Professional Documents
Culture Documents
ComPAC
Chiller unit with screw compressor
Manual for ComPAC with screw compressor
The chiller unit can be configured with various types of equipment depending on its function and
requirements.
Some of the equipment may be described in this manual even though it is not featured on your
particular unit.
Please note that this manual does not include instructions for the:
Compressor
Unisab III controller
You can find the compressor number and the equipment configured on your unit below.
Compressor type
Designation
Compressor no.
Refrigerant
R717
Oil type
PAO68 Other _____________
Level control
Mechanical float valve Electronic valve
Approval
PED (2014/68/EU) Other _____________
Drive type
Fixed speed Variable speed
IP23 IP55
Motor
Ex-execution
Both compressor and unit are safeguarded
Condenser
Float housing
Evaporator
Liquid separator
Oil separator
Oil cooler
Safety valve:
Data for calculation of
Receiver
downstream line accord-
ing to EN 13136
Economiser
Desuperheater
Subcooler
Other
Back-pressure dependent
Back-pressure independent
1. Introduction ..................................................................................... 8
1.1 Introduction to the manual ..................................................... 8
1.1.1 Amendments to the manual............................................. 9
1.1.2 Definition of safety precautions used in this
manual ............................................................................ 10
1.1.3 Requirements for competent persons ........................... 10
2. Safety ............................................................................................... 11
2.1 Areas of application ............................................................... 11
2.1.1 Application ...................................................................... 11
2.1.2 Application of combustion engines ................................ 11
2.2 Identification ......................................................................... 12
2.2.1 Identification of equipment............................................ 12
2.2.2 Unit/pipe system name plate ......................................... 13
2.2.3 Compressor name plates ............................................... 15
2.2.4 Vessel name plate .......................................................... 17
2.2.5 Signs .............................................................................. 18
2.3 Safety precautions ................................................................ 19
2.3.1 General precautions ....................................................... 19
2.3.2 During operation ............................................................ 19
2.3.3 Cooling water systems ................................................... 20
2.3.4 Cooling media ................................................................. 20
2.3.5 Safety during maintenance and service ........................ 20
2.3.6 Power supply .................................................................. 20
2.3.7 Lubricating oils ............................................................... 21
2.3.8 Refrigerants .................................................................... 21
2.3.9 Purging a refrigeration plant .......................................... 21
2.3.10 F-gas regulation (fluorinated greenhouse
gases) ............................................................................. 22
2.3.11 First aid for accidents with ammonia ............................. 24
2.3.12 Protecting the operator as well as the
environment ................................................................... 25
2.3.13 Emergency stop .............................................................. 26
8. Appendices ..................................................................................... 52
8.1 Spare parts list for HP float valve .......................................... 52
8.2 Spare parts list for CVUA 1201 oil recovery pot ................... 53
8.3 Declaration of conformity ...................................................... 54
Index ................................................................................................ 55
1. Introduction
2020.03 Version 4
• The copy of the declaration of conformity (Unit) is now only contained in the printed
manual delivered with the unit and the pdf version uploaded with the order specific
documentation.
• Various minor changes.
2018.10 Version 3
2018.01 Version 2
• Name plates with EurAsian Conformity mark (EAC) have been added.
• ‘Requirements for competent persons’ section has been added.
• ‘F-gas regulation’ section has been updated.
• Updated version of declaration of conformity for unit.
• And more.
The original version of this manual is the English language version. If there are any discrepancies
or conflicts between the English and any other version that has been translated into another lan-
guage, the English version will prevail.
Danger!
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious
injury.
Warning!
Indicates a potentially hazardous situation or practice which, if not avoided, will result in death or
serious injury.
Caution!
Indicates a potentially hazardous situation or practice which, if not avoided, will result in damage
to equipment and/or minor injury.
Note: Indicates an operating procedure, practice, etc., or portion thereof, which is essential to
highlight.
2. Safety
Warning!
Johnson Controls Denmark is not liable for injuries to personnel or damage to equipment resulting
from using the equipment for other purposes than the ones stated above.
