Electrical Installation

Condition Report
Report No. IPN4/0506770

Client: Manor Primary School

Date: 24/08/2017

Address: Ettingshall Road

Wolverhampton, WV14 9UQ

Electrical Test Midlands t 01922 710014


110B Walsall Road, Cannock, e admin@electricaltestmidlands.com
West Midlands, WS11 OJB www.electricaltestmidlands.com

COMPANY REGISTRATION No. 5126996 V.A.T. No. 851 3359 29


This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


ELECTRICAL INSTALLATION
Contractor's Reference Number CONDITION REPORT
Issued in accordance with British Standard 7671 - Requirements for Electrical Installations by an Approved Contractor or
035056 Conforming Body enrolled with NICEIC, Warwick House,Houghton Hall Park, Houghton Regis,Dunstable,LU5 5ZX

A. DETAILS OF THE CLIENT


Client: Manor Primary School Address: Manor Primary School

Original
Ettingshall Road
Wolverhampton

Postcode: WV14 9UQ

B. PURPOSE OF THE REPORT This report must be used only for reporting on the condition of an existing installation.
Purpose for which Electrical Installation Condition Report
this report is required:
Date(s) on which inspection and testing were carried out: 17/08/2017 - 24/08/2017

C. DETAILS OF THE INSTALLATION

Occupier Manor Primary School Address Manor Primary School


Ettingshall Road
Wolverhampton
Postcode: WV14 9UQ
If yes,
Estimated age of the
electrical installation: 35 years Description of premises:
domestic, commercial, School
Evidence of alterations
or additions á estimated Misc years
industrial, other age
Date of previous N/A (Please state) Electrical Installation Certificate No or previous N/A
inspection: Periodic Inspection or Condition Report No:

Records of installation available: No Records held by: N/A

D. EXTENT OF THE INSTALLATION AND LIMITATIONS ON THE INSPECTION AND TESTING


Extent of the electrical installation covered by this report:
Complete Installation

Agreed limitations (including the reasons), if any, on the inspection and testing:
10% Fittings Removed. 100% Visual. Visual & Accessible Items Tested Only

Agreed with: Client

Operational limitations including the reasons (see page No. )


No Access To Main Supply Protective Device

The inspection and testing have been carried out in accordance with BS 7671, as amended. Cables concealed within trunking and conduits, or cables and conduits
concealed under floors, in inaccessible roof spaces and generally within the fabric of the building or underground, have not been visually inspected unless
specifically agreed between the client and inspector prior to the inspection.

E. SUMMARY OF THE CONDITION OF THE INSTALLATION


General condition of the installation (in terms of electrical safety):

See Observations (Page 2)

Summary of the condition of the installation continued on additional pages? No á Yes Specify page No(s):

Overall assessment An ‘Unsatisfactory’ assessment indicates that dangerous (CODE C1) and/or potentially
of the installation: SATISFACTORY / UNSATISFACTORY dangerous (CODE C2) conditions have been identified, or that Further investigation without
delay (FI) is required

This report should have been reviewed and confirmed by the registered Qualified Supervisor Page 1 of 78
of the Approved Contractor responsible for issuing it. (See declaration on page 2)

This report is based on the model forms shown in Appendix 6 of BS7671 Please see the 'Notes for Recipients'
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015)
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


ELECTRICAL INSTALLATION
CONDITION REPORT
F. OBSERVATIONS AND RECOMMENDATIONS FOR ACTIONS TO BE TAKEN
Referring to the attached schedules of inspection and test results, and subject to the limitations at D:
There are no items adversely affecting electrical safety. N/A or The following observations and recommendations for á
are made

Item No Code Ú

Original
1 Main Panel 1 - Circuit 1L123 - Correct Overload Settings Present Within ESP Unit Right Hand Side Of This NOTE
Panel

2 Main Panel 1 - Circuit 2L123 - This Circuit Supplies Empty DB That Is Isolated & not In Use NOTE
3 DB/0/1/BL - Unable To Obtain Z's Readings To Lighting Circuits Due To height Of Ceilings And Access To Sensors LIM
4 DB 0/1/A - Circuits 1L1,2L1,3L1 - Unable To Obtain Reading Due To Access Of Equipment LIM
5 DB 0/1/A(2) - Unable To Obtain Z's Readings To Lighting Circuits Due To Height Of Ceilings And Access To Sensors LIM
6 DB Severy - Alot Of Redundant Cables In Bottom Of DB C3
7 DB Severy - 4 x 20mm Holes In Side Of DB C2
8 DB Severy - 2 x 20mm Holes In Trunking In DB C2
9 DB Severy - 2 x 25mm Holes In Trunking Under DB C2
10 DB Severy - 1 x Board Screw Missing C2
11 DB Severy - Circuit 1L1 - Unable To Obtain Z's Due To Height Of Fitting LIM
12 DB Caretakers - 3 x Board Cover Pins Missing C3
13 DB Caretakers - Circuits 1L1, 1L2 + 11L3 - Overrated MCB For Conductor Size C2
14 DB Caretakers - Circuits 1L2 + 1L3 - Unknown Circuit Further Investigation Is Required To Locate Final C2
Termination Of Circuit

15 DB Caretakers - Circuit 3L3 - Damaged Double Socket C2


16 DB C - 4 x 20mm Holes In DB C2
17 DB C - 9 x Board Blanks Missing C2
18 DB C - Circuits 7L3 + 8L2 - Unable To Obtain Z's Readings To Lighting Circuits Due To Height Of Ceilings And Access To Sensors LIM
19 DB D - DB Not To IPX4 C2
20 DB A - DB Not To IPX4 C2

Additional Pages? No Yes á Specify page 9


Immediate remedial action
ÚOne of the following codes, as appropriate, has been allocated to each of the required for items:
observations made above to indicate to the person(s) responsible for the installation
the degree of urgency for remedial action: Urgent remedial action
required for items: 7, 8, 9, 10, 13, 14, 15, 16, 17, 19, 20, 22, 24, 25, 26, 3
Code C1 "Danger Present". Risk of injury. Immediate remedial action required.
Code C2 "Potentially dangerous". Urgent remedial action required. Further investigation required
without delay for items:
Code C3 "Improvement recommended".
Code FI "Further investigation required without delay". Improvement
recommended for items: 6, 12, 21, 23, 27, 29, 31, 32, 34, 45, 51, 52, 53, 55, 57
Please see the notes for recipient for guidance regarding the Classification codes.

G. DECLARATION
I/We, being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by my/our signatures below), particulars of which
are described in page 1 (see C), having exercised reasonable skill and care when carrying out the inspection and testing, hereby declare that the information
in this report, including the observations (see F) and the attached schedules (see H), provides an accurate assessment of the condition of the electrical
i n s t a l l a t i o n t a k i n g i n t o a c c o u n t t h e s t a t e d e x t e n t o f t h e i n s t a ll a t i o n a n d t h e l i m i t a t i o n s o f t h e i n s p e c t i o n a n d t e s t i n g ( s e e D ) .
I/We further declare that in my/our judgement, the overall assessment of the installation in terms of its suitability for continued use is
SATISFACTORY / UNSATISFACTORY* (see F) at the time the inspection was carried out, and that it should be further inspected as recommended (see I).
*An ‘Unsatisfactory’ assessment indicates that dangerous (CODE C1) and/or potentially dangerous (CODE C2) conditions have been identified, or that Further investigation
without delay (FI) is required.
INSPECTION, TESTING AND ASSESSMENT BY: REPORT REVIEWED AND CONFIRMED BY:
Signature Signature
Name Name
(CAPITALS) ANTHONY KNAPP (CAPITALS) MICHAEL BRYAN

Position (Registered Qualified Supervisor for the Approved Contractor at J)


Test Engineer

Date: 24/08/2017 Date: 25/08/2017

Page 2 of 78
This report is based on the model forms shown in Appendix 6 of BS7671 Please see the 'Guidance for Recipients on the
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) classification codes' in the 'Notes for Recipients'
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


ELECTRICAL INSTALLATION
CONDITION REPORT
H. SCHEDULES AND ADDITIONAL PAGES
Inspection Schedule: Page(s) No 4,5,6 Additional pages, including additional Page No(s)
source(s) data sheets:
Schedule of Circuit Details for the Installation: Page No(s) Odd, 7 - 73 Schedule of Test Results for the Installation: Page No(s) Even, 8 - 74

Original
The pages identified are an essential part of this report. The report is valid only if accompanied by all the schedules and additional pages identified above.

I. NEXT INSPECTION
I/We recommend that this installation is further (Enter interval in terms of
inspected and tested after an interval of not more than 5 Years years, months or weeks, as appropriate)
provided that any items at F which have been attributed a Classification code C1 (danger present) are remedied immediately and that any items
which have been attributed a code C2 (potentially dangerous) or FI (further investigation required without delay) are remedied or investigated
respectively as a matter of urgency. Items which have been attributed a Classification code C3 should be improved as soon as
practicable (see F).

J. DETAILS OF NICEIC APPROVED CONTRACTOR


Trading Title: Electrical Test Midlands Ltd
Address: 110B Walsall Road Telephone number: 01922 710014
Cannock
Email Address: admin@electricaltestmidlands.com

Enrolment number:
(Essential information)
035056
Postcode:WS11 0JB Branch number:
N/A
(if applicable)

K. SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS Characteristics of Primary Supply


Overcurrent Protective Device(s)
System Type(s) Number and Type of Live Conductors Nature of Supply Parameters
Nominal Uþ
TN-S N/A a.c. á d.c. N/A Voltage(s):
400
V UÒþ
230
V BS(EN) 88

1-phase 1-phase Nominal 50 Notes:


TN-C-S á (2 wire) N/A (3 wire) N/A 2 pole N/A frequency, fþ Hz (1) by enquiry Type 2
Prospective fault (2) by enquiry or by
2-phase N/A 3 pole N/A 39.9 Rated current 200 A
TN-C N/A (3 wire) current, IÙÄÅ kA measurement
(3) where more than
N/A External earth fault 0.01 Short-circuit
TT N/A 3-phase
(3 wire) N/A 3-phase
(4 wire) á other loop impendance, Ñ Å Ç É one supply, record
the higher or highest
capacity 80 kA
values
IT N/A Other N/A Number of
sources
1
(4) by measurement
Confirmation of
supply polarity á (á)

L. PARTICULARS OF INSTALLATION AT THE ORIGIN


Means of Earthing Details of Installation Earth Electrode (where applicable)
Type:
Distributor's
facility: á (eg rod(s),tape(s))
N/A Location: N/A

Installation Electrode N/A Method of N/A


earth electrode: N/A resistance, RÕ: (É) measurement:
Main Switch/Switch-Fuse/Circuit-Breaker/RCD Earthing and protective bonding conductors
Earthing conductor Main protective bonding conductors Bonding of extraneous-conductive-parts (á)
Type: 60947-3 Voltage 690 Conductor Conductor
BS(EN) rating V material
Copper
material
Copper Water
installation pipes á Lightning
protection N/A
No of Rated Conductor Conductor
Poles
3
current,IÐ
250 A csa
50.0 mmâ csa
50.0 mmâ Oil
installation pipes N/A Structural
steel á
Primary supply RCD operating
conductors
material
Copper
current, IÜ *
N/A mA Connection/
continuity á (á) Connection/
continuity á (á) Gas
installation pipes á
Primary supply verified verified
95.0 mmâ Rated time N/A Other
conductors delay* ms
csa N/A
RCD operating N/A ms
time (at IÜ )*
* (applicable only where an RCD is suitable and is used as a main circuit-breaker)

Page 3 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 Please see the 'Notes for Recipients'
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015)
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


ELECTRICAL INSTALLATION CONDITION REPORT
INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS
Item Description Outcome* Location reference
1.0 Condition/adequacy of distributor's/supply intake equipmentÚ
1.1 Service cable á
1.2 Service head N/A
1.3 Distributor's earthing arrangement(s) á

Original
1.4 Meter tails - Distributor/ Consumer á
1.5 Metering equipment á
1.6 Means of main isolation (where present) á
2.0 Presence of adequate arrangements for parallel or switched alternative sources
2.1 Adequate arrangements where a generating set operates as a switched alternative to the public supply N/A
2.2 Adequate arrangements where a generating set operates in parallel with the public supply N/A

3.0 Automatic disconnection of supply


3.1 Main earthing and bonding arrangements
Presence and condition of distributor's earthing arrangement á
Presence and condition of earth electrode arrangement N/A
Adequacy of earthing conductor size á
Adequacy of earthing conductor connections á
Accessibility of earthing conductor connections á
Adequacy of main protective bonding conductor size(s) á
Adequacy of main protective bonding conductor connections á
Accessibility of main protective bonding connections á
Accessibility and condition of other protective bonding connections á
Provision of earthing/bonding labels at all appropriate locations á
3.2 FELV
Source providing at least simple separation N/A
Plugs, socket-outlets and the like not interchangeable with those of other systems within the premises N/A
3.3 Reduced low voltage
Adequacy of source N/A
Plugs, socket-outlets and the like not interchangeable with those of other systems within the premises N/A

4.0 Other methods of protection (where the methods of protection listed below are employed, details should be
provided on separate sheets)
4.1 Double insulation á
4.2 Reinforced insulation á
4.3 Use of obstacles N/A
4.4 Placing out of reach á
4.5 Non-conducting location N/A
4.6 Earth-free local equipotential bonding N/A
4.7 Electrical separation for more than one item of equipment N/A

5.0 Distribution equipment


5.1 Adequacy of working space/accessibility of equipment á
5.2 Security of fixing á
5.3 Condition of insulation of live parts C2
5.4 Adequacy/security of barriers á
5.5 Condition of enclosure(s) in terms of IP rating C2
5.6 Condition of enclosure(s) in terms of fire rating á
5.7 Enclosure not damaged/deteriorated so as to impair safety á
5.8 Presence of main switch(es), linked where required á
5.9 Operation of main switch(es) (functional check) á

* All Outcome boxes must be completed Unacceptable condition state C1 or C2 Outcome


'á' indicates Acceptable condition Improvement recommended state C3 Provide additional comment where appropriate on Page 4 of 78
'LIM' indicates a Limitation Further investigation required without delay state FI attached numbered sheets. C1, C2, C3 and FI coded
'N/A' indicates Not applicable (to determine whether danger or potential danger exists) items to be recorded in Section F of the report.

