is operated as a synchronous condenser. and gas turbine (Bus 2) are applied to the system which are
In this validation case, the Q-PSH system is initialized to absorb same as previous pumping mode case. Both the pump and the
100 MW from the system. The wind generation (Bus 6) ramped turbine in the Q-PSH system provide a fast and reliable
up from 100 MW to 125 MW (with ramp-rate limited to 1.25 response after each frequency event which is shown in Fig. 9.
MW/second) at 10 seconds. The second frequency event, a Compare with the response from the pump and the turbine, the
generation loss of gas turbine (Bus 2), occurred at 50 seconds. adjustable-speed pump responds quicker and provide more
After the frequency events, both the adjustable-speed pump and power which is benefitting from the power electronic device.
hydropower generator provide inertial responses shown in Fig. Compared with pumping mode results, in the HSC mode, Q-
8 (b). Especially, after the generation loss of gas turbine, the PSH system provides more frequency response to reach the
system renewable penetration level gets higher from 26.32% to steady-state frequency at a higher level, because of the
44.64%. The Q-PSH still provide reliable and fast frequency participation of the turbine in the primary frequency
support to the system. Owing to the dead band, there is a delay (rebounding) period. However, in the arresting period, since
in the inertial response from pump part. Since hydropower both the pump and the turbine provide inertial response both in
generator is operated as a synchronous condenser, after the the HSC case and the pumping case, there is not any difference
inertial response, its power output goes back to zero. At the at the frequency nadir between these two cases after the
same time, benefitting from primary frequency controller, the generation loss of gas turbine.
1949-3029 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Canberra. Downloaded on April 27,2020 at 14:28:36 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2020.2980585, IEEE
Transactions on Sustainable Energy
(a) Fig. 10. Frequency response and pump part electrical power of Q-PSH under
different proportion gains in the inertia controller
(b)
Fig. 9. whole system responses (a) and details two parts power output (b) in
HSC mode Fig. 11. Frequency response and pump part electrical power of Q-PSH under
different proportion gains in the primary frequency controller
1949-3029 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Canberra. Downloaded on April 27,2020 at 14:28:36 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2020.2980585, IEEE
Transactions on Sustainable Energy
1949-3029 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Canberra. Downloaded on April 27,2020 at 14:28:36 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2020.2980585, IEEE
Transactions on Sustainable Energy
1949-3029 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Canberra. Downloaded on April 27,2020 at 14:28:36 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2020.2980585, IEEE
Transactions on Sustainable Energy
1949-3029 (c) 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of Canberra. Downloaded on April 27,2020 at 14:28:36 UTC from IEEE Xplore. Restrictions apply.