2.2 Identification
2.2.1 Identification of equipment
All equipment from Johnson Controls Denmark can be identified by one or several name plates
positioned as illustrated in the following drawing:
Johnson Controls Denmark ApS 2516-342 Johnson Controls Denmark ApS 2516-343
Christian X's Vej 201 Christian X's Vej 201
8270 Højbjerg, Denmark 8270 Højbjerg, Denmark
www.sabroe.com www.sabroe.com
Fig. 2: Name plate for standard unit Fig. 3: Name plate for ATEX unit
The unit name plate is positioned on the frame and contains this information:
Note: Main supply voltage can be found on the motor and/or electrical panel name plate.
2516-345
No Year No Year
Fig. 5: Name plate for standard compressor Fig. 6: Name plate for ATEX compressor
No Year
Compressor Type Speed rpm
Refrigerant
Swept Volume cfm
Pressure system LP side HP side
Allowable pressure Max. psig
Test pressure psig
Fig. 7: Name plate for compressor with EurAsian Con- Fig. 8: Name plate for compressor to the USA
formity mark (EAC)
The compressor name plate is positioned on the compressor and contains this information:
Nº cocyдa
Vessel No
Mасса пустого cocyдa кг год
Empty weight Kg Year
Тип/Type
Пpoeкт пo cтaндapтy
Design code
Утвepждeн пoд N° / Кат.
Approval No /Cat.
The pressure vessel name plate is positioned on the shell of the vessel and contains this
information:
Note: Depending on the supplier of the pressure vessel/heat exchanger, the layout and content
of the vessel name plate may differ from the Sabroe name plate above.
2.2.5 Signs
All signs which may be found on your equipment are shown below. The number of signs, however,
may vary from one product to another.
High surface
High voltage/ The compressor may be
Risk of electric shock temperature
High pressure top-heavy
(about 70°C)
Compressor blocks and units are usu- The magnetic field on the rotor may The VSD contains capacitors capable
ally delivered without refrigerant and affect pacemakers. The motor rotor of storing electrical energy, meaning
oil. To protect the compressors against contains a powerful magnetic field. that there is a risk of electric shock
internal corrosion, they are delivered This field may affect digital devices within 15 minutes after the drive has
evacuated of all atmospheric air and such as watches and mobile phones. been turned off.
charged with dry Nitrogen (N2) to an Assembly or maintenance of the rotor
overpressure of 0.5 bar [7.3 PSI]. must not be carried out by people with
In such cases, a yellow sign is affixed pacemakers or any other implanted
to a visible spot on the compressor. medical electronic device.
Note: These instructions only provide general information. The owner of the refrigeration plant is
responsible for ensuring that all codes, regulations and industry standards are complied with.
Warning!
All safety features, disengagement and interlocks must be in place and function correctly before
the equipment is put into operation. Never by-pass or wire around any safety device.
Ventilation
Before operating the unit always check, where relevant, the function of the ventilation system
and refrigerant detectors used in the area where the compressor/unit is located (machine room).
Rotating parts
Warning!
Safety guards, shields, barriers, covers and protective devices must not be removed while the
compressor/unit is operating.
Pressure
Danger!
A compressor/unit comprises a pressurised system. Never loosen threaded joints while the sys-
tem is under pressure, and never open pressurised system parts.
Note: Whenever a relief valve/safety valve has been activated, we recommend recalibrating it.
This must be carried out by competent personnel only. See also EN 378 and existing national
legislation.
Warning!
The recirculation water system may contain chemicals or biological contaminants, including le-
gionella, which can be harmful if inhaled or ingested. Water systems should only be operated with
an effective biological treatment programme.
Disposal of brine
The brine must be collected in suitable containers clearly marked with the contents and sent to an
approved hazardous waste disposal site. However, in some cases, if approved by the local author-
ities, brine can be discharged into the sewage system.
Danger!
• The voltage used in the drive can cause severe electric shock and/or burns and may be le-
thal. Extreme care must be taken at all times when working with or close to the drive. Spe-
cific warnings are given wherever relevant in this manual.