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015)
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


ELECTRICAL INSTALLATION CONDITION REPORT
INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS
Item Description Outcome* Location reference
5.10 Correct identification of circuit protective devices á
5.11 Adequacy of protective devices for prospective fault current á
5.12 RCD(s) provided for fault protection - includes RCBOs á
5.13 RCD(s) provided for additional protection - includes RCBOs á

Original
5.14 RCD(s) provided for protection against fire - includes RCBOs á
5.15 Manual operation of circuit-breakers and RCDs to prove disconnection á
5.16 Presence of RCD retest notice at or near equipment where required á
5.17 Presence of diagrams, charts or schedules at or near equipment, where required á
5.18 Presence of non-standard (mixed) cable colour warning notice at or near equipment where required á
5.19 Presence of alternative/additional supply arrangement warning notice(s) at or near equipment where required N/A

5.20 Presence of replacement next inspection recommendation label á


5.21 Presence of other required labelling (specify) N/A
5.22 Examination of protective device(s) and base(s); correct type and rating (no signs of unacceptable thermal damage,
arcing or overheating)
á
5.23 Single-pole switching or protective devices in line conductors only á
5.24 Protection against mechanical damage where cables enter equipment á
5.25 Protection against electromagnetic effects where cables enter metallic enclosures á
6.0 Distribution/final circuits
6.1 Identification of conductors á
6.2 Cables correctly supported throughout their length á
6.3 Condition of insulation of live parts á
6.4 Non-sheathed cables protected by enclosure in conduit, ducting or trunking á
6.5 Suitability of containment systems for continued use (including flexible conduit) á
6.6 Cables correctly terminated in enclosures (indicate extent of sampling in Section D of report) á
6.7 Confirmation of indication that SPD(s) are functional á
6.8 Confirmation that ALL conductor connections, including connections to busbars are correctly located in terminals and
are tight and secure
á
6.9 Examination of cables for signs of unacceptable thermal and mechanical damage/deterioration á
6.10 Adequacy of cables for current-carrying capacity with regard to the type and nature of installation C2
6.11 Adequacy of protective devices; type and rated current for fault protection á
6.12 Presence and adequacy of circuit protective conductors á
6.13 Co-ordination between conductors and overload protective devices á
6.14 Cable installation methods/practices appropriate to the type and nature of installation and external influences á
6.15 Cables where exposed to direct sunlight, of a suitable type á
6.16 Cables installed under floors, above ceilings, in walls / partitions, adequately protected against damage
installed in prescribed zones (see Section D. Extent and limitations) LIM
incorporating earthed armour or sheath, or installed within earthed wiring system, or otherwise protected against N/A
mechanical damage by nails, screws and the like (see Section D. Extent and limitations)
6.17 Provision of additional protection by 30 mA RCD
Ú for mobile equipment not exceeding a rating of 32 A for use outdoors á
Ú for all socket-outlets of rating 20 A or less, unless exempt á
Ú for cables installed in walls / partitions at a depth of less than 50 mm C3
Ú for cables installed in walls / partitions containing metal parts regardless of depth á
6.18 Provision of fire barriers, sealing arrangements and protection against thermal effects á
6.19 Band II cables segregated/separated from Band I cables á
6.20 Cables segregated/separated from non-electrical services á
6.21 Termination of cables at enclosures (identify numbers and locations of items inspected in Section D)
Connections under no undue strain á
No basic insulation of a conductor visible outside an enclosure á
Connections of live conductors adequately enclosed á

* All Outcome boxes must be completed Unacceptable condition state C1 or C2 Outcome


'á' indicates Acceptable condition Improvement recommended state C3 Provide additional comment where appropriate on Page 5 of 78
'LIM' indicates a Limitation Further investigation required without delay state FI attached numbered sheets. C1, C2, C3 and FI coded
'N/A' indicates Not applicable (to determine whether danger or potential danger exists) items to be recorded in Section F of the report.

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015)
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


ELECTRICAL INSTALLATION CONDITION REPORT
INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS
Item Description Outcome* Location reference
6.21 Adequacy of connection at point of entry to enclosure (gland, bush or similar) á
6.22 General condition of wiring systems á
6.23 Temperature rating of cable insulation á
6.24 Condition of accessories including socket-outlets, switches and joint boxes á

Original
6.25 Suitability of accessories for external influences á
6.26 Single-pole switching or protective devices in line conductors only á
6.27 Adequacy of connections, including cpcs, within accessories and to fixed and stationary equipment - identify /record
numbers and locations of items inspected
á
7.0 Isolation and switching
7.1 Isolators
presence and condition of appropriate devices á
acceptable location (state if local or remote) á
capable of being secured in the OFF position á
correct operation verified á
clearly identified by position and/or durable marking(s) á
Warning label posted in situations where live parts cannot be isolated by the operation of a single device á
7.2 Switching off for mechanical maintenance
presence and condition of appropriate devices á
acceptable location á
capable of being secured in the OFF position á
correct operation verified á
clearly identified by position and/or durable marking(s) á
7.3 Emergency switching/stopping
presence and condition of appropriate devices á
readily accessible for operation where danger might occur á
correct operation verified á
clearly identified by position and/or durable marking(s) á
7.4 Functional switching
presence and condition of appropriate devices á
correct operation verified á
8.0 Current-using equipment (permanently connected)
8.1 Condition of equipment in terms of IP rating á
8.2 Equipment does not constitute a fire hazard á
8.3 Enclosure not damaged/deteriorated so as to impair safety á
8.4 Suitability for the environment and external influences á
8.5 Security of fixing á
8.6 Cable entry holes in ceiling above luminaires, sized or sealed so as to restrict the spread of fire (indicate extent of
sampling in Section D of report)
á
8.7 Recessed luminaires (e.g. downlighters)
correct type of lamps fitted á
installed to minimise build-up of heat by use of "fire rated" fittings, insulation displacement box or similar á
no signs of overheating to surrounding building fabric á
no signs of overheating to conductors/terminations á
9.0 Location(s) containing a bath or shower
9.1 Additional protection by RCD not exceeding 30 mA
for low voltage circuits serving the location N/A
for low voltage circuits passing through Zone 1 and Zone 2 not serving the location N/A
9.2 Where used as a protective measure, requirements for SELV or PELV are met N/A

* All Outcome boxes must be completed Unacceptable condition state C1 or C2 Outcome


'á' indicates Acceptable condition Improvement recommended state C3 Provide additional comment where appropriate on Page 6 of 78
'LIM' indicates a Limitation Further investigation required without delay state FI attached numbered sheets. C1, C2, C3 and FI coded
'N/A' indicates Not applicable (to determine whether danger or potential danger exists) items to be recorded in Section F of the report.

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015)
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


ELECTRICAL INSTALLATION CONDITION REPORT
INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS
Item Description Outcome* Location reference
9.3 Shaver sockets comply with BS EN 61558-2-5 or BS 3535 N/A
9.4 Presence of supplementary bonding conductors unless not required by BS 7671: 2008 N/A
9.5 Low voltage (e.g. 230 volts) socket-outlets sited at least 3 m from zone 1 N/A
9.6 Suitability of equipment for external influences for installed location in terms of IP rating N/A

Original
9.7 Suitability of equipment for installation in a particular zone N/A
9.8 Suitability of current-using equipment for a particular position within the location N/A

10.0 Other special installations or locations


List special locations present, if any. List the results of particular inspections applied (a separate page is required for
each location). N/A
N/A
N/A
N/A
N/A
N/A

* All Outcome boxes must be completed Unacceptable condition state C1 or C2 Outcome


'á' indicates Acceptable condition Improvement recommended state C3 Provide additional comment where appropriate on Page 7 of 78
'LIM' indicates a Limitation Further investigation required without delay state FI attached numbered sheets. C1, C2, C3 and FI coded
'N/A' indicates Not applicable (to determine whether danger or potential danger exists) items to be recorded in Section F of the report.

This report is based on the model forms shown in Appendix 6 of BS7671


Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015)
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of METER STORE GROUND Supply to distribution ORIGIN No of Nominal 400


phases: 3 V

Original
distribution board: LEVEL board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution MAIN PANEL 1 SW FUSE Type: N/A Rating: N/A A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L123 Supply to: MAIN PANEL 1 D B 1 95.0 50.0 5.0 88 Fuse HRC 2 200 80 - 0.18

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 8 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.01 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 39.9 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L123 - - - 0.02 - 200 200 200 200 á 0.03 - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 9 of 78
Name: ANTHONY KNAPP Date of 17/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of METER STORE GROUND Supply to distribution MAIN PANEL 1 SW FUSE No of Nominal 400
phases: 3 V

Original
distribution board: LEVEL board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution MAIN PANEL 1 Type: 88 Rating: 200 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L123 ESP UNIT D B 1 10.0 10.0 5.0 60947-2 MCCB 2 100 25 - 0.42
2L123 DB (SPARE) F C 1 25.0 C/S 5.0 60947-2 MCCB 2 100 25 - 0.42
3L123 Supply to: DB 0/1/BP F C 1 35.0 25.0 5.0 60947-2 MCCB 2 100 25 - 0.42
4L123 Supply to: DB 0/1/A F C 1 25.0 25.0 5.0 60947-2 MCCB 2 100 25 - 0.42
5L123 Supply to: DB SEVERY G C 1 50.0 25.0 5.0 60947-2 MCCB 2 125 36 - 0.32
6L123 Supply to: DB CARETAKERS G C 1 50.0 25.0 5.0 60947-2 MCCB 2 200 36 - 0.18
7L123 Supply to: DB 14 G C 1 25.0 C/S 5.0 60947-2 MCCB 2 100 25 - 0.42
8L123 Supply to: DB A1 G C 1 35.0 C/S 5.0 60947-2 MCCB 2 100 25 - 0.42
9L123 SPARE - - - - - - - - - - - -
10L123 Supply to: DB 13 G C 1 25.0 C/S 5.0 60947-2 MCCB 2 100 25 - 0.42
11L1 SPARE - - - - - - - - - - - -
11L2 FIRE ALARM PANEL O C 1 2.5 1.5 0.4 60947-2 MCCB 2 16 65 - 2.43
11L3 SPARE - - - - - - - - - - - -
12L123 Supply to: MAIN PANEL 2 SWITCH FUSE D B 1 95.0 50.0 5.0 60947-2 MCCB 2 200 36 - 0.18

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 10 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.03 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 15.4 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L123 - - - 0.01 - 200 200 200 200 á 0.04 - -


2L123 - - - 0.01 - 200 200 200 200 á 0.04 - -
3L123 - - - 0.14 - 200 200 200 200 á 0.17 - -
4L123 - - - 0.08 - 200 200 200 200 á 0.11 - -
5L123 - - - 0.14 - 200 200 200 200 á 0.17 - -
6L123 - - - 0.12 - 200 200 200 200 á 0.15 - -
7L123 - - - 0.12 - 200 200 200 200 á 0.15 - -
8L123 - - - 0.14 - 200 200 200 200 á 0.17 - -
9L123 - - - - - - - - - - - -
10L123 - - - 0.13 - 200 200 200 200 á 0.16 - -
11L1 - - - - - - - - - - - -
11L2 - - - 0.07 - - - 200 200 á 0.10 - -
11L3 - - - - - - - - - - - -
12L123 - - - 0.01 - 200 200 200 200 á 0.04 - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 11 of 78
Name: ANTHONY KNAPP Date of 17/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of CORRIDOR 13 Supply to distribution MAIN PANEL 1 No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 0/1/BP Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 RECEPTION W.C WATER HEATER B B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
1L2 NURSERY SOCKETS B B 10 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
1L3 RECEPTION W.C WATER HEATER B B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
2L1 CORRIDOR SOCKET (OPPOSITE DB) B B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
2L2 SPARE - - - - - - - - - - - -
2L3 CLASS 2 + CLOAK ROOM SOCKETS B B 5 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
3L1 NURSERY W.C WATER HEATER B B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
3L2 SPARE - - - - - - - - - - - -
3L3 CLASS 2 DADO SOCKETS B B 5 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
4L1 CLASS 3 DADO SOCKETS B B 9 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
4L2 COOKER B B 1 6.0 6.0 0.4 61009 RCD/RCBO B 32 10 30 1.37
4L3 CLASS WATER HEATER B B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
5L1 TOILET HEATER B B 1 2.5 2.5 0.4 61009 RCD/RCBO B 16 10 30 2.73
5L2 HOB B B 2 2.5 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
5L3 CLASS 1 SOCKETS B B 4 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
6L1 CLASS 3 WATER HEATER B B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
6L2 BREAKOUT SPACE SOCKETS B B 9 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
6L3 CLASS 1 DADO SOCKETS B B 5 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
7L1 CORRIDOR SOCKETS B B 3 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
7L2 SPARE - - - - - - - - - - - -
7L3 CLASS 1 WATER HEATER B B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
8L1 CORRIDOR SOCKETS B B 2 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
8L2 MEETING SPACE SOCKETS B B 5 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
8L3 NURSERY SOCKET B B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
9L1 ADT SPUR B B 1 2.5 2.5 0.4 61009 RCD/RCBO B 10 10 30 4.37
9L2 MOTOR SPUR B B 1 2.5 2.5 0.4 61009 RCD/RCBO B 10 10 30 4.37
9L3 SPARE - - - - - - - - - - - -
10L1 SPARE - - - - - - - - - - - -
10L2 SPARE - - - - - - - - - - - -
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 12 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340212 RCD 101340212
impedance

Original
* See note below
Operating times
Ö *0.17 É At IÜ N/A ms Insulation 101340210 Multi N/A
of associated resistance function
IÙ 2.7 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340210 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - 0.10 - - - 200 200 á 0.27 36.4 26.4 á


