Professional Documents
Culture Documents
USE OF TEMPORARY
ELECTRICAL INSTALLATIONS
Electrical installations are often required to be designed and erected for use for short
periods of time ranging from a few hours to few months and are connected to supply
source in open ground. This is particularly true of construction sites where green field
projects are undertaken. Such installations are generally unprotected from
environmental hazards as compared to installations in the buildings.
The major risks in the use of power in such installation arise from short circuit resulting
in fire accidents and exposure to live wire resulting in shock. It is therefore imperative to
lay down the necessary precautions to be observed for such installations from the point
of view of safety.
Whatever may be the type of installation, the broad principles of precaution are the
same, the object being to ensure the safety of personnel and equipment.
Electric Shock: Shock occurs when the body becomes part of the electric circuit. The
current must enter the body at one point and leave at another. Shock may occur in one
of the three ways:
The major risks in the use of power in such installation arise from short circuit resulting
in fire accidents and exposure to live wire resulting in shock. It is therefore imperative to
lay down the necessary precautions to be observed for such installations from the point
of view of safety.
Electricity Rules have been covered in Eleven chapters in all. Chapters IV for general
safety requirements and Chapter V cover the general rules applicable to all class of
installation .Chapter VI covers the rules applicable to low and medium voltage
installations supply and use while chapter VII covers the rules applicable to high and
extra high voltage installations.
Chapter VIII deals with the provision of rules applicable to over head lines and
underground cables. Chapter X deals with the provision of rules applicable to mines
and oilfield
CEA Regulations
1.Construction Standards
II) Central Electricity Authority ( Measures relating to Safety and Electricity Supply)
Regulations, 2010
3. Connectivity Standards
I )Technical standard for Connectivity to the Grid ( Amendment) Regulation, 2013 New
II) Technical Standards for Connectivity of the Distributed Generation Resources
4. Operation Standards
5. Metering Regulations
Substation
In case the loads required for the temporary installations are large and power supply
authority has no network in the vicinity of the temporary installation that could be utilized
then it would be necessary to establish a temporary substation where the switch and
transformer can be installed. The substation site shall be so selected that it is as close
to the load center as possible.
The power supply authority’s line should be brought up to the substation in a separate
enclosure. If overhead line is laid up to the temporary substation, then the ‘supporting
poles, conductors, materials of the line, insulation and the method of stringing the
conductors and the mechanical strength of the line as a whole shall coform to the
relevant provisions of IS : 5613 (Part 1/ Sec.1)-1970 and IS:5613 (Part 1/ Sec2)-1971.
Power Distribution
At the origin of each installation a unit containing the main control gear and principal
protective device shall be provided. The main switch shall be installed in an enclosure
or a wooden cupboard and as close to the metering point as possible
Means of emergency switching shall be provided on the supply to all current using
equipment on which it may be necessary to disconnect all live conductors in order to
remove a hazard. The enclosure or cupboard in which the main-switch is installed shall
be such that the equipment within shall be unaffected by the environmental conditions.
The main switch on the installation shall be connected to the point of supply by means
of an armoured cable and termination of this cable shall adequately protected from rain
water.
The main switches shall be located at a height not exceeding 1.5 m so as to accessible
in emergencies.
The cable shall be laid either underground or supported in the air. Precautions shall be
taken to ensure that this cable when laid underground is done so with the same
meticulous care as is done for permanent installation. In case the cable passes
underneath the passages, it shall be laid in whole or split pipes. When laid overground,
the cables shall either be cleated with saddles of proper size along the walls of a
permanent structure if available or alternatively, it shall be supported on rigid poles. The
height of the cable shall not be less than 2m when run inside the compound and atleast
5m when run along or across the road. Crossing of the road shall preferably be avoided.
An independent earthing shall be established inside the installation premises. In case
overhead wires are used in the installation they should conform to the relevant Indian
Standards.
In selecting the equipment and cables, the rating shall be decided taking the
environmental conditions into account. The supply intake point shall be placed outside
the periphery of area which is accessible to the general public.
Control of Circuits
A device shall be provided on the incoming cable to each supply unit and each
distribution unit for switching and isolating. With this type of arrangement it shall be
possible to switch off the supply at the intake point or at the distribution point.
The main switch shall be adequately protected from ingress of water. The incoming and
outgoing cables/wires of the main switch shall be firmly supported so that cable and
The main switch shall be installed on a firm and vertical surface, which can withstand
the mechanical vibration created at the installation site as well as the wind pressure at
the location.
There shall be adequate ventilation in the room where main switches are installed and
there shall be operational space around the switch in accordance with good practice.
The switch room shall be accessible at any time of the day or night to authorized
persons.