• The drive line is connected to voltage. Be aware of live circuits.
• Pay close attention to the electrical installation and system maintenance to avoid hazards
both during normal operation or in the event of equipment malfunctioning.
• When the cause of the shutdown has been removed, the motor may restart. This can be
dangerous for machines and installations, and it is therefore important that the user takes
adequate precautions against restarting if the motor makes an unscheduled stop.
• System maintenance must always be carried out by personnel who have the necessary
training and experience.
See the SABROE oil recommendation for the recommended type of oil.
Warning!
When charging oil, follow the safety instructions given by the oil supplier (MSDS: Material Safety
Data Sheet). Always avoid direct contact with the oil as this may cause skin allergies. Always use
protective equipment, goggles and gloves, when charging oil.
When changing oil on the compressor or draining oil from the vessel of the refrigeration plant, al-
ways collect the used oil in containers marked “waste oil,” and send them to an approved hazard-
ous waste disposal site. It is not recommended to reuse oil.
2.3.8 Refrigerants
Be very careful when dealing with refrigerants. For safe handling, please refer to the safety/data
sheets delivered by the refrigerant supplier.
Warning!
Be aware that large amounts of leaking (or released) refrigerant entail a risk of asphyxiation. If in
direct contact with leaking liquid refrigerant, there is a high risk of injuries caused by frostbite.
Note: The occurrence of air is usually an indication of poor maintenance or lack of thoroughness
at installation.
Note: Ammonia systems should be purged on a regular basis to avoid atmospheric air and other
non-condensable gases.
Bans on GWP
R404A/R507A and other refrigerants with a GWP over 2500 are banned from new stationary sys-
tems after 2020. Existing systems can be serviced with reclaimed refrigerant until 2030, provided
that proper-quality refrigerant is available. Read the local regulations.
Labelling
The unit must be fitted with a label (name plate). Refrigerant type, charge in kg and CO2Equiva-
lent (CO2eq) must be stated on the plate.
Leakage test
It is the operator’s responsibility to ensure that the unit is checked for leakages by a competent
person. For units charged with fluorinated greenhouse gases, the following conditions apply de-
pending on type of plant and amount of charge:
Recovery of refrigerant
Operators are responsible for putting in place arrangements for the proper recovery of fluorinated
greenhouse gases by competent personnel to ensure recycling, reclamation or destruction.
Certification of personnel
According to directive 303/2008, it is mandatory for the member states to establish certification
and training programs for personnel involved in leakage inspections and the recovery, recycling,
reclamation and destruction of fluorinated gases.
Record keeping
For all units containing fluorinated greenhouse gases in quantities of more than 5 tonnes of
CO2eq, records must be kept indicating the quantity and type of product, quantities added for re-
charges and the quantity recovered during servicing, maintenance and final disposal. Other rele-
vant information is also requested, such as identification of the servicing company or technician,
as well as dates and results of the checks.
For further information, please see the F-gas regulation in full.
General
Ammonia is not a cumulative poison. It has a distinctive, pungent odour that even at very low,
harmless concentrations is detectable by most people.
As ammonia is self-alarming, it serves as its own warning agent so that no person stays voluntar-
ily in hazardous concentrations. Since ammonia is lighter than air, adequate ventilation is the best
means of preventing accumulation.
Experience has shown that ammonia is extremely hard to ignite and under normal conditions a
very stable compound. At extremely high, though limited concentrations, ammonia can form
ignitable mixtures with air and oxygen and should be treated with respect.
Emergency stop
Emergency stop
For resetting and further information, please see the Unisab III manual.
Pos. Pos.
Component Component
no. no.
1 Motor 14 Electrical panel
2 Compressor 15 VSD panel
3 Evaporator/liquid separator 16 Oil separator
4 Outlet evaporator 17 Oil filter
5 Inlet evaporator 18 Oil cooler
6 Condenser 19 High level alarm
7 Outlet condenser 20 Heat recovery inlet (optional)
8 Inlet condenser 21 Heat recovery outlet (optional)
9 Expansion valve 22 R717 charge valve
10 Oil recovery system 23 Condenser manifold (optional)
11 Safety valve 24 Evaporator manifold (optional)
12 Oil reservoir 25 Oil recovery system (from evaporator)
13 Unisab III controller (built into the electrical panel - optional)
Note: Changes in factory settings must only be carried out by competent personnel.