1L2 0.66 0.67 0.73 0.23 - - - 200 200 á 0.40 31.5 30.7 á
1L3 - - - 0.17 - - - 200 200 á 0.34 32.4 22.4 á
2L1 - - - 0.13 - - - 200 200 á 0.30 31.6 30.2 á
2L2 - - - - - - - - - - - -
2L3 0.60 0.61 0.69 0.29 - - - 200 200 á 0.46 38.6 28.4 á
3L1 - - - 0.13 - - - 200 200 á 0.40 38.4 28.2 á
3L2 - - - - - - - - - - - -
3L3 0.21 0.21 0.30 0.12 - - - 200 200 á 0.29 38.2 31 á
4L1 0.55 0.56 0.63 0.17 - - - 200 200 á 0.34 38.4 28.4 á
4L2 - - - 0.26 - - - 200 200 á 0.43 28.6 27.9 á
4L3 - - - 0.21 - - - 200 200 á 0.38 31.7 29.6 á
5L1 - - - 0.13 - - - 200 200 á 0.30 38.4 28.4 á
5L2 - - - 0.32 - - - 200 200 á 0.49 28.6 28.3 á
5L3 0.46 0.46 0.40 0.31 - - - 200 200 á 0.48 38.7 28.4 á
6L1 - - - 0.28 - - - 200 200 á 0.45 38.4 28.6 á
6L2 0.68 0.69 0.75 0.30 - - - 200 200 á 0.47 38.6 27.8 á
6L3 0.30 0.32 0.41 0.18 - - - 200 200 á 0.35 38.2 28.3 á
7L1 0.52 0.53 0.42 0.11 - - - 200 200 á 0.28 38.7 28.2 á
7L2 - - - - - - - - - - - -
7L3 - - - 0.26 - - - 200 200 á 0.43 32.5 28.6 á
8L1 0.37 0.38 0.36 0.17 - - - 200 200 á 0.34 38.8 28.4 á
8L2 0.78 0.78 0.77 0.37 - - - 200 200 á 0.54 38.3 28.4 á
8L3 - - - 0.24 - - - 200 200 á 0.41 32.8 30.8 á
9L1 - - - 0.19 - - - 200 200 0.36 - -
9L2 - - - LIM - - - 200 200 LIM - -
9L3 - - - - - - - - - - - -
10L1 - - - - - - - - - - - -
10L2 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 13 of 78
Name: JOE LACEY Date of 23/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of CORRIDOR 13 Supply to distribution MAIN PANEL 1 No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 0/1/BP Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
10L3 SPARE - - - - - - - - - - - -
11L123 SPARE - - - - - - - - - - - -
12L123 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 14 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340212 RCD 101340212
impedance

Original
* See note below
Operating times
Ö *0.17 É At IÜ N/A ms Insulation 101340210 Multi N/A
of associated resistance function
IÙ 2.7 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340210 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

10L3 - - - - - - - - - - - -
11L123 - - - - - - - - - - - -
12L123 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 15 of 78
Name: JOE LACEY Date of 23/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of CORRIDOR 13 Supply to distribution LIVE SIDE OF DB/0/1/BP No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB/0/1/BL Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 LIGHTS RECEPTION + NURSERY W.C B B 13 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
1L2 LIGHTS RECEPTION W.C + CLOAKROOM B B 8 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
1L3 CORRIDOR LIGHTS B B 5 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
2L1 SPARE - - - - - - - - - - - -
2L2 NURSERY LIGHTS B B 15 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
2L3 CLASS 2 LIGHTS B B 9 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
3L1 CLASS 3 LIGHTS B B 9 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
3L2 LIGHTS BREAKOUT + RECEPTION CLOAKROOM B B 9 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
3L3 CLASS 1 LIGHTS B B 9 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
4L1 MEETING SPACE LIGHTS B B 3 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
4L2 ROOF FANS B B 1 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
4L3 SPARE - - - - - - - - - - - -
5L123 SPARE - - - - - - - - - - - -
6L123 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 16 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340212 RCD 101340212
impedance

Original
* See note below
Operating times
Ö *0.18 É At IÜ N/A ms Insulation 101340210 Multi N/A
of associated resistance function
IÙ 2.88 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340210 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - LIM - - - 200 200 LIM - -


1L2 - - - 0.16 - - - 200 200 á 0.34 - -
1L3 - - - LIM - - - 200 200 LIM - -
2L1 - - - - - - - - - - - -
2L2 - - - LIM - - - 200 200 LIM - -
2L3 - - - LIM - - - 200 200 LIM - -
3L1 - - - LIM - - - 200 200 LIM - -
3L2 - - - LIM - - - 200 200 LIM - -
3L3 - - - LIM - - - 200 200 LIM - -
4L1 - - - LIM - - - 200 200 LIM - -
4L2 - - - LIM - - - 200 200 LIM - -
4L3 - - - - - - - - - - - -
5L123 - - - - - - - - - - - -
6L123 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 17 of 78
Name: JOE LACEY Date of 23/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of METER STORE GROUND Supply to distribution MAIN PANEL 1 No of Nominal 400
phases: 3 V

Original
distribution board: LEVEL board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 0/1/A Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 CISTERMISER B/D B 2 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
1L2 SOCKET BELOW B/D B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
1L3 DOOR ENTRY SYSTEM B/D B 1 2.5 2.5 0.4 60898 MCB B 10 10 - 4.37
2L1 WATER HEATER GIRLS W.C B/D B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
2L2 SOCKETS CLASS ROOM NEAR B/D B 9 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
2L3 SOCKETS CLASS ROOM MIDDLE B/D B 9 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
3L1 WATER HEATER BOYS W.C B/D B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
3L2 WATER HEATER NEAR B/D B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
3L3 WATER HEATER MIDDLE B/D B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
4L1 SOCKETS CLASSROOM FAR B/D B 9 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
4L2 SOCKETS CORRIDOR B/D B 3 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
4L3 SPARE - - - - - - - - - - - -
5L1 SPARE - - - - - - - - - - - -
5L2 SPARE - - - - - - - - - - - -
5L3 HAND DRIERS IN W.C'S A B 2 2.5 1.5 0.4 61009 RCD/RCBO C 10 10 30 2.19
6L1 WATER HEATER FAR B/D B 1 2.5 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
6L2 ADT SPUR B/D 1 2.5 2.5 0.4 0.4 60898 MCB B 6 10 - 7.28
6L3 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 18 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.11 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 4.2 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - LIM - - - 200 200 LIM 28.3 28.6 á


1L2 - - - 0.02 - - - 200 200 á 0.13 28.3 28.3 á
1L3 - - - 0.08 - - - 200 200 á 0.19 - -
2L1 - - - LIM - - - 200 200 LIM 28.7 28.7 á
2L2 0.23 0.23 0.22 0.12 - - - 200 200 á 0.23 33.1 31.0 á
2L3 0.49 0.49 0.49 0.26 - - - 200 200 á 0.37 33.6 31.2 á
3L1 - - - LIM - - - 200 200 LIM 28.4 28.0 á
3L2 - - - 0.09 - - - 200 200 á 0.20 28.4 28.4 á
3L3 - - - 0.16 - - - 200 200 á 0.27 28.4 28.4 á
4L1 0.57 0.56 0.56 0.29 - - - 200 200 á 0.40 28.4 31.0 á
4L2 0.16 0.16 0.16 0.09 - - - 200 200 á 0.20 28.4 28.5 á
4L3 - - - - - - - - - - - -
5L1 - - - - - - - - - - - -
5L2 - - - - - - - - - - - -
5L3 - - - 0.15 - - - 200 200 á 0.26 28.6 29.1 á
6L1 - - - 0.21 - - - 200 200 á 0.32 28.5 28.4 á
6L2 - - - 0.14 - - - 200 200 á 0.25 - -
6L3 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 19 of 78
Name: ANTHONY KNAPP Date of 17/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of METER STORE GROUND Supply to distribution DB 0/1/A (LIVESIDE) No of Nominal 400
phases: 3 V

Original
distribution board: LEVEL board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 0/1/A(2) Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 W.C LIGHTS D/B B 10 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
1L2 CLASS ROOM LIGHTS NEAR D/B B 14 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
1L3 CLASS ROOM LIGHTS MIDDLE D/B B 12 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
2L1 CLASS ROOM LIGHTS FAR D/B B 13 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
2L2 CORRIDOR LIGHTS D/B B 13 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
2L3 LIGHT THIS ROOM D/B B 1 1.5 1.5 0.4 60898 MCB B 6 10 - 7.28
3L123 SPARE - - - - - - - - - - - -
4L123 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 20 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.11 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 4.2 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - LIM - - - 200 200 LIM - -


1L2 - - - LIM - - - 200 200 LIM - -
1L3 - - - LIM - - - 200 200 LIM - -
2L1 - - - LIM - - - 200 200 LIM - -
2L2 - - - LIM - - - 200 200 LIM - -
2L3 - - - LIM - - - 200 200 LIM - -
3L123 - - - - - - - - - - - -
4L123 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 21 of 78
Name: ANTHONY KNAPP Date of 18/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of STORE NEXT TO HALL Supply to distribution MAIN PANEL 1 No of Nominal 400
phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB SEVERY Type: 60947-2 Rating: 125 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 LIGHTS THIS ROOM C B 2 2.5 1.5 0.4 60898 MCB C 6 10 - 3.64
1L2 SPARE - - - - - - - - - - - -
1L3 SPARE - - - - - - - - - - - -
2L123 SPARE - - - - - - - - - - - -
3L123 SPARE - - - - - - - - - - - -
4L123 SPARE - - - - - - - - - - - -
5L1 LIGHT STORE D B 1 2.5 1.5 0.4 60898 MCB B 6 10 - 7.28
5L2 SOCKETS HALL + RECEPTION D B 2 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
5L3 SOCKET HALL D B 1 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
6L123 SPARE - - - - - - - - - - - -
7L1 LIGHTS HALL D B 5 2.5 1.5 0.4 60898 MCB B 6 10 - 7.28
7L2 SPARE - - - - - - - - - - - -
7L3 SPARE - - - - - - - - - - - -
8L1 LIGHTS HALL D B 5 1.5 1.5 0.4 60898 MCB B 6 10 - 7.28
8L2 SPARE - - - - - - - - - - - -
8L3 SPARE - - - - - - - - - - - -
9L1 SOCKETS THIS ROOM D B 8 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
9L2 SOCKETS HALL BACK WALL B B 1 6.0 6.0 0.4 61009 RCD/RCBO C 32 10 30 0.68
9L3 SPARE - - - - - - - - - - - -
10L123 SPARE - - - - - - - - - - - -
11L123 SPARE - - - - - - - - - - - -
12L123 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 22 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop N/A RCD N/A
impedance

Original
* See note below
Operating times
Ö *0.17 É At IÜ N/A ms Insulation N/A Multi 101393074
of associated resistance function
IÙ 2.64 kA RCD (if any) At 5IÜ N/A ms
*
Continuity N/A Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - LIM - - - 200 200 LIM - -


1L2 - - - - - - - - - - - -
1L3 - - - - - - - - - - - -
2L123 - - - - - - - - - - - -
3L123 - - - - - - - - - - - -
4L123 - - - - - - - - - - - -
5L1 - - - 0.44 - - - 200 200 á 0.61 - -
5L2 - - - 0.36 - - - 200 200 á 0.53 38.7 18.6 á
5L3 - - - 0.30 - - - 200 200 á 0.47 28.7 18.7 á
6L123 - - - - - - - - - - - -
7L1 - - - 0.52 - - - 200 200 á 0.69 - -
7L2 - - - - - - - - - - - -
7L3 - - - - - - - - - - - -
8L1 - - - 0.58 - - - 200 200 á 0.75 - -
8L2 - - - - - - - - - - - -
8L3 - - - - - - - - - - - -
9L1 0.41 0.41 0.68 0.09 - - - 200 200 á 0.24 38.6 28.5 á
9L2 - - - 0.05 - - - 200 200 á 0.21 38.9 28.7 á
9L3 - - - - - - - - - - - -
10L123 - - - - - - - - - - - -
11L123 - - - - - - - - - - - -
12L123 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 23 of 78
Name: MICHAEL DAVIES Date of 18/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of TOP OF STAIRS TO LOWER Supply to distribution MAIN PANEL 1 No of Nominal 400
phases: 3 V

Original
distribution board: LEVEL NEAR HALL board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB CARETAKERS Type: 60947-2 Rating: 200 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 WHITEBOARD SOCKETS CLASSROOM NEAR H C 4 2.5 CASE 0.4 61009 RCD/RCBO C 32 10 30 0.68
1L2 UNKNOWN H C LIM 4.0 CASE 0.4 60898 MCB C 50 10 30 0.44
1L3 UNKNOWN H C LIM 4.0 CASE 0.4 60898 MCB C 50 10 30 0.44
2L1 SOCKETS CLASSROOM NEAR H C 8 4.0 CASE 0.4 61009 RCD/RCBO C 32 10 30 0.68
2L2 SPARE - - - - - - - - - - - -
2L3 SPARE - - - - - - - - - - - -
3L1 EMERGENCY LIGHTS HALL + CORRIDOR D B 1 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
3L2 HALL LIGHTS D B 6 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
3L3 HALL SOCKETS + DADO RIGHT HAND SIDE D B 4 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
4L1 EMERGENCY LIGHTS HALL + CORRIDOR D B 1 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
4L2 HALL LIGHTS D B 6 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
4L3 HALL SOCKETS/ DADO LEFT HAND SIDE D B 8 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
5L1 HALL STAGE LIGHTS D B 2 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37
5L2 SPARE - - - - - - - - - - - -
5L3 SPARE - - - - - - - - - - - -
6L1 HALL STAGE LIGHTS D B 2 1.5 1.0 0.4 60898 MCB B 6 10 - 7.28
6L2 DOOR MAGS SUPPLY O C 1 2.5 1.5 0.4 60898 MCB C 16 10 - 1.37
6L3 SOCKET LEFT HAND SIDE D B 1 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
7L1 Supply to: DB C F E 1 25.0 25.0 5.0 60898 MCB C 63 10 - 0.35
7L2 Supply to: DB E F E 1 25.0 25.0 5.0 60898 MCB C 63 10 - 0.35
7L3 Supply to: DB D F E 1 25.0 25.0 5.0 60898 MCB C 63 10 - 0.35
8L1 Supply to: DB A F E 1 25.0 25.0 5.0 60898 MCB C 63 10 - 0.35
8L2 Supply to: DB B F E 1 25.0 25.0 5.0 60898 MCB C 63 10 - 0.35
8L3 LIGHTS CLASSROOM NEAR D B 8 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
9L123 Supply to: DB BH F C 1 6.0 C/S 5.0 60898 MCB C 20 10 - 1.09
10L123 SPARE - - - - - - - - - - - -
11L123 Supply to: DB F F C 1 25.0 C/S 5.0 60898 MCB C 63 10 - 0.35
12L123 ESP RIGHT HAND SIDE D B 1 16.0 16.0 5.0 60898 MCB D 63 10 - 0.35

