LV SWG Ansi Arc
LV SWG Ansi Arc
85kA Magnum AR
Arc Resistant Low Voltage Switchgear
Test Certification
IEEE C37.20.7 - 2007 Type 2B
85 kA for 0.5 sec
Front, Rear & Side
Eaton Corporation
Electrical Assemblies Division
221 Haywood Rd.
Arden, NC USA 28704
Test Certification 85kA Magnum AR
Arc Resistant Low Voltage Switchgear
Effective July 2009
Type: 85kA Magnum AR Arc Resistant Type 2B (Front, Rear & Sides) per IEEE C37.20.7 - 2007
1. Maximum Voltage: 635 Vac rms 5. Power Frequency Withstand: 2.2 kV RMS
2. Frequency: 60 HZ 6. First peak Prospective Current: 196 kA Peak
3. Fault Withstand: 85 kA RMS 7. Arcing Time: 0.5 sec.
4. Impulse Withstand: NA kV Peak
Tests Performed:
All tests were performed to the procedures specified in IEEE C37.20.7 - 2007 Type 2B
Test Location: Kema Powertest, Chalfont, PA USA
Voltage: 635 Vac
Frequency: 60 HZ
Perspective Peak Current of first Peak: 196 kA Peak
Short Circuit Current: 85 kA RMS
Arcing Time: 0.500 sec.
Compartments: Breaker, Main/Vertical Bus, and Cable
Certification:
The above is a true and correct summary of data obtained from tests performed at: Kema Powertest, Chalfont, PA USA.
The test results demonstrate the capability of the 85kA Magnum AR Low Voltage Switchgear enclosure to meet the requirements of arc
resistant test procedure per IEEE C37.20.7 - 2007 Type 2B, when applied within its ratings.