3.2.3 Evaporator
The evaporator is a fully welded plate heat exchanger where plates are welded together into cas-
settes. R717 evaporates between the two welded plates which make up the cassettes and water/
brine is cooled in the channels inside the cassettes. The R717 droplets are separated from the va-
pour in the separator room above the plates.
The evaporator has one or two sets of brine connections depending on size and operating
conditions.
A sight glass is mounted at the end cover.
Note: The liquid level must never be visible in the inspection glass. See subsection 6.3 R717
charge and the P&I diagram for correct charge.
3.2.4 Condenser
The ComPAC is equipped with a water-cooled condenser. The condenser is a fully welded plate
heat exchanger where plates are welded together into cassettes.
R717 condenses between the welded plates which make up the cassettes and cooling water circu-
lates in the channels between the cassettes.
The liquid expansion system is based on a high pressure regulating system which is built into the
bottom of the condenser.
3.2.5 Receiver
The ComPAC (external condenser) is equipped with a receiver. The purpose of the receiver is to
accumulate the liquid coming from the condenser. The receiver has the following connections and
sight glasses, all located on the flat end cover:
The receiver must never be filled completely with liquid. The level can always be checked in the
three sight glasses.
Warning!
The level must never rise above the middle of the upper sight glass.
To ensure correct operation of the chiller, the bottom sight glass should always be minimum half
full. This will prevent gas from entering the liquid line.
3 4 1 2
Note: The valve at the bottom of the cover, Fig. 14, pos. 4, is used for liquid draining (R717).
During air purging the air purge valve should be connected to an open vessel containing water via
a refrigerant hose.
The air will leave the water as bubbles whereas the R717 gas will be absorbed by the water.
Note: R717 containing water must be disposed of in a correct and proper way, see chapter 2.3.9
Purging a refrigeration plant.
When the oil level in the recovery pot, Fig. 16, is high, the float switch, pos. 1, is activated. The
switch turns on the solenoid valve in the oil recovery system. Incoming discharge gas pushes
down the piston, pos. 3, which blocks the oil drain inlet port. Discharge gas is led into the oil reser-
voir through the small nozzle, pos. 2. The rising pressure forces the oil back into the suction side
of the compressor.
To ensure proper functioning, a timer delays the off-signal from the float switch for a few seconds.
Note: As shown in Fig. 16, the float ball must be positioned with NO facing upwards.
For further information about the oil recovery pot, see chapter 8. Appendices.
1 2
Discharge gas
DN25
NO Oil / R-717
CN
Oil
Note: The liquid level must never be visible in the inspection glass.
4. Installation information
4.3.3 Foundation
To obtain the desired vibration damping, the concrete foundation must have the necessary bear-
ing strength and be as plane as possible. Always collect weight information of the chiller unit be-
fore projecting the concrete foundation.
Lock nut
Note: Rapid temperature variations in the secondary system can damage the chiller. It is recom-
mended to keep temperature changes below 1 K/min. Install a buffer tank or balancing tank to
avoid great variations in load and temperature. Avoid fluctuating pressure and temperature as
this can damage the heat exchangers.
Note: In order to obtain the correct mixture, it is recommended to premix secondary refrigerants
(glycol or brine) and to check it subsequently.
5. Operating instructions
Qualification requirements
Before operating a chiller unit, all personnel must have studied the unit manuals carefully.
The operator must be confident operating a Unisab III controller.
Prior to start-up and running of the chiller unit, the pre-start check must be accomplished, see
subsection 5.2.1 Pre-start check. Having performed the checkpoints in the pre-start check, it is
important that there is a cooling requirement.
5.2 Pre-start
5.2.1 Pre-start check
Before starting the chiller unit, the operator must make sure that installation in terms of mechani-
cal work (refrigeration system and piping), electrical work and installation of safety equipment is
completed according to the installation information.