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated FP200
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 24 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 1013402013
impedance

Original
* See note below
Operating times
Ö *0.15 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 3.0 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - 0.25 - - - 200 200 á 0.40 32.9 10.9 á


1L2 - - - LIM - - - 200 200 LIM - -
1L3 - - - LIM - - - 200 200 LIM - -
2L1 - - - 0.25 - - - 200 200 á 0.40 30.7 10.2 á
2L2 - - - - - - - - - - - -
2L3 - - - - - - - - - - - -
3L1 - - - 0.35 - - - 200 200 á 0.50 - -
3L2 - - - 0.39 - - - 200 200 á 0.54 - -
3L3 0.64 0.63 0.70 0.34 - - - 200 200 á 0.49 40.2 20.2 á
4L1 - - - 0.39 - - - 200 200 á 0.54 - -
4L2 - - - 0.34 - - - 200 200 á 0.49 - -
4L3 0.55 0.55 0.99 0.40 - - - 200 200 á 0.55 40.2 20.2 á
5L1 - - - 0.31 - - - 200 200 á 0.56 - -
5L2 - - - - - - - - - - - -
5L3 - - - - - - - - - - - -
6L1 - - - 0.44 - - - 200 200 á 0.59 - -
6L2 - - - 0.24 - - - 200 200 á 0.39 - -
6L3 - - - 0.11 - - - 200 200 á 0.26 20.4 28.5 á
7L1 - - - 0.10 - - - 200 200 á 0.25 - -
7L2 - - - 0.06 - - - 200 200 0.21 - -
7L3 - - - 0.03 - - - 200 200 á 0.18 - -
8L1 - - - 0.10 - - - 200 200 á 0.25 - -
8L2 - - - 0.10 - - - 200 200 á 0.25 - -
8L3 - - - 0.34 - - - 200 200 á 0.49 - -
9L123 - - - 0.17 - - - 200 200 á 0.32 - -
10L123 - - - - - - - - - - - -
11L123 - - - 0.15 - 200 200 200 200 á 0.30 - -
12L123 - - - 0.11 - 200 200 200 200 á 0.26 - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 25 of 78
Name: ANTHONY KNAPP Date of 21/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of NURSERY BREAKOUT ROOM Supply to distribution DB CARETAKERS No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB C Type: 60898 Rating: 63 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L123 SPARE - - - - - - - - - - - -
2L123 SPARE - - - - - - - - - - - -
3L123 SPARE - - - - - - - - - - - -
4L123 SPARE - - - - - - - - - - - -
5L123 SPARE - - - - - - - - - - - -
6L123 SPARE - - - - - - - - - - - -
7L1 SPARE *- - - - - - - - - - - -
7L2 SPARE - - - - - - - - - - - -
7L3 LIGHTS CORRIDOR A B 8 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37
8L1 SPARE - - - - - - - - - - - -
8L2 LIGHTS CORRIDOR A B 8 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37
8L3 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 26 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop N/A RCD N/A
impedance

Original
* See note below
Operating times
Ö *0.25 É At IÜ N/A ms Insulation N/A Multi 101393074
of associated resistance function
IÙ 1.80 kA RCD (if any) At 5IÜ N/A ms
*
Continuity N/A Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L123 - - - - - - - - - - - -
2L123 - - - - - - - - - - - -
3L123 - - - - - - - - - - - -
4L123 - - - - - - - - - - - -
5L123 - - - - - - - - - - - -
6L123 - - - - - - - - - - - -
7L1 - - - - - - - - - - - -
7L2 - - - - - - - - - - - -
7L3 - - - LIM - - - 200 200 LIM - -
8L1 - - - - - - - - - - - -
8L2 - - - LIM - - - 200 200 LIM - -
8L3 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 27 of 78
Name: MICHAEL DAVIES Date of 22/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of CLASS ROOM DOOR NO'12 Supply to distribution DB CARETAKERS No of Nominal 230
phases: 1 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB E Type: 60898 Rating: 63 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L2 LIGHTS ROOM NO'13 B B 9 2.5 M/F 0.4 60898 MCB B 10 10 - 4.37
2L2 LIGHTS STORE + STORE NEXT DOOR B B 2 2.5 M/F 0.4 60898 MCB B 10 10 - 4.37
3L2 LIGHTS ROOM NO'12 B B 9 2.5 M/F 0.4 60898 MCB B 10 10 - 4.37
4L2 LIGHTS ROOM NO'11 B B 8 2.5 M/F 0.4 60898 MCB B 10 10 - 4.37
5L2 LIGHTS ROOM NO'10 B B 8 2.5 M/F 0.4 60898 MCB B 10 10 - 4.37
6L2 LIGHTS CORRIDOR + ROOM NO'11 B B 7 2.5 M/F 0.4 60898 MCB B 10 10 - 4.37
7L2 LIGHTS MEDIA SUITE B B 6 2.5 M/F 0.4 60898 MCB B 10 10 - 4.37
8L2 SOCKETS NEXT STORE B B 1 4.0 4.0 0.4 61009 RCD/RCBO C 16 10 30 1.37
9L2 SPARE - - - - - - - - - - - -
10L2 SPARE - - - - - - - - - - - -
11L2 SPARE - - - - - - - - - - - -
12L2 SPARE - - - - - - - - - - - -
13L2 SPARE - - - - - - - - - - - -
14L2 SPARE - - - - - - - - - - - -
15L2 SPARE - - - - - - - - - - - -
16L2 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 28 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.21 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 2.20 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L2 - - - 0.20 - - - 200 200 á 0.41 - -


2L2 - - - 0.09 - - - 200 200 á 0.30 - -
3L2 - - - 0.18 - - - 200 200 á 0.39 - -
4L2 - - - 0.48 - - - 200 200 á 0.69 - -
5L2 - - - 0.51 - - - 200 200 á 0.72 - -
6L2 - - - 0.43 - - - 200 200 á 0.64 - -
7L2 - - - 0.48 - - - 200 200 á 0.69 - -
8L2 - - - 0.06 - - - 200 200 á 0.27 22.5 22.5 á
9L2 - - - - - - - - - - - -
10L2 - - - - - - - - - - - -
11L2 - - - - - - - - - - - -
12L2 - - - - - - - - - - - -
13L2 - - - - - - - - - - - -
14L2 - - - - - - - - - - - -
15L2 - - - - - - - - - - - -
16L2 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 29 of 78
Name: ANTHONY KNAPP Date of 21/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of CLASSROOM DOOR NO'12 Supply to distribution DB CARETAKERS No of Nominal 230


phases: 1 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB D Type: 60898 Rating: 63 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L3 SOCKETS MEDIA SUITE + ROOMS 10 + 11 B B 35 2 X 2.5 M/F 0.4 61009 RCD/RCBO C 32 10 30 0.68
2L3 SOCKETS ROOMS 12 + 13 B B 18 2 X 2.5 M/F 0.4 61009 RCD/RCBO C 32 10 30 0.68
3L3 SPARE - - - - - - - - - - - -
4L3 SPARE - - - - - - - - - - - -
5L3 SPARE - - - - - - - - - - - -
6L3 SPARE - - - - - - - - - - - -
7L3 SPARE - - - - - - - - - - - -
8L3 SPARE - - - - - - - - - - - -
9L3 SPARE - - - - - - - - - - - -
10L3 SPARE - - - - - - - - - - - -
11L3 SPARE - - - - - - - - - - - -
12L3 SPARE - - - - - - - - - - - -
13L3 SPARE - - - - - - - - - - - -
14L3 SPARE - - - - - - - - - - - -
15L3 SPARE - - - - - - - - - - - -
16L3 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 30 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.18 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 2.56 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L3 1.20 1.20 - 0.28 - - - 200 200 á 0.86 36.2 32.0 á


2L3 0.40 0.40 - 0.20 - - - 200 200 á 0.73 34.0 31.0 á
3L3 - - - - - - - - - - - -
4L3 - - - - - - - - - - - -
5L3 - - - - - - - - - - - -
6L3 - - - - - - - - - - - -
7L3 - - - - - - - - - - - -
8L3 - - - - - - - - - - - -
9L3 - - - - - - - - - - - -
10L3 - - - - - - - - - - - -
11L3 - - - - - - - - - - - -
12L3 - - - - - - - - - - - -
13L3 - - - - - - - - - - - -
14L3 - - - - - - - - - - - -
15L3 - - - - - - - - - - - -
16L3 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 31 of 78
Name: ANTHONY KNAPP Date of 21/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of RECEPTION AREA Supply to distribution DB CARETAKERS No of Nominal 230


phases: 1 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB A Type: 60898 Rating: 63 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 Supply to: DB AH H C 1 2.5 CASE 5.0 60898 MCB C 10 10 - 2.19
2L1 Supply to: DB A+2 H C 1 2.5 CASE 5.0 60898 MCB B 10 10 - 4.37
3L1 LIGHTS LIBRARY LOBBY B B 4 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
4L1 SOCKETS NEAR B B 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
5L1 LIGHTS LOBBY + ENTRANCE B B 25 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
6L1 UNKNOWN CIRCUIT B B LIM 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
7L1 LIGHTS STAIRS + TOILETS UPSTAIRS B B 11 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
8L1 UNKNOWN CIRCUIT O C LIM 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37
9L1 CORRIDOR LIGHTS O C 16 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37
10L1 LIGHTS HEADS OFFICE, STORE + ALARM B B 5 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
11L1 SPARE - - - - - - - - - - - -
12L1 SPARE - - - - - - - - - - - -
13L1 SPARE - - - - - - - - - - - -
14L1 SPARE - - - - - - - - - - - -
15L1 CORRIDOR LIGHTS O C 16 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37
16L1 CORRIDOR SPOTS A C 7 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 32 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.25 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 1.80 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - 0.01 - - - 200 200 á 0.26 - -


2L1 - - - 0.43 - - - 200 200 á 0.68 - -
3L1 - - - 0.21 - - - 200 200 á 0.46 - -
4L1 - - - 0.05 - - - 200 200 á 0.30 28.8 28.8 á
5L1 - - - 0.34 - - - 200 200 á 0.59 - -
6L1 - - - LIM - - - 200 200 LIM - -
7L1 - - - 0.44 - - - 200 200 á 0.69 - -
8L1 - - - LIM - - - 200 200 LIM - -
9L1 - - - 0.29 - - - 200 200 á 0.54 - -
10L1 - - - 0.31 - - - 200 200 á 0.56 - -
11L1 - - - - - - - - - - - -
12L1 - - - - - - - - - - - -
13L1 - - - - - - - - - - - -
14L1 - - - - - - - - - - - -
15L1 - - - 0.57 - - - 200 200 á 0.82 - -
16L1 - - - 0.64 - - - 200 200 á 0.89 - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 33 of 78
Name: ANTHONY KNAPP Date of 23/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of RECEPTION AREA Supply to distribution DB CARETAKERS No of Nominal 230


phases: 1 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB B Type: 60898 Rating: 63 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L2 SOCKETS HEADS OFFICE B B 9 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
2L2 CIRCUIT SWITCHED OFF LEFT OFF B B LIM 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
3L2 DADO HALL SOCKETS B B 5 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 20 10 30 2.19
4L2 SPARE - - - - - - - - - - - -
5L2 DATA CAB SOCKETS A C 2 2.5 1.5 0.4 60898 MCB B 20 10 - 2.19
6L2 SOCKETS DATA CAB ROOM B B 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
7L2 FIRE ALARM A C 1 2.5 1.5 0.4 60898 MCB C 20 10 - 1.09
8L2 UNKNOWN A C LIM 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
9L2 SPARE - - - - - - - - - - - -
10L2 SPARE - - - - - - - - - - - -
11L2 UNKNOWN B B LIM 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73
12L2 HALL CORRIDOR SOCKET O C 2 2.5 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
13L2 SOCKETS PART OFFICE + LOBBY B B 8 2.5 2.5 0.4 61009 RCD/RCBO C 20 10 30 1.09
14L2 UNKNOWN A C LIM 4.0 4.0 0.4 60898 MCB B 16 10 - 2.73
15L2 UNKNOWN A C LIM 4.0 4.0 0.4 61009 RCD/RCBO C 16 10 30 1.37
16L2 SPARE - - - - - - - - - - - -
17L2 SPARE - - - - - - - - - - - -
18L2 SPARE - - - - - - - - - - - -
19L2 SPARE - - - - - - - - - - - -
20L2 SPARE - - - - - - - - - - - -
21L2 Supply to: DB STAFF ROOM F C 1 6.0 6.0 5.0 60898 MCB B 32 10 - 1.37
22L2 UNKNOWN A C LIM 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37
23L2 UNKNOWN A C LIM 2.5 1.5 0.4 60898 MCB C 16 10 - 1.37
24L2 PSU LOBBY A C 1 2.5 1.5 0.4 60898 MCB C 16 10 - 1.37

