Liquid Flow Measurements

5 .7.1 Water (other than condensate) and brine flow rates shall be measured with a liquid flow or
quantity meter that is accurate to within ±0 .5% of the quantity measured. 5 .8 Speed Measuring
Instruments 5 .8 .1 Speed measuring instruments shall be made with a revolution counter,
tachometer, stroboscope, or oscilloscope that is accurate to within ±1 .0% of the reading. 5 .9
Time and Mass Instruments 5 .9 .1 Time interval measurements shall be made with an instrument
that is accurate to within ±0