Make sure that all necessary documents are available, including operating manuals, machine
card, logbooks, etc. and/or other documentation required according to local rules and/or EN 378.
Check the following before starting the chiller:
1. Check that installation is performed in accordance with the recommendations.
2. Turn on the power supply and the control voltage.
3. Make sure that the heating element in the oil reservoir has been activated for six to eight
hours.
4. Check the oil level in the oil reservoir. The oil level should be visible up to the middle of the
sight glass.
5. Check that all valves are positioned as stated in Table 1: Valve positions during operation,
ComPAC.
6. Check the position of the emergency stop button.
7. Check the position of all external switches, if any.
8. Unisab III must display: READY as running state.
9. Check that auxiliary equipment (condenser, cooling water, pumps, etc.) is ready/in
operation.
5.3 Starting
5.3.1 Starting procedures
Starting and stopping can only be carried out from Unisab III. The operator must always make
sure that the appropriate external starting conditions exist before start-up.
Top bar
Content area
Info bar
F-key area
Note: A long stop requires a long-term stop procedure as described in the following.
Checklist
Along with this Operating manual we have provided a Checklist, as shown in Fig. 20, which will
serve as a help to the service engineer and must be filled in during commissioning and
start-up.
Keep the filled-in checklist, and send a copy to SABROE Factory as documentation that the unit
has been installed and commissioned correctly. The checklist will be required in case of a warranty
issue.
Checklist Checklist
Checklist for commissioning of compressor, chiller and heat pump units Start-up log: Monitoring of operation at start-up
Compressor serial no.: Date: Name: Compressor serial no.: Date: Name:
Read and understand all Sabroe manuals (compressor, Unisab, chiller, etc.) Operation time [hours]
Read and understand manuals for third party components (electric motors, valves,
Suction pressure [°C/R]
etc.)
Check unit installation and vibration damper adjustment Suction temperature [°C]
Carry out functional testing of safety equipment Superheating, suction gas [K]
Read the opening pressures on all safety valves, and check that they are correct Discharge pressure [°C/R]
Check Unisab set-up (see list of settings), and check VSD set-up, as applicable Oil pressure, compressor [bar]
Check that the heating element in the oil has been on for 6-8 hours before start Oil temperature [°C]
Take a sample of the primary refrigerant (must be free from water, air, etc.) Oil temperature, separator [°C]
Check that the motor rotation direction is correct Oil collection from shaft seal [ml]
Check that the coupling is aligned Oil level [0, 1/4, 1/2, 3/4, Full]
Check that the plant is not leaking Motor 1/1 load [amp.]
Check that the valves are in the correct position for operation Capacity load [%]
Check that the capacity regulation system is working correctly Vibrations (0-100% capacity) [OK/not OK]
Check the refrigerant charge (at full load) Brine temperature, outlet - Evaporator [°C]
Check the unit for vibrations Brine temperature, outlet - Condenser [°C]
Check the unit for vibrations using VibraGuard (variable speed) Refrigerant charge [Kg]
Make a start-up log at full load (on the back of this form) Please fill in this form, file it, and send a copy to: Noreply.Sabroe@jci.com.
Take out a representative lubricating oil sample after about 1 hour of operation, and
save it for minimum 1 year from commissioning date
This form is also available on the Sabroe SUPPORT site on www.sabroe.com.
Go to ‘Document search’ and search for Checklist .
Fig. 20: The checklist which MUST be filled in during commissioning and start-up
Caution!
Wire connections to the motor and VSD must not be touched immediately after the chiller is pow-
ered down as the capacitors in the VSD may still be charged. Read the warning label on the VSD.
5.6.2 Troubleshooting
Too high condensing pressure
Cause Solution
Air or non-condensable gases in the system Remove air from the condenser.
A 1°K lower condensing temperature results in a 1% higher cooling performance and 3% lower
power consumption.
Too low evaporating temperature
Cause Solution
Cause Solution
1. Check the function and position of the oil float switch (see de-
scription of oil recovery pot). When the float is up, the switch
must be closed (ON) and vice versa.