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 34 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.25 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 1.80 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L2 0.72 0.71 0.96 0.42 - - - 200 200 á 0.67 28.4 28.4 á
2L2 0.66 0.69 0.00 LIM - - - 200 200 LIM LIM LIM
3L2 0.86 0.86 0.00 0.23 - - - 200 200 á 0.48 32.3 31.0 á
4L2 - - - - - - - - - - - -
5L2 - - - 0.07 - - - 200 200 á 0.32 - -
6L2 - - - 0.07 - - - 200 200 á 0.32 27.9 27.7 á
7L2 - - - 0.05 - - - 200 200 á 0.30 - -
8L2 - - - LIM - - - 200 200 LIM 30.2 28.6 á
9L2 - - - - - - - - - - - -
10L2 - - - - - - - - - - - -
11L2 - - - LIM - - - 200 200 LIM - -
12L2 - - - 0.21 - - - 200 200 á 0.46 28.6 28.6 á
13L2 - - - 0.13 - - - 200 200 á 0.39 28.2 31.0 á
14L2 - - - LIM - - - 200 200 LIM - -
15L2 - - - LIM - - - 200 200 LIM 28.7 28.4 á
16L2 - - - - - - - - - - - -
17L2 - - - - - - - - - - - -
18L2 - - - - - - - - - - - -
19L2 - - - - - - - - - - - -
20L2 - - - - - - - - - - - -
21L2 - - - 0.03 - - - 200 200 á 0.28 - -
22L2 - - - LIM - - - 200 200 LIM - -
23L2 - - - LIM - - - 200 200 LIM - -
24L2 - - - 0.04 - - - 200 200 á 0.29 - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 35 of 78
Name: ANTHONY KNAPP Date of 22/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of STAFFROOM ABOVE Supply to distribution DB B No of Nominal 230


phases: 1 V

Original
distribution board: RECEPTION board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB STAFF ROOM Type: 60898 Rating: 32 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L2 SOCKETS A C 12 2 X 2.5 2 X 1.5 0.4 60898 MCB B 32 6 - 1.37
2L2 WATER BOILER A C 1 2.5 1.5 0.4 60898 MCB B 20 6 - 2.19
3L2 ZIP BOLER A C 1 2.5 1.5 0.4 60898 MCB B 20 6 - 2.19
4L2 LIGHTS A C 11 1.5 1.0 0.4 60898 MCB B 10 6 - 4.37

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 36 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.28 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 0.82 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L2 0.66 0.65 1.11 0.45 - - - 200 200 á 0.73 - -


2L2 - - - 0.05 - - - 200 200 á 0.33 - -
3L2 - - - 0.06 - - - 200 200 á 0.34 - -
4L2 - - - 0.21 - - - 200 200 á 0.49 - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 37 of 78
Name: ANTHONY KNAPP Date of 23/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of OLD BOILER HOUSE Supply to distribution DB CARETAKERS No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB BH Type: 60898 Rating: 20 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 SPARE - - - - - - - - - - - -
1L2 SPARE - - - - - - - - - - - -
1L3 SPARE - - - - - - - - - - - -
2L1 SPARE - - - - - - - - - - - -
2L2 SPARE - - - - - - - - - - - -
2L3 SPARE - - - - - - - - - - - -
3L1 LIGHTS B B 6 1.5 1.5 0.4 60898 MCB C 6 10 - 3.64
3L2 RCD SOCKET D B 1 2.5 2.5 0.4 60898 MCB C 16 10 - 1.37
3L3 SPARE - - - - - - - - - - - -
4L123 BOILER PANEL B B 1 6.0 6.0 0.4 60898 MCB C 16 10 - 1.37

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 38 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.32 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 1.44 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - - - - - - - - - -
1L2 - - - - - - - - - - - -
1L3 - - - - - - - - - - - -
2L1 - - - - - - - - - - - -
2L2 - - - - - - - - - - - -
2L3 - - - - - - - - - - - -
3L1 - - - 0.14 - - - 200 200 á 0.46 - -
3L2 - - - 0.02 - - 200 200 200 á 0.34 - -
3L3 - - - - - - - - - - - -
4L123 - - - 0.02 - 200 200 200 200 á 0.34 - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 39 of 78
Name: ANTHONY KNAPP Date of 21/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of CLOAK ROOM SIDE Supply to distribution DB CARETAKERS No of Nominal 400


phases: 3 V

Original
distribution board: ENTRANCE board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB F Type: 60898 Rating: 63 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 BOILER INFANTS A C 1 4.0 1.5 0.4 60898 MCB C 20 10 - 1.09
1L2 BOILER JUNIORS A C 1 4.0 1.5 0.4 60898 MCB C 20 10 - 1.09
1L3 LIGHTS INFANTS + DWC A C 9 1.5 1.0 0.4 60898 MCB C 10 10 - 2.19
2L1 LIGHTS JUNIORS A C 10 1.5 1.0 0.4 60898 MCB C 10 10 - 2.19
2L2 LIGHTS CLOAK ROOM + EML A C 14 1.5 1.0 0.4 60898 MCB C 10 10 - 2.19
2L3 DATA CAB O C 1 1.5 1.0 0.4 60898 MCB B 16 10 - 2.73
3L1 PSU SUPPLY O C 1 2.5 1.5 0.4 60898 MCB C 16 10 - 1.37
3L2 HAND DRIER INFANTS A C 2 2.5 1.5 0.4 60898 MCB C 20 10 - 1.09
3L3 HAND DRIER JUNIORS A C 2 2.5 1.5 0.4 60898 MCB C 20 10 - 1.09
4L1 EXTRACT FAN JUNIORS A C 2 1.5 1.0 0.4 60898 MCB C 16 10 - 1.37
4L2 EXTRACT FAN INFANTS + DWC A C 3 1.5 1.0 0.4 60898 MCB C 16 10 - 1.37
4L3 SOCKETS CLOAK ROOM + CEILING SPUR A C 3 4.0/2.5 2 X 1.5 0.4 61009 RCD/RCBO C 16 10 30 1.37

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 40 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.30 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 1.5 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - 0.16 - - - 200 200 á 0.46 - -


1L2 - - - 0.29 - - - 200 200 á 0.59 - -
1L3 - - - 0.30 - - - 200 200 á 0.60 - -
2L1 - - - 0.55 - - - 200 200 á 0.85 - -
2L2 - - - 0.42 - - - 200 200 á 0.72 - -
2L3 - - - 0.06 - - - 200 200 á 0.36 - -
3L1 - - - 0.02 - - - 200 200 á 0.32 - -
3L2 - - - 0.19 - - - 200 200 á 0.49 - -
3L3 - - - 0.51 - - - 200 200 á 0.81 - -
4L1 - - - 0.30 - - - 200 200 á 0.60 - -
4L2 - - - 0.19 - - - 200 200 á 0.49 - -
4L3 - - - 0.16 - - - 200 200 á 0.46 38.6 19.1 á

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 41 of 78
Name: ANTHONY KNAPP Date of 21/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of GENTS W.C Supply to distribution MAIN PANEL 1 No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 14 Type: 60947-2 Rating: 100 A RCD No N/A IÜ mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 KITCHEN SOCKETS A C 12 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
1L2 TOILET LIGHTS A C 12 3 X 1.5 3 X 1.5 0.4 60898 MCB C 6 10 - 3.64
1L3 HALL SOCKETS A C 15 2 X 2.5 2 X 2.5 0.4 60898 MCB B 32 10 - 1.37
2L1 KITCHEN HOB A C 1 6.0 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
2L2 KITCHEN LIGHTS A C 6 1.5 1.5 0.4 60898 MCB C 6 10 - 3.64
2L3 HALL LIGHTS A C 10 1.5 1.5 0.4 60898 MCB C 6 10 - 3.64
3L1 KITCHEN OVENS A C 1 6.0 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
3L2 DOOR ACCESS A C 1 2.5 1.5 0.4 60898 MCB C 20 10 - 1.09
3L3 SPARE - - - - - - - - - - - -
4L1 BOILER KITCHEN A C 1 2.5 1.5 0.4 61009 RCD/RCBO C 20 10 30 1.09
4L2 SPARE - - - - - - - - - - - -
4L3 HEATER PANEL A C 1 4.0 4.0 0.4 60898 MCB B 16 10 - 2.73
5L123 SPARE - - - - - - - - - - - -
6L123 SPARE - - - - - - - - - - - -
7L123 SPARE - - - - - - - - - - - -
8L1 SPARE - - - - - - - - - - - -
8L2 SPARE - - - - - - - - - - - -
8L3 Supply to: DB RECEPTION F C 1 16.0 16.0 5.0 60898 MCB B 63 10 - 0.69

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 42 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.15 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 3.06 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 10134021 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 0.31 0.31 0.75 0.27 - - - 200 200 á 0.42 27.9 28.4 á
1L2 - - - 0.24 - - - 200 200 á 0.39 - -
1L3 0.90 0.90 0.96 0.47 - - - 200 200 á 0.42 - -
2L1 - - - 0.03 - - - 200 200 á 0.18 28.5 28.7 á
2L2 - - - 0.27 - - - 200 200 á 0.42 - -
2L3 - - - 0.45 - - - 200 200 á 0.60 - -
3L1 - - - 0.04 - - - 200 200 á 0.19 28.5 28.5 á
3L2 - - - 0.05 - - - 200 200 á 0.20 - -
3L3 - - - - - - - - - - - -
4L1 - - - 0.05 - - - 200 200 á 0.20 30.2 28.5 á
4L2 - - - - - - - - - - - -
4L3 - - - 0.08 - - - 200 200 á 0.23 - -
5L123 - - - - - - - - - - - -
6L123 - - - - - - - - - - - -
7L123 - - - - - - - - - - - -
8L1 - - - - - - - - - - - -
8L2 - - - - - - - - - - - -
8L3 - - - 0.01 - - - 200 200 á 0.16 - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 43 of 78
Name: ANTHONY KNAPP Date of 18/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of ENTRANCE LOBBY REAR Supply to distribution DB 14 No of Nominal 230


phases: 1 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB RECEPTION Type: 60898 Rating: 63 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L3 STORE ROOM SOCKETS A/C C/B 2 2.5 2.5 0.4 60898 MCB B 20 6 - 2.19
2L3 OFFICE SOCKETS A/C C/B 8 2.5 2.5 0.4 60898 MCB B 20 6 - 2.19
3L3 LIGHTS LOBBY + STORE A/C C/B 7 1.5 1.5 0.4 60898 MCB B 6 6 - 7.28
4L3 LIGHTS LOBBY + OFFICES A/C C/B 6 1.5 1.5 0.4 60898 MCB B 6 6 - 7.28
5L3 SOCKET BELOW A/C C/B 1 2.5 2.5 0.4 60898 MCB B 16 6 - 2.73
6L3 DOOR SUPPLY A/C C/B 1 1.5 1.5 0.4 60898 MCB B 6 6 - 7.28
7L3 SPARE - - - - - - - - - - - -
8L3 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 44 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.16 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 1.44 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L3 - - - 0.11 - - - 200 200 á 0.27 - -


2L3 - - - 0.14 - - - 200 200 á 0.30 - -
3L3 - - - LIM - - - 200 200 LIM - -
4L3 - - - LIM - - - 200 200 LIM - -
5L3 - - - 0.12 - - - 200 200 á 0.28 - -
6L3 - - - LIM - - - 200 200 LIM - -
7L3 - - - - - - - - - - - -
8L3 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 45 of 78
Name: ANTHONY KNAPP Date of 18/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of CLOAK ROOM Supply to distribution MAIN PANEL 1 No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB A1 Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 SOCKETS CLOAKS + CLASSROOM RHS A B 12 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
1L2 SOCKETS CLASSROOM LEFT HAND SIDE A B 10 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
1L3 SOCKETS CORRIDOR A C 2 2.5 1.5 0.4 61009 RCD/RCBO C 10 10 30 2.19
2L1 LIGHTS CLASS ROOM RIGHT HAND SIDE A C 4 2 X 1.5 2 X 1.0 0.4 60898 MCB C 10 10 - 2.19
2L2 LIGHTS CLASS ROOM LEFT HAND SIDE A C 6 2 X 2.5 2 X 1.0 0.4 60898 MCB C 10 10 - 2.19
2L3 LIGHTS CORRIDOR A C 9 2 X 1.5 2 X 1.0 0.4 60898 MCB C 10 10 - 2.19
3L1 LIGHTS CLOAKS + W.C A C 7 2 X 1.5 2 X 1.0 0.4 60898 MCB C 10 10 - 2.19
3L2 HAND DRIER W.C A C 1 4.0 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
3L3 HAND DRIER W.C A C 1 4.0 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
4L1 LIGHTS CLASS ROOM RIGHT HAND SIDE A C 2 2.5 1.5 0.4 60898 MCB C 10 10 - 2.19
4L2 LIGHTS CLASS ROOM LEFT HAND SIDE A C 3 2.5 1.5 0.4 60898 MCB C 10 10 - 2.19
4L3 HAND DRIER W.C A C 1 4.0 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
5L1 HAND DRIER W.C A C 1 4.0 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
5L2 WATER HEATER CLASS ROOM A C 1 4.0 2.5 0.4 60898 MCB C 16 10 - 1.37
5L3 WATER HEATER CLASS ROOM A C 1 4.0 2.5 0.4 60898 MCB B 16 10 - 2.73
6L1 VENTILATION FCU A B 1 4.0 2.5 0.4 60898 MCB B 16 10 - 2.73
6L2 DISABLED ALARM A C 1 2.5 1.5 0.4 60898 MCB B 16 10 - 2.73
6L3 ALARM + DOOR CONTROL A C 2 4.0 2.5 0.4 60898 MCB B 16 10 - 2.73
7L1 HAND DRIER A C 1 4.0 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
7L2 LIGHTS STAIRS + STORE A B 5 2 X 1.5 2 X 1.0 0.4 60898 MCB C 10 10 - 2.19
7L3 SOCKETS STORE A B 2 2.5 1.5 0.4 61009 RCD/RCBO C 10 10 30 2.19
8L1 DATA CAB A B 1 4.0 2.5 0.4 60898 MCB B 16 10 - 2.73
8L2 CONTACTOR/TIME CLOCK A B 1 2.5 1.5 0.4 60898 MCB B 6 10 - 7.28
8L3 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 46 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101393074 RCD 101393074
impedance

