Magnetic shield insulation of cable support systems

General planning aids

The magnetic field (H) of strength 3 kA/m in a defined experimental setup: without cable support
system on the left, with cable support system on the right. 1 = Field H, 2 = V1 LzuPE

The magnetic shield insulation of V1 is measured in the unshielded Experiment result:


cable support systems is the ratio cable. The same cable is then po- The magnetic shield effect αS of a
in decibels (dB) of an induced sitioned in the centre of a cable cable support system could be
voltage into an unprotected cable support system (once with a cover, clearly proved by the experiments
to the induced voltage into the once without) and subjected to the and the simulation with an FEM
same cable, when this is in a same magnetic field of 3 kA/m. program.
cable support system. Here, the induced voltage V2 is The best result of around 50 dB

04_KTS_Produkteinheitenkatalog_EX_2018 / en / 2018/11/13 10:55:57 10:55:57 (LLExport_02475) / 2018/11/13 10:59:11 10:59:11


measured in the unshielded cable. was achieved with cable support
Experimental structure to determ- The magnetic shield insulation is systems (cable trays) with covers.
ine the magnetic shield insulation calculated from the measured val-
of cable support systems: ues according to the formula: Note:
An unshielded cable (NYM-J 5 x αS = 20 log (V1/V2) dB The shield insulation against elec-
6 mm²) is subjected to an 8/20 trical fields is almost perfect as it
magnetic field with a strength of 3 has a Faraday cage.
kA/m. Here, the induced voltage

Magnetic shield insulation 8/20 dB


Type, cable tray / cable ladder Without cover With cover
RKSM 630 FS 20 50
MKS 630 FS 20 50
MKS 630 FT 20 50
MKSU 630 FS 20 50
MKSU 630 FT 20 50
MKSU 630 VA 20 50
GRM 55/300 FS 15 34
LG 630 NS FT 10 15