Sub Circuit
The switches shall be mounted on a firm support and shall be at a height between 1m
and 2m from the floor level. The sub-circuit switch shall be so spaced that there shallbe
a minimum clear distance of 60mm., between the switches for ease of operation
The outgoing wires from the subcircuit switches inside the enclosure shall be cleated
firmly on wooden battens or taken through conduits which are fixed by means of
saddles to the masonry wall or wooden partition wall. The lead wires connected to the
sub-circuits switches shall be suitably supported on wall with clips and shall not be left
hanging. Spans which are more than 2 m shall have guide wire support.
A broken bulb of lamps in series circuit is a risk and therefore series lamps shall
not strung or hug at heights less than 3m. A defective series lamp shall not be allowed
to remain in its position and shall be immediately removed.
Earthing
The installation as a whole shall be protected against overload, short-circuit , and earth
leakage by suitable protective devices. Temporary supply is generally used at public
places and for public functions and therefore, extreme care shall be taken to ensure that
there is no risk of any type of hazard either from electrical shock or fire.
No flammable material shall be stored near the service intake point or the operational
area of electrical equipment or appliances. For large public functions, exhibitions, etc,
suitable fire extinguishers shall be kept at the supply intake point and near the main
switch of the installation.
In construction sites, protection of persons against indirect contact shall be assured by
automatic disconnection of supply appropriate to the system earthing. Socket outlet
shall either be protected by residual current devices having operating current not
exceeding 30 mA or be supplied by safety extra- low voltage or electrical separation of
circuit each socket outlet being supplied by a separate transformer.
1) Red
2) Blue
3) Yellow
Generally live wires are made of copper material because it is the best conductor of
electricity.
Earth resistance in the circuit should be as less as possible generally 0-2 ohms.
Bare wire loose connection in supply Plug can lead to Electric shocks, Electric sparks
causing fire as well as tripping hazard therefore wires should be properly insulated.
The best fire extinguishers used for extinguishing electrical fire are Carbondioxide or
Dry Chemical Powder type conforming to relevant Indian standards shall be provided as
per site requirement.
To prevent from Electrical Shock type of Hand Gloves which should be worn at the time
of work is rubber gloves.
Also while working on sites ELCB i.e Earth leakage circuit breaker should be used so
that if any short circuit the ELCB trips the supply to to the equipments thus preventing
damage to the equipment and also shock .
Rules 58 : Clearance above ground of the lowest conductor above overhead lines
-
(2 ) No conductor of an overhead line, including service lines , erected along any street
shall at any part thereof be at a height less than –
(a) For lines of voltage not exceeding 650 Volts : 5.5 metres
(3) No conductor of in overhead line including service lines, erected elsewhere than
along or across any street shall be at a height less than-
(a) For lines of voltage upto and including11,000 volts, if bare : 4.6 metres
(4 ) For lines of voltage exceeding 33kV the clearance above ground shall not be less
than 5.2 metres plus 0.3 metre for every 33,000 volts or part thereof by which the
voltage of the line exceeds 33,000 volts.
Provided that the minimum clearance along or across any street shall not be less
than 6.1 metres
(1) No conductor of an overhead line crossing a tramway or trolley bus route using
trolley wires shall have less than the following clearances above any trolley wire : -
Provided that where an insulated conductor suspended from a bearer wire crosses a
trolley wire the minimum clearance for such insulated conductor shall be 0.6 metre.
(2) Where an overhead line of voltage not exceeding 650 volts passes above or
adjacent to or terminates on any building, the following minimum clearances from any
accessible point, on the basis of maximum sag, shall be observed:
(a ) For any flat roof, open balcony, verandah roof and lean-to-roof :
i) When the line passes above the building a vertical clearance of 2.5 metres from the
highest point, and
ii) When the line passes adjacent to the building a horizontal clearance of 1.2 metres
(1) An overhead line shall not cross over an existing building as far as possible and no
building shall be constructed under an existing overhead line.
(2) Where an overhead line of voltage, exceeding 650 V passes above or adjacent to
any building or part of a building I shall have on the basis maximum sag a vertical
clearance above the highest part of building immediately under such line, of not less
than –
(i) For lines of voltage exceeding 650 Volts upto : 3.7 metres
And including 33000 Volts
ii) For lines of voltages exceeding 33 kV : 3.7 metres plus 0.30
metres for every additional
33000 Volts or part thereof
(3) The horizontal clearance between the nearest conductor and any part of such
building shall, on the basis of maximum deflection due to wind pressure, be not less
than
Marking: Access to dangerous electrical equipment should have warning signs. The
following general shock protection methods can also be employed:
• Insulation of parts routinely or accidentally touched by persons(knobs, dials handles
etc)
• Rheostat and potentiometer control shafts can be coupled to non-conductive rods
and knobs.
• Rubber mats must be provided near switchboards.
• Rubber gloves and non-conductive shoes must be worn while working.
GFCI interrupts current to load when current to ground exceeds some predetermined
value, which is less than that required to operate the over-current protective device of
the circuit. Circuit breakers and fuses will open under comparatively large current, which
is fatal to man.
***