Original
* See note below
Operating times
Ö *0.17 É At IÜ N/A ms Insulation 101393074 Multi N/A
of associated resistance function
IÙ 2.68 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101393074 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 0.93 0.93 1.56 0.52 - - - 200 200 á 0.69 59.9 29.9 á
1L2 0.64 0.65 1.09 0.40 - - - 200 200 á 0.57 30.0 15.8
1L3 - - - 0.17 - - - 200 200 á 0.34 28.7 9.1 á
2L1 - - - LIM - - - 200 200 LIM - -
2L2 - - - LIM - - - 200 200 LIM - -
2L3 - - - LIM - - - 200 200 LIM - -
3L1 - - - LIM - - - 200 200 LIM - -
3L2 - - - 0.11 - - - 200 200 á 0.28 29.2 9.31
3L3 - - - 0.09 - - - 200 200 á 0.26 46.8 9.31
4L1 - - - LIM - - - 200 200 LIM - -
4L2 - - - LIM - - - 200 200 LIM - -
4L3 - - - 0.12 - - - 200 200 á 0.29 29.0 9.11 á
5L1 - - - 0.12 - - - 200 200 á 0.29 46.1 9.31 á
5L2 - - - 0.16 - - - 200 200 á 0.33 - -
5L3 - - - 0.14 - - - 200 200 á 0.31 - -
6L1 - - - 0.27 - - - 200 200 á 0.44 - -
6L2 - - - 0.21 - - - 200 200 á 0.38 - -
6L3 - - - 0.38 - - - 200 200 á 0.55 - -
7L1 - - - 0.10 - - - 200 200 á 0.27 36.7 9.40 á
7L2 - - - LIM - - - 200 200 LIM - -
7L3 - - - 0.32 - - - 200 200 á 0.49 41.2 23.8 á
8L1 - - - 0.08 - - - 200 200 á 0.25 - -
8L2 - - - 0.02 - - - 200 200 á 0.19 - -
8L3 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 47 of 78
Name: MICHAEL DAVIES Date of 18/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of METER STORE GROUND Supply to distribution MAIN PANEL 1 No of Nominal 400
phases: 3 V

Original
distribution board: LEVEL board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution MAIN PANEL 2 SWITCH FUS Type: 60947-2 Rating: 200 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L123 Supply to: MAIN PANEL 2 G C 1 95.0 50.0 5.0 88 Fuse HRC 2 160 80 - 0.27

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 48 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340213 RCD 101340213
impedance

Original
* See note below
Operating times
Ö *0.04 É At IÜ N/A ms Insulation 101340211 Multi N/A
of associated resistance function
IÙ 11.5 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340211 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L123 - - - 0.06 - 200 200 200 200 á 0.10 - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Test Engineer
Page 49 of 78
Name: ANTHONY KNAPP Date of 18/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of UNDER CROFT CORRIDOR Supply to distribution MAIN PANEL 2 SWITCH FUSE No of Nominal 400
phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution MAIN PANEL 2 Type: 88-2 Rating: 160 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L123 Supply to: DB 0/2/A G B 1 25.0 16.0 5.0 60947-2 MCCB 2 80 25 - 0.18
2L123 Supply to: DB 0/2/E G B 1 25.0 25.0 5.0 60947-2 MCCB 2 100 25 - 0.42
3L123 SPARE - - - - - - - - - - - -
4L123 Supply to: DB 0/2/B G B 1 35.0 25.0 5.0 60947-2 MCCB 2 100 25 - 0.42
5L123 Supply to: DB 0/2/MCPA G B 1 25.0 16.0 5.0 60947-2 MCCB 2 100 25 - 0.42
6L123 SPARE - - - - - - - - - - - -
7L123 SPARE - - - - - - - - - - - -
8L123 DB 0/2 A B 1 25.0 50.0 5.0 60947-2 MCCB 2 100 25 - 0.42
9L123 Supply to: DB 0/2/C G B 1 35.0 35.0 5.0 60947-2 MCCB 2 100 25 - 0.42
10L123 SPARE - - - - - - - - - - - -
11L123 SPARE - - - - - - - - - - - -
12L123 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 50 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop N/A RCD N/A
impedance

Original
* See note below
Operating times
Ö *0.10 É At IÜ N/A ms Insulation N/A Multi 101617007
of associated resistance function
IÙ 3.13 kA RCD (if any) At 5IÜ N/A ms
*
Continuity N/A Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L123 - - - 0.01 - 200 200 200 200 á 0.11 - -


2L123 - - - 0.04 - 200 200 200 200 á 0.14 - -
3L123 - - - - - - - - - - - -
4L123 - - - 0.04 - 200 200 200 200 á 0.14 - -
5L123 - - - 0.07 - 200 200 200 200 á 0.17 - -
6L123 - - - - - - - - - - - -
7L123 - - - - - - - - - - - -
8L123 - - - 0.01 - 200 200 200 200 á 0.11 - -
9L123 - - - 0.04 - 200 200 200 200 á 0.14 - -
10L123 - - - - - - - - - - - -
11L123 - - - - - - - - - - - -
12L123 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 51 of 78
Name: MARK PERRY Date of 24/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of TOILET AREA Supply to distribution MAIN PANEL 2 No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 0/2/A Type: 60947-2 Rating: 80 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 GIRLS + BOY W.C LIGHTS A A 22 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
1L2 STAFF, DISABLED, CLEANERS + CORRIDOR LIGHTS A A 5 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
1L3 LIGHTS DINING HALL ROWS 1-3 A A 17 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
2L1 SPARE - - - - - - - - - - - -
2L2 SPARE - - - - - - - - - - - -
2L3 LIGHTS DINING HALL ROWS 4-6 A A 10 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 52 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop N/A RCD N/A
impedance

Original
* See note below
Operating times
Ö *0.11 É At IÜ N/A ms Insulation 101340210 Multi N/A
of associated resistance function
IÙ 4.2 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340210 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - LIM - - - 200 200 LIM - -


1L2 - - - LIM - - - 200 200 LIM - -
1L3 - - - LIM - - - 200 200 LIM - -
2L1 - - - - - - - - - - - -
2L2 - - - - - - - - - - - -
2L3 - - - LIM - - - 200 200 LIM - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 53 of 78
Name: JOE LACEY Date of 21/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of TOILET AREA Supply to distribution DB 0/2/A LIVE SIDE No of Nominal 400
phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 0/2/A1 Type: 60947-2 Rating: 80 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L123 LIFT G A 1 16.0 16.0 5.0 60898 MCB B 50 10 - 0.87
2L1 LIFT G A 1 6.0 6.0 0.4 61009 RCD/RCBO C 32 10 30 0.68
2L2 DINING HALL SOCKETS A A 3 2.5 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
2L3 DINING HALL HR02 HR03 + HR04 A A 3 2.5 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
3L1 BOYS W.C FC04 + GIRLS W.C A A 2 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
3L2 GIRLS W.C FC05 A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
3L3 E5 + E5 CONSTANT DAMPERS A A 2 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
4L1 FEMALE STAFF HAND DRIER A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
4L2 GIRLS W.C HAND DRIER A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
4L3 MALE STAFF HAND DRIER A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
5L1 BOYS W.C HAND DRIER A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
5L2 DISABLED W.C ALARM + HAND DRIER A A 2 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
5L3 UNKNOWN A A LIM 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73
6L123 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 54 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340212 RCD 101340212
impedance

Original
* See note below
Operating times
Ö *0.13 É At IÜ 38.4 ms Insulation 101340210 Multi N/A
of associated resistance function
IÙ 3.84 kA RCD (if any) At 5IÜ 28.4 ms
*
Continuity 101340210 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L123 - - LIM - - - 200 200 LIM - -


2L1 - - - LIM - - - 200 200 LIM LIM LIM
2L2 0.97 0.96 0.55 0.27 - - - 200 200 á 0.40 38.4 28.4 á
2L3 - - - LIM - - - 200 200 LIM LIM LIM
3L1 - - - LIM - - - 200 200 LIM LIM LIM
3L2 - - - LIM - - - 200 200 LIM LIM LIM
3L3 - - - LIM - - - 200 200 LIM LIM LIM
4L1 - - - 0.39 - - - 200 200 á 0.52 38.4 27.6 á
4L2 - - - 0.33 - - - 200 200 á 0.46 38.4 28.4 á
4L3 - - - 0.36 - - - 200 200 á 0.49 38.4 28.4 á
5L1 - - - 0.28 - - - 200 200 á 0.41 38.4 28.5 á
5L2 - - - 0.23 - - - 200 200 á 0.36 38.5 28.6 á
5L3 - - - LIM - - - 200 200 LIM - -
6L123 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 55 of 78
Name: JOE LACEY Date of 21/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of KITCHEN Supply to distribution MAIN PANEL 2 No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 0/2/E Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L123 INDUCTION HOB A A 1 6.0 6.0 0.4 60898 MCB C 32 10 - 0.68
2L123 STEAMER 1 A A 1 6.0 6.0 0.4 60898 MCB C 32 10 - 0.68
3L123 STEAMER 2 A A 1 6.0 6.0 0.4 60898 MCB C 32 10 - 0.68
4L123 DISHWASHER A A 1 6.0 6.0 0.4 60898 MCB C 32 10 - 0.68
5L1 EXTRACT HOOD A A 1 2.5 2.5 0.4 60898 MCB C 16 10 - 1.37
5L2 UPRIGHT FRIDGE A A 1 2.5 2.5 0.4 60898 MCB C 16 10 - 1.37
5L3 CHEST FREEZER A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
6L1 KITCHEN CONTROL OFFICE A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
6L2 KITCHEN SOCKETS A A 2 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
6L3 OFFICE SOCKETS A A 2 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
7L1 MIXER A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
7L2 UPRIGHT FRIDGE A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
7L3 CHEST FREEZER A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
8L1 SERVERY A A 1 2.5 2.5 0.4 60898 MCB C 16 10 30 1.37
8L2 W.C EXTRACT A A 1 2.5 2.5 0.4 60898 MCB C 16 10 30 1.37
8L3 SPARE - - - - - - - - - - - -
9L1 SERVERY A A 1 2.5 2.5 0.4 60898 MCB C 16 10 - 1.37
9L2 SPARE - - - - - - - - - - - -
9L3 SPARE - - - - - - - - - - - -
10L1 EXTRACTOR HOOD LIGHTING A A 1 2.5 2.5 0.4 60898 MCB C 16 10 - 1.37
10L2 EXTRACT EF02 A A 1 2.5 2.5 0.4 60898 MCB C 16 10 - 1.37
10L3 W.C HAND DRIER A A 1 2.5 2.5 0.4 60898 MCB C 16 10 - 1.37
11L1 KITCHEN CONTROL OLD A A 1 2.5 2.5 0.4 60898 MCB C 16 10 - 1.37
11L2 SPARE - - - - - - - - - - - -
11L3 SPARE - - - - - - - - - - - -
12L123 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 56 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340212 RCD 101340212
impedance

Original
* See note below
Operating times
Ö *0.14 É At IÜ N/A ms Insulation 101340210 Multi N/A
of associated resistance function
IÙ 3.28 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340210 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L123 - - - 0.19 - - - 200 200 á 0.33 - -


2L123 - - - 0.22 - - - 200 200 á 0.36 - -
3L123 - - - 0.20 - - - 200 200 á 0.34 - -
4L123 - - - 0.16 - - - 200 200 á 0.30 - -
5L1 - - - LIM - - - 200 200 LIM - -
5L2 - - - 0.15 - - - 200 200 á 0.28 - -
5L3 - - - 0.19 - - - 200 200 á 0.33 38.4 26.4 á
6L1 - - - 0.33 - - - 200 200 á 0.47 38.7 28.4 á
6L2 0.52 0.53 0.26 0.13 - - - 200 200 á 0.27 28.7 18.4 á
6L3 0.29 0.29 0.28 0.18 - - - 200 200 á 0.32 38.4 28.4 á
7L1 - - - 0.03 - - - 200 200 á 0.17 38.7 28.7 á
7L2 - - - 0.14 - - - 200 200 á 0.28 38.6 28.4 á
7L3 - - - 0.16 - - - 200 200 á 0.30 38.7 28.6 á
8L1 - - - 0.28 - - - 200 200 á 0.42 - -
8L2 - - - LIM - - - 200 200 LIM - -
8L3 - - - - - - - - - - - -
9L1 - - - 0.23 - - - 200 200 á 0.37 - -
9L2 - - - - - - - - - - - -
9L3 - - - - - - - - - - - -
10L1 - - - LIM - - - 200 200 LIM - -
10L2 - - - LIM - - - 200 200 LIM - -
10L3 - - - 0.32 - - - 200 200 á 0.46 - -
11L1 - - - LIM - - - 200 200 LIM - -
11L2 - - - - - - - - - - - -
11L3 - - - - - - - - - - - -
12L123 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 57 of 78
Name: JOE LACEY Date of 22/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of KITCHEN Supply to distribution DB 0/2/E LIVE SIDE No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 0/2/E1 Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 KITCHEN LIGHTS A A 9 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
1L2 BACK ROOM LIGHTS A A 5 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
1L3 SPARE - - - - - - - - - - - -
2L123 SPARE - - - - - - - - - - - -
3L123 SPARE - - - - - - - - - - - -
4L123 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 58 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340212 RCD 101340212
impedance

Original
* See note below
Operating times
Ö *0.13 É At IÜ N/A ms Insulation 101340210 Multi N/A
of associated resistance function
IÙ 4.6 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340210 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - LIM - - - 200 200 LIM - -


1L2 - - - LIM - - - 200 200 LIM - -
1L3 - - - - - - - - - - - -
2L123 - - - - - - - - - - - -
3L123 - - - - - - - - - - - -
4L123 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 59 of 78
Name: JOE LACEY Date of 22/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of UNDER CROFT CORRIDOR Supply to distribution MAIN PANEL 2 No of Nominal 400
phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 0/2/B Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 CLASS U1 SOCKETS B B 7 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
1L2 CLASS U2 SOCKETS B B 8 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
1L3 CLASS U3 SOCKETS B B 8 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
2L1 CLASS U1 WATER HEATER B B 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
2L2 CLASS U2 WATER HEATER B B 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
2L3 CLASS U3 WATER HEATER B B 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
3L1 CLASS U1 HRV 85+86 B B 2 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
3L2 CLASS U2 HRV 07+08 B B 2 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
3L3 CLASS U3 HRV 09+10 B B 2 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
4L1 HALLWAY SOCKETS B B 4 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
4L2 DOOR ACCESS PSU B B 1 2.5 2.5 0.4 60898 MCB C 10 10 30 2.19
4L3 UNKNOWN B B LIM 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 60 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop N/A RCD N/A
impedance