2. Check that the piston in the oil recovery pot is able to move
Defect oil return/ smoothly.
oil recovery system 3. Check all solenoid valves and filters.
4. Check timers in Unisab III.
See Unisab III settings list for timer settings.
5. Check if the oil separator is filled with oil. If so, adjust the
timers in Unisab III. Increase the solenoid valve “ON” time.
In the period after start-up and at low-load operation, the oil recovery system will return more oil
to the compressor than during full load.
At part-load operation, the oil will settle easier because of less boiling in the evaporator.
Drop in oil temperature
Cause Solution
Wet suction gas due to quick changes in Adjust settings for load/unload compressor capacity
compressor capacity in Unisab III.
Reduce water flow or temperature to compressor
Too much compressor cooling cooling. See compressor manual for more
information.
6. Maintenance instructions
Note: The liquid level must never be visible in the inspection glass.
The quality of the refrigerant must be appropriate for refrigeration applications; for details, see:
TI2015-01 Ammonia quality.
7. Final disposal
Danger!
Before dismantling the plant, read the safety precautions carefully.
Danger!
Be very careful when using cutting tools, such as angle grinders or flame cutters, during the dis-
mantling process, as pipes and the like contain oil residue and refrigerant, which may be toxic
and/or flammable.
8. Appendices
2 3 1
8.2 Spare parts list for CVUA 1201 oil recovery pot
1 8
2 6
3
7
11
DN25
NO
CN 10
12 9
5
NO: 3247--128
A
Air purge valve ........................................................................................................................... 32
Amendments to the manual ......................................................................................................... 9
Ammonia accidents - first aid ..................................................................................................... 24
Application ................................................................................................................................. 11
Automatic oil recovery ............................................................................................................... 33
B
Batteries .................................................................................................................................... 51
Brine .......................................................................................................................................... 38
C
Cleaning in place ........................................................................................................................ 38
Combustion engines - application .............................................................................................. 11
Competent persons - requirements............................................................................................ 10
Compressor................................................................................................................................ 29
Compressor name plates............................................................................................................ 15
Condenser.................................................................................................................................. 29
Control system ........................................................................................................................... 29
Cooling media ............................................................................................................................ 20
Cooling water systems ............................................................................................................... 20
CVUA 1201 oil recovery pot ........................................................................................................ 53
D
Declaration of conformity ........................................................................................................... 54
Detector - R717.......................................................................................................................... 38
E
Emergency stop ......................................................................................................................... 26
Evaporator ................................................................................................................................. 29
F
F-gas regulation ......................................................................................................................... 22
Final disposal.............................................................................................................................. 51
First aid for ammonia accidents.................................................................................................. 24
Foundation ................................................................................................................................. 37
G
Greenhouse gases...................................................................................................................... 22
H
HP float valve ............................................................................................................................. 52
HP regulating system ................................................................................................................. 31
L
Logbook ..................................................................................................................................... 44
Lubricating oil............................................................................................................................. 21
O
Oil types ..................................................................................................................................... 21
P
Power supply .............................................................................................................................. 20
Pre-start check........................................................................................................................... 40
Protecting the operator .............................................................................................................. 25
Purging ...................................................................................................................................... 21
R
R717 charge............................................................................................................................... 50
Receiver ..................................................................................................................................... 30
Refrigerants ............................................................................................................................... 21
Restarting .................................................................................................................................. 44
S
Safety during maintenance and service...................................................................................... 20
Safety signs ............................................................................................................................... 18
Selecting lubricating oil .............................................................................................................. 49
Shutting down............................................................................................................................ 46
Sound and noise data ................................................................................................................. 36
Spare parts list ..................................................................................................................... 52–53
Starting procedures ................................................................................................................... 41
Stopping .................................................................................................................................... 46
T
Temperature and flow control..................................................................................................... 38
Troubleshooting ......................................................................................................................... 47
U
Unit/pipe system name plate ..................................................................................................... 13
V
Vessel name plate ...................................................................................................................... 17
Vibration dampers...................................................................................................................... 37
VSD (variable speed drive)......................................................................................................... 37
W
Water ......................................................................................................................................... 38
We hereby declare that our products within the scope of eco-design, implemented according to regulation
No 2015/1095 for low (-25°C) and medium (-8°C) temperatures and No 2016/2281 for high temperatures
(+7°C), are in compliance. The harmonised standards EN 14511 series and EN 14825 have been used
for testing and calculation. Value tolerances for selection tools comply with EN 12900.
