Professional Documents
Culture Documents
11. Insulation Screen (Metal Part) Single Layer stranded Cu. Single Layer stranded Cu.
12. Metallic Screen withstand earth
25 KA for 1 sec. 25 KA for 1 sec.
fault current without damage
Single Layer of Single Layer of
13. Armour material
non-magnetic wire non-magnetic wire
PVC with pb nepthanate
14. Over Sheath/covering material PVC with pb nepthanate
(Black) (2.7 mm)
15. Maximum conductor
Normal 90oC / short Ckt. 250oC Normal 90oC / short Ckt. 250oC
temperature
16. Packing Length per Drum (500 m ± 10%) / drum (500 m ± 10%) / drum
17. Drum Material Non-returnable steel drum Non-returnable steel drum
Rated voltage, conductor size,
Manufacturer’s name, year of
18. Embossed every 1 meter length Agreed
manufacturer. Purchaser’s name
RURAL ELECTRIFICATION BOARD
Item
Description Standards
No.
1Cx400 sq. mm
XLPE Insulated, Design and testing shall be in accordance to the
1.
Single core, Armoured, IEC 60502-2, IEC 60228
33 kV underground Cable