Original
* See note below
Operating times
Ö *0.14 É At IÜ N/A ms Insulation N/A Multi 101617007
of associated resistance function
IÙ 3.12 kA RCD (if any) At 5IÜ N/A ms
*
Continuity N/A Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 0.33 0.32 0.35 0.18 - - 200 200 200 á 0.32 28.6 9.7 á
1L2 0.29 0.26 0.30 0.14 - - 200 200 200 á 0.28 28.8 10.4 á
1L3 0.32 0.33 0.31 0.18 - - 200 200 200 á 0.32 27.4 8.8
2L1 - - - 0.25 - - 200 200 200 á 0.39 27.7 10.1 á
2L2 - - - 0.27 - - 200 200 200 á 0.41 26.9 9.9 á
2L3 - - - 0.32 - - 200 200 200 á 0.46 28.5 11.3 á
3L1 - - - LIM - - - 200 200 LIM LIM LIM
3L2 - - - LIM - - - 200 200 LIM LIM LIM
3L3 - - - LIM - - - 200 200 LIM LIM LIM
4L1 0.23 0.25 0.24 0.14 - - 200 200 200 á 0.28 28.6 9.4 á
4L2 - - - 0.16 - - 200 200 200 á 0.30 - -
4L3 - - - LIM - - - 200 200 LIM - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 61 of 78
Name: MARK PERRY Date of 23/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of UNDER CROFT CORRIDOR Supply to distribution DB 0/2/B LIVE SIDE No of Nominal 400
phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 0/2/B1 Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 LIGHTING CLASS U1 B B 11 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
1L2 LIGHTING CLASS U2 B B 13 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
1L3 LIGHTING CLASS U3 B B 11 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
2L1 LIGHTING U1, U2 + U3 W.C'S B B 10 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
2L2 LIGHTING EXTERNAL B B 5 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
2L3 LIGHTING EXTERNAL B B 4 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
3L1 LIGHTING EXTERNAL TIME CLOCK B B 1 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
3L2 SPARE - - - - - - - - - - - -
3L3 SPARE - - - - - - - - - - - -
4L123 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 62 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop N/A RCD N/A
impedance

Original
* See note below
Operating times
Ö *0.14 É At IÜ N/A ms Insulation N/A Multi 101617007
of associated resistance function
IÙ 3.12 kA RCD (if any) At 5IÜ N/A ms
*
Continuity N/A Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - LIM - - - 200 200 LIM - -


1L2 - - - LIM - - - 200 200 LIM - -
1L3 - - - LIM - - - 200 200 LIM - -
2L1 - - - LIM - - - 200 200 LIM - -
2L2 - - - LIM - - - 200 200 LIM - -
2L3 - - - LIM - - - 200 200 LIM - -
3L1 - - - LIM - - - 200 200 LIM - -
3L2 - - - - - - - - - - - -
3L3 - - - - - - - - - - - -
4L123 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 63 of 78
Name: MARK PERRY Date of 24/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of BOILER HOUSE Supply to distribution MAIN PANEL 2 No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 0/2/MCPA Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L123 BMS PANEL B B 1 16.0 10.0 5.0 60898 MCB C 40 10 - 0.55
2L1 PLANT ROOM SOCKETS B B 2 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
2L2 PLANT ROOM LIGHTING + EML B B 2 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
2L3 STORM PUMP B B 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
3L1 EXTERNAL CONDENSER A.C G B 1 6.0 6.0 5.0 60898 MCB C 40 10 - 0.55
3L2 EXTERNAL LIGHTING G B 3 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
3L3 PILLER G B 2 2.5 2.5 0.4 60898 MCB C 16 10 - 1.37
4L123 FOUL PUMP G B 1 2.5 2.5 0.4 60898 MCB C 16 10 - 1.37

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 64 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop N/A RCD N/A
impedance

Original
* See note below
Operating times
Ö *0.17 É At IÜ N/A ms Insulation N/A Multi 101617007
of associated resistance function
IÙ 2.6 kA RCD (if any) At 5IÜ N/A ms
*
Continuity N/A Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L123 - - - 0.01 - 200 200 200 200 á 0.18 - -


2L1 0.11 0.12 0.11 0.07 - - 200 200 200 á 0.24 23.3 9.7 á
2L2 - - - 0.19 - - - 200 200 á 0.36 - -
2L3 - - - 0.02 - - 200 200 200 á 0.19 28.7 17.4 á
3L1 - - - LIM - - - 200 200 LIM - -
3L2 - - - 0.14 - - 200 200 200 á 0.31 - -
3L3 - - - 0.43 - - 200 200 200 á 0.60 - -
4L123 - - - 0.08 - 200 - 200 200 á 0.25 - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 65 of 78
Name: MARK PERRY Date of 24/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of CLOAK ROOM Supply to distribution MAIN PANEL 2 No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 0/2/C Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 CLASS U4 LIGHTS A A 8 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
1L2 CLASS U5 LIGHTS A A 8 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
1L3 CORRIDOR LIGHTS A A 14 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
2L1 CORRIDOR LIGHTS A A 4 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
2L2 ICT LIGHTS A A 11 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
2L3 CLASS U6 LIGHTS A A 10 1.5 1.5 0.4 60898 MCB C 10 10 - 2.19
3L123 SPARE - - - - - - - - - - - -
4L123 SPARE - - - - - - - - - - - -
5L1 CLASS U4 SOCKETS A E 5 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
5L2 CLASS U5 A E 6 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
5L3 ICT SOCKETS A E 7 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
6L1 CLOAK HRV 19 A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
6L2 CLASS U6 SOCKETS A E 9 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
6L3 EXT CONDENSER - OVO1 A A 1 4.0 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
7L1 CLASS U4 WATER HEATER A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
7L2 CLASS U5 WATER HEATER A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
7L3 SPARE - - - - - - - - - - - -
8L1 CLASS U4 HRV 13+14 A A 2 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
8L2 CLASS U6 WATER HEATER A A 1 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
8L3 SPARE - - - - - - - - - - - -
9L1 CORRIDOR SOCKETS A E 8 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO B 32 10 30 1.37
9L2 CLASS U5 HRV 13 + 14 A A 2 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
9L3 CLASS ICT HRV 15 + 16 A A 2 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
10L1 SPARE - - - - - - - - - - - -
10L2 CLASS U6 HRV 17+ 18 A A 2 2.5 2.5 0.4 61009 RCD/RCBO C 16 10 30 1.37
10L3 SPARE - - - - - - - - - - - -

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 66 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop 101340212 RCD 101340212
impedance

Original
* See note below
Operating times
Ö *0.14 É At IÜ N/A ms Insulation 101340210 Multi N/A
of associated resistance function
IÙ 3.28 kA RCD (if any) At 5IÜ N/A ms
*
Continuity 101340210 Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - LIM - - - 200 200 LIM - -


1L2 - - - LIM - - - 200 200 LIM - -
1L3 - - - LIM - - - 200 200 LIM - -
2L1 - - - LIM - - - 200 200 LIM - -
2L2 - - - LIM - - - 200 200 LIM - -
2L3 - - - LIM - - - 200 200 LIM - -
3L123 - - - - - - - - - - - -
4L123 - - - - - - - - - - - -
5L1 0.87 0.87 0.77 0.31 - - - 200 200 á 0.45 38.4 28.5 á
5L2 0.72 0.72 0.74 0.24 - - - 200 200 á 0.38 38.4 28.5 á
5L3 0.78 0.78 0.59 0.26 - - - 200 200 á 0.40 28.6 28.6 á
6L1 - - - LIM - - - 200 200 LIM LIM LIM
6L2 0.67 0.67 0.57 0.16 - - - 200 200 á 0.30 28.7 28.4 á
6L3 - - - LIM - - - 200 200 LIM LIM LIM
7L1 - - - 0.27 - - - 200 200 á 0.41 36.5 25.4 á
7L2 - - - 0.30 - - - 200 200 á 0.44 38.2 26.7 á
7L3 - - - - - - - - - - - -
8L1 - - - LIM - - - 200 200 LIM LIM LIM
8L2 - - - 0.37 - - - 200 200 á 0.51 37.2 27.4 á
8L3 - - - - - - - - - - - -
9L1 0.69 0.68 0.36 0.18 - - - 200 200 á 0.32 38.4 28.4 á
9L2 - - - LIM - - - 200 200 LIM LIM LIM
9L3 - - - LIM - - - 200 200 LIM LIM LIM
10L1 - - - - - - - - - - - -
10L2 - - - LIM - - - 200 200 LIM LIM LIM
10L3 - - - - - - - - - - - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 67 of 78
Name: JOE LACEY Date of 23/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of 304 ROOM STORE Supply to distribution MAIN PANEL 1 No of Nominal 400
phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 13A Type: 60947-2 Rating: 100 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 LIGHTING 304 A B 8 1.5 1.0 0.4 60898 MCB B 10 10 - 4.37
1L2 LIGHTING 307 B B 12 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
1L3 LIGHTING 034 EML NEAR OFFICE B B 13 1.5 1.5 0.4 60898 MCB B 6 10 - 7.28
2L1 SOCKETS 304 + ENTRANCE A B 5 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
2L2 DISABLED WATER HEATER D B 1 4.0 4.0 0.4 60898 MCB B 16 10 - 2.73
2L3 LIGHTING MAIN OFFICE + REAR STORES B B 10 1.5 1.5 0.4 60898 MCB B 6 10 - 7.28
3L1 SOCKETS CORRIDOR 311 A B 2 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
3L2 FRIDGE 307 A B 1 2.5 1.5 0.4 60898 MCB B 16 10 - 2.73
3L3 SOCKETS 59, 60A, 054, 058, 301 + PSU B B 24 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
4L123 Supply to: DB 13 D B 1 10.0 46.0 5.0 60898 MCB C 40 10 - 0.55
5L1 UNKNOWN LIM LIM LIM LIM LIM 0.4 60898 MCB B LIM LIM LIM LIM
5L2 UNKNOWN LIM LIM LIM LIM LIM 0.4 60898 MCB B LIM LIM LIM LIM
5L3 SPARE - - - - - - - - - - - -
6L1 A.C MAIN OFFICE B B 2 2.5 2.5 0.4 60898 MCB B 20 10 - 2.19
6L2 WATER HEATER 307 D B 1 4.0 4.0 0.4 60898 MCB B 16 10 - 2.73
6L3 SPARE - - - - - - - - - - - -
7L1 DISABLED ALARM D B 1 4.0 4.0 0.4 60898 MCB B 16 10 - 2.73
7L2 COOKER 307 D B 1 10.0 4.0 5.0 60898 MCB B 40 10 - 1.09
7L3 UNKNOWN LIM LIM LIM LIM LIM 0.4 61009 RCD/RCBO C LIM LIM LIM LIM
8L1 CONTRACTOR VIA TIME CLOCK D B 1 1.5 1.5 0.4 60898 MCB B 6 10 - 7.28
8L2 SOCKETS 307 D B 7 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
8L3 SOCKETS BELOW B B 2 2 X 2.5 2 X 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 68 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop N/A RCD N/A
impedance

Original
* See note below
Operating times
Ö *0.16 É At IÜ N/A ms Insulation N/A Multi 101617007
of associated resistance function
IÙ 2.8 kA RCD (if any) At 5IÜ N/A ms
*
Continuity N/A Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - 0.16 - - - 200 200 á 0.37 - -


1L2 - - - 0.35 - - - 200 200 á 0.51 - -
1L3 - - - 0.62 - - - 200 200 á 0.78 - -
2L1 0.45 0.45 0.68 0.39 - - 200 200 200 á 0.55 36.3 14.5 á
2L2 - - - 0.15 - - 200 200 200 á 0.31 - -
2L3 - - - 0.87 - - - 200 200 á 1.03 - -
3L1 0.28 0.33 0.41 0.16 - - 200 200 200 á 0.32 21.3 12.6 á
3L2 - - - 0.23 - - 200 200 200 á 0.39 - -
3L3 0.50 0.55 0.77 0.49 - - - 200 200 á 0.65 FAIL 19.1 á
4L123 - - - 0.01 - 200 200 200 200 á 0.17 - -
5L1 - - - LIM - - - 200 200 LIM - -
5L2 - - - LIM - - - 200 200 LIM - -
5L3 - - - - - - - - - - - -
6L1 - - - 0.33 - - 200 200 200 á 0.49 - -
6L2 - - - 0.12 - - 200 200 200 á 0.28 - -
6L3 - - - - - - - - - - - -
7L1 - - - 0.13 - - 200 200 200 á 0.29 - -
7L2 - - - 0.11 - - 200 200 200 á 0.27 - -
7L3 - - - LIM - - 200 200 200 LIM - -
8L1 - - - 0.04 - - 200 200 200 á 0.20 - -
8L2 0.36 0.36 0.37 0.10 - - 200 200 200 á 0.26 28.7 9.6 á
8L3 0.03 0.04 0.06 0.03 - - 200 200 200 á 0.21 24.3 8.7 á

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 69 of 78
Name: MARK PERRY Date of 21/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of ROOM 304 Supply to distribution DB 13A No of Nominal 400


phases: 3 V

Original
distribution board: board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB 13 Type: 60898 Rating: 40 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 LIGHTING CORRIDOR 311 D B 8 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
1L2 LIGHTING 303-306 D B 12 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
1L3 SPARE - - - - - - - - - - - -
2L1 PSU'S OPPOSITE THIS ROOM D B 1 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73
2L2 LIGHTING DISABLED W.C + CORRIDOR D B 7 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
2L3 SPARE - - - - - - - - - - - -
3L1 SPARE - - - - - - - - - - - -
3L2 SOCKETS 306 D B 7 2.5 1.5 0.4 61009 RCD/RCBO C 32 10 30 0.68
3L3 DBH CONTACTOR CONTROL D B 1 1.5 1.5 0.4 60898 MCB B 6 10 - 7.28
4L123 SPARE - - - - - - - - - - - -
5L1 HIGH LEVEL SPUR 306 A C 1 1.5 1.0 0.4 60898 MCB B 6 10 - 7.28
5L2 WATER HEATER 306 D B 1 4.0 4.0 0.4 60898 MCB B 16 10 - 2.73
5L3 PROJECTOR SPUR + SOCKETS 301 D B 2 2.5 2.5 0.4 60898 MCB B 16 10 - 2.73
6L1 SPARE - - - - - - - - - - - -
6L2 DOOR BELL ENTRANCE A B 1 2.5 1.5 0.4 60898 MCB B 16 10 - 2.73
6L3 SPARE - - - - - - - - - - - -
7L1 ALARM PSU BELOW O C 1 1.5 1.5 0.4 60898 MCB B 16 10 - 2.73
7L2 RIGHT HAND SIDE PSU ENTRANCE 303 A B 1 2.5 1.5 0.4 60898 MCB B 16 10 - 2.73
7L3 LIGHTING 301 D B 12 1.5 1.5 0.4 60898 MCB B 10 10 - 4.37
8L1 SPARE - - - - - - - - - - - -
8L2 LEFT HAND SIDE ENTRANCE 303 A B 1 2.5 1.5 0.4 60898 MCB B 16 10 - 2.73
8L3 DADO SOCKETS 301 D B 5 2 X 2.5 2 X 2.5 0.4 61009 RCD/RCBO C 32 10 30 0.68