Preconditions:
a EER calculations are defined as COP (Coefficient Of Performance) in our nomenclature for
evaporator calculation in COMP1 sales tools. Capacity control is variable.
b SEPR calculations are made by spreadsheet tool version 1.5.3 date 2013-09-01.
Diagram lines drawn as straight lines between legal condition points and product points.
See data and calculation on page 2. Degradation coefficient Cc = 0.9 for part load.
Specific EER, SEPR and η,SC values are included in the operating manual.
c Screw compressors without performance-increasing system (economizer).
d Secondary refrigerant ethylene glycol -25°C and -8°C. Secondary refrigerant water at +7°C.
e Superheat 0°K and subcooling approx. 1°K.
f Suction and discharge pressure drop included.
g Electric power for liquid pumps included according to EN 14511-3, Annex G.4.
h GWP<150 allows 10% lower value included for low – and medium temperatures.
i Chiller includes evaporator (Water/brine) and condenser (Water/brine or air).
j Examples of calculations are shown with selected models representing the respective model
program. All other conditions or types/models must be calculated in COMP1.
Højbjerg, Denmark
Place By written authority
Page 1 of 2 TPH/20-1-2021
Letter of compliance for ECO-design, Process & Comfort Chiller
Directive 2009/125/EC
Data:
Process Chiller, Reciprocating water/brine cooled
High Medium High Medium
<400kW ChillPAC28V-A 229 kW <300kW ChillPAC28V-C 113 kW >400kW ChillPAC 112LV-A 1061 kW >300kW ChillPAC 12LV-C 529 kW
Sabroe unit Legal limit Sabroe unit Legal limit Sabroe unit Legal limit Sabroe unit Legal limit
SEPR SEPR SEPR SEPR
9,30 7,0 5,05 2,96 9,40 8,0 5,00 3,93
Conditions Conditions Conditions Conditions
Condenser Evaporator Condenser Evaporator Condenser Evaporator Condenser Evaporator
Inlet/outlet Inlet/outlet Inlet/outlet Inlet/outlet Inlet/outlet Inlet/outlet Inlet/outlet Inlet/outlet
30/35 +12/+7 30/35 -2/-8 30/35 +12/+7 30/35 -2/-8
Process Chiller, Screw water/brine cooled
High Medium High Medium
<1500kW ComPAC 151LV-A 932 kW >300kW ComPAC 151LV-A 514 kW <1500kW ComPAC 193LV-A 1455 kW >300kW ComPAC 193LV-C 794 kW
SEPR Sabroe unit Legal limit SEPR Sabroe unit Legal limit SEPR Sabroe unit Legal limit SEPR Sabroe unit Legal limit
8,02 8,0 4,60 3,93 9,77 8,0 4,72 3,93
Conditions Conditions Conditions Conditions
Condenser Evaporator Condenser Evaporator Condenser Evaporator Condenser Evaporator
Inlet/outlet Inlet/outlet Inlet/outlet Inlet/outlet Inlet/outlet Inlet/outlet Inlet/outlet Inlet/outlet
30/35 +12/+7 30/35 -2/-8 30/35 +12/+7 30/35 -2/-8
Process Chiller water/brine evaporator, Air Cooled condenser
High Medium
<400kW SABlight A400-1 392 kW <300kW A400-1EG 237
SEPR Sabroe unit Legal limit SEPR Sabroe unit Legal limit
5,02 5,0 3,73 2,32
Conditions Conditions
Evaporator Evaporator
Condenser Inlet Condenser Inlet
Inlet/outlet Inlet/outlet
35 +12/+7 35 -2/-8