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated FP200
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 70 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop N/A RCD N/A
impedance

Original
* See note below
Operating times
Ö *0.17 É At IÜ N/A ms Insulation N/A Multi 101617007
of associated resistance function
IÙ 2.74 kA RCD (if any) At 5IÜ N/A ms
*
Continuity N/A Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - 0.79 - - - 200 200 á 0.96 - -


1L2 - - - 0.26 - - - 200 200 á 0.43 - -
1L3 - - - - - - - - - - - -
2L1 - - - 0.04 - - - 200 200 á 0.21 - -
2L2 - - - 0.31 - - - 200 200 á 0.48 - -
2L3 - - - - - - - - - - - -
3L1 - - - - - - - - - - - -
3L2 0.41 0.43 0.62 0.26 - - 200 200 200 á 0.43 39.7 17.4 á
3L3 - - - 0.02 - - 200 200 200 á 0.19 - -
4L123 - - - - - - - - - - - -
5L1 - - - 0.11 - - 200 200 200 á 0.28 - -
5L2 - - - 0.14 - - 200 200 200 á 0.31 - -
5L3 - - - 0.35 - - 200 200 200 á 0.52 - -
6L1 - - - - - - - - - - - -
6L2 - - - LIM - - - 200 200 LIM - -
6L3 - - - - - - - - - - - -
7L1 - - - 0.02 - - 200 200 200 á 0.19 - -
7L2 - - - LIM - - - 200 200 LIM - -
7L3 - - - 0.42 - - - 200 200 á 0.59 - -
8L1 - - - - - - - - - - - -
8L2 - - - LIM - - - 200 200 LIM - -
8L3 0.28 0.38 0.30 0.14 - - 200 200 200 á 0.31 39.8 16.4

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 71 of 78
Name: MARK PERRY Date of 24/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of CLEANERS CUPBOARD Supply to distribution DB A No of Nominal 230


phases: 1 V

Original
distribution board: CENTRAL STRUCTURE board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB A+2 Type: 60898 Rating: 10 A RCD No N/A IÜ mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 LIGHTS H C 1 1.5 CASE 0.4 3036 Fuse (SE) 3 30 4 - 1.09
2L1 SOCKET H C 1 1.5 CASE 0.4 3036 Fuse (SE) 3 30 4 - 1.09

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 72 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop N/A RCD N/A
impedance

Original
* See note below
Operating times
Ö *0.68 É At IÜ N/A ms Insulation N/A Multi 101617007
of associated resistance function
IÙ 0.32 kA RCD (if any) At 5IÜ N/A ms
*
Continuity N/A Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - 0.41 - - 200 200 200 á 1.09 - -


2L1 - - - 0.03 - - 200 200 200 á 0.71 - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 73 of 78
Name: MARK PERRY Date of 24/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location of OFFICE VIA CENTRAL Supply to distribution DB A No of Nominal 230


phases: 1 V

Original
distribution board: JUNCTION board is from: voltage:
Associated N/A
Overcurrent protective device for the distribution circuit: RCD (if any): BS(EN)
Distribution DB A+1 Type: 60898 Rating: 10 A RCD No N/A IÜ N/A mA
board designation: BS(EN) of poles:

permitted by BS 7671
Circuit Overcurrent protective devices RCD

Max. disconnection
Circuit designation conductors: csa
(see code below)
Circuit number

Type of wiring

time permitted
Þ Live cpc

points served
BS (EN)

Short-circuit
and line

Maximum Ö
by BS 7671

current, IÜ
Number of
Reference

Operating
capacity
method

Rating
Type
(mmâ) (mmâ) (s) (A) (kA) (mA) (É)
1L1 LIGHT H C 1 1.5 CASE 0.4 3036 Fuse (SE) 3 30 4 - 1.09
2L1 SOCKET H C 1 1.5 CASE 0.4 3036 Fuse (SE) 3 30 4 - 1.09

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRING


A B C D E F G H O (Other - please state)

Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic Thermoplastic/ Thermosetting/ Mineral-


insulated/ cables in cables in non cables in cables in non SWA cables SWA cables insulated
sheathed cables metallic conduit metallic conduit metallic trunking metallic trunking cables
Page 74 of 78

This report is based on the model forms shown in Appendix 6 of BS7671 See next page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Test Results
This certificate is not valid if the serial
number has been defaced or altered IPN4/0506770

(To the person ordering the work)


SCHEDULE OF TEST RESULTS
FOR THE PRIMARY DISTRIBUTION BOARD
TEST RESULTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
DIRECTLY TO THE ORIGIN OF THE INSTALLATION Test instruments (serial numbers) used:
Characteristics at this distribution board
YES Confirmation of supply polarity Earth fault loop N/A RCD N/A
impedance

Original
* See note below
Operating times
Ö *0.26 É At IÜ N/A ms Insulation N/A Multi 101617007
of associated resistance function
IÙ 0.884 kA RCD (if any) At 5IÜ N/A ms
*
Continuity N/A Other N/A
Phase sequence confirmed (where appropriate)

Circuit impedances Insulation resistance Polarity Maximum RCD operating


(É) measured earth times
Circuit number

fault loop Test


and line

Ring final circuits only All circuits Line/Line Ú Line/Neutral Ú Line/Earth Ú Neutral/Earth impedance, Ö at IÜ at 5IÜ button
(measured end to end) (At least one column operation
to be completed) (if applicable)

rã rÐ rå
(Line) (Neutral) (cpc) Rã + Rå Rå (MÉ) (MÉ) (MÉ) (MÉ) (á) (É) (ms) (ms) (á)

1L1 - - - 0.27 - - 200 200 200 á 0.53 - -


2L1 - - - 0.25 - - 200 200 200 á 0.51 - -

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highest
values must be recorded.

TESTED BY
Signature: Position: Electrician
Page 75 of 78
Name: MARK PERRY Date of 24/08/2017
(CAPITALS) testing:

This report is based on the model forms shown in Appendix 6 of BS7671 See previous page for
Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. ©
Copyright Certsure LLP (January 2015) Schedule of Circuit Details
F. OBSERVATIONS AND RECOMMENDATIONS FOR ACTIONS TO BE TAKEN
Referring to the attached schedules of inspection and test results, and subject to the limitations at D:
There are no items adversely affecting electrical safety. N/A or The following observations and recommendations for á
are made

Item No Code Ú
21 DB A - Board Cover Pin Missing C3
22 DB A - Circuits 6L1 + 8L1 - Unknown Circuit Further Investigation Is Required To Locate Final C2
Termination Of Circuit

23 DB B - 2 x Board Cover Pins Missing C3


24 DB B - DB Not To IPX4 C2
25 DB B - Damaged Pattress In Heads room C2
26 DB B - Circuits 8L2,11L2, 14L2, 15L2 + 23L2 - Unknown Circuit Further Investigation Is Required To C2
Locate Final Termination Of Circuit

27 DB B - Circuit 2L2 - Circuit Found Of At Time Of Test And Left Off C3


28 DB BH - Circuit 3L2 - RCD Socket - (X1 37.8) (X5 17.5) NOTE
29 DB BH - Board Cover Pin Missing C3
30 DB F - Circuit 4L1 - Spur Off Circuit Has Hole At Cable Entry - Not Correctly IP Rated C2
31 DB 14 - 1 x Board Cover Missing C3
32 DB 14 - 2 x 400v Label C3
33 DB Reception - Circuit 3L3 + 4L3 - Unable To Obtain Reading Due To High Level PIR's/ No Local Switch LIM
34 DB Reception - Single Core Cable Present Within This DB - Requires Disconnecting Or Terminating C3
35 DB Reception - Board Not To IPX4 C2
36 DB A1 - Circuits 2L1, 2L2, 2L3, 3L1, 4L1, 4L2 + 7L2 - Unable To Obtain Z's Due To Height LIM
37 DB A1 - Circuit 1L2 - Damaged Socket by Entrance Door In Class Room C2
38 DB 0/2/A - Limitation On All Lighting Circuits On This DB Due To High Level Access LIM
39 DB 0/2/E - Circuits 5L1, 8L2, 10L1, 10L2 + 11L1 - No Access To Obtain Z's Readings LIM
40 DB 0/2/E1 - Circuits 1L1 + 1L2 - No Z's Obtained Due To Access of Fittings LIM

Additional Pages? No Yes á Specify page 76


Immediate remedial action
ÚOne of the following codes, as appropriate, has been allocated to each of the required for items:
observations made above to indicate to the person(s) responsible for the installation
the degree of urgency for remedial action: Urgent remedial action
required for items: 22,24,25,26,30,35,37,42,47,48,49,56,60,
Code C1 "Danger Present". Risk of injury. Immediate remedial action required.
Code C2 "Potentially dangerous". Urgent remedial action required. Further investigation
required for items:
Code C3 "Improvement recommended".
Code FI "Further investigation required without delay". Improvement
recommended for items: 21,23,27,29,31,32,34,45,51,52,53,55,57,58,59,61,
Please see the notes for recipient for guidance regarding the Classification codes.

Please see the 'Guidance for Recipients on the


classification codes' in the 'Notes for Recipients'
F. OBSERVATIONS AND RECOMMENDATIONS FOR ACTIONS TO BE TAKEN
Referring to the attached schedules of inspection and test results, and subject to the limitations at D:
There are no items adversely affecting electrical safety. N/A or The following observations and recommendations for á
are made

Item No Code Ú
41 DB 0/2/B - Circuits 3L1,3L2 + 3L3 - Unable To Access To Obtain Z's LIM
42 DB 0/2/B - Circuit 4L3 - Unknown Circuit Further Investigation Is Required To C2
Locate Final Termination Of Circuit

43 DB 0/2/B1 - Circuits 1L1 - 3L1 - Limitation On All Lighting Circuits On This DB Due To High Level Access LIM
44 DB 0/2/MCPA - Circuit 3L1 - Limited Access To Obtain Z's Reading LIM
45 DB 0/2/MCPA - No Rcd Label At DB C3
46 DB 0/2/C - Circuits 1L1 - 2L3, 6L1, 6L3, 8L1, 9L2, 9L3, + 10L2 - Limited Access To Obtain Z's Reading C3
47 DB 13A - Circuit 5L1, 5L2 + 7L3 - Unknown Circuit Further Investigation Is Required To C2
Locate Final Termination Of Circuit

48 DB 13A - Circuit 3L3 - RCBO Failed To Trip In Permitted Times C2


49 DB 13A - Cracked Double Socket C2
50 DB 13A - Lighting Circuits - Limitation On All Lighting Circuits On This DB Due To High Level Access LIM
51 DB 13A - No Mixed Colour Label C3
52 DB 13 - Circuit 5L2 - Additional RCD Protection Required C3
53 DB 13 - Circuit 5L3 - Additional RCD Protection Required C3
54 DB 13 - Circuit 6L2, 7L2 + 8L2 - Limited Access To Obtain Z's Reading LIM
55 DB A+2 - No Rcd Protection for Sockets C3
56 DB A+2 - No Discrimination Between Lights & Sockets C2
57 DB A+2 - Corroded CS Earth Terminations For Mims C3
58 DB A+2 - Inproper Termination Of Earth At Junction Box C3
59 DB A+2 - Missing Pin From Light Switch C3
60 DB A+1 - No Discrimination Between Lights & Sockets C2

Additional Pages? No Yes á Specify page 77


Immediate remedial action
ÚOne of the following codes, as appropriate, has been allocated to each of the required for items:
observations made above to indicate to the person(s) responsible for the installation
the degree of urgency for remedial action: Urgent remedial action
required for items: 42,47,48,49,56,60,
Code C1 "Danger Present". Risk of injury. Immediate remedial action required.
Code C2 "Potentially dangerous". Urgent remedial action required. Further investigation
required for items:
Code C3 "Improvement recommended".
Code FI "Further investigation required without delay". Improvement
recommended for items: 45,51,52,53,55,57,58,59,61,
Please see the notes for recipient for guidance regarding the Classification codes.

Please see the 'Guidance for Recipients on the


classification codes' in the 'Notes for Recipients'
F. OBSERVATIONS AND RECOMMENDATIONS FOR ACTIONS TO BE TAKEN
Referring to the attached schedules of inspection and test results, and subject to the limitations at D:
There are no items adversely affecting electrical safety. N/A or The following observations and recommendations for á
are made

Item No Code Ú
61 DB A+1 - No Rcd Protection To Sockets C3

Additional Pages? No á Yes Specify page


Immediate remedial action
ÚOne of the following codes, as appropriate, has been allocated to each of the required for items:
observations made above to indicate to the person(s) responsible for the installation
the degree of urgency for remedial action: Urgent remedial action
required for items:
Code C1 "Danger Present". Risk of injury. Immediate remedial action required.
Code C2 "Potentially dangerous". Urgent remedial action required. Further investigation
required for items:
Code C3 "Improvement recommended".
Code FI "Further investigation required without delay". Improvement
recommended for items: 61,
Please see the notes for recipient for guidance regarding the Classification codes.

Please see the 'Guidance for Recipients on the


classification codes' in the 'Notes for Recipients'
Thank you for using our services and if
you would like to discuss your
companies further requirements
please get in touch.

Call one of the team


on 01922 710014
or email admin@electricaltestmidlands.com

• Alarms & Security • Energy Monitoring


• Electrical Inspection & Testing • Electrical Installation Drawings
• Building Services • Fire Alarm Installation & Testing
• Electrical Compliance • Gas Installation & Plumbing
• Electrical Installation • (PAT) Portable Appliance Testing
• Emergency Lighting • Thermal Imaging (Thermography)

Electrical Test Midlands Ltd


110B Walsall Road, Cannock,
West Midlands, WS11 OJB

t 01922 710014
t 0800 066 3227
e admin@electricaltestmidlands.com

www.electricaltestmidlands.com