Limitorque CS/CSE/CSL

TM

Control Station/Control Station - Electronic/Constrol Station-Local

Experience In Motion
Limitorque announces a unique concept in remote
The CS/CSE/CSL device replaces all previously supplied Limitorque SW stations. The CS is available in three versions: a hardwired
version designated the CS (Control Station), an electronic version designated the CSE (Control Station – Electronic), and a local
control only version designated the CSL (Control Station – Local). All devices are contained in one platform and operation is via two
selector switches, making valve control easier.

CS (Control Station) • Solid-state LEDs are featured for long life and ease of
replacement. The standard RED for Open and GREEN
The basic CS can be used for virtually all of Limitorque’s
for Closed can be reversed. All devices can be mounted
hardwired controls. It is compatible with 120 or 220 VAC
remotely for easier cycling of actuators that are installed in
control schemes. (Switch rating = 6A resistive.)
hard-to-reach locations.

CSE (Control Station-Electronic) Global Certifications Available, XP and WP:


The electronic CSE can be used with previously supplied UEC • Non-hazardous (Weatherproof/Submersion) Certification
controls and the MX series of non-intrusive actuators. It is Options:
compatible with 24 VDC control schemes.
– NEMA 6; 6 feet head for 30 minutes
– CSA – NEMA 3, 4, 4X, & 6
CSL (Control Station-Local) – IEC 529 protection code IP68; 3 meters for 48 hours
continuous
The CSL is similar to the CS, except it is used for local control
– Limitorque specification; 20 feet head for 24 hours
only. It is compatible with 120 or 220 VAC control schemes.
(Switch rating = 6A resistive.) – NEMA 4X – to ASTM B117
• Hazardous Environments (Explosion proof) Certification
Options:
Standard Features – FM – Class I, Groups C & D, DIV.1 and Class II, Groups E,
• Two easy-to-use selector switches: F, & G

– CS/CSE: One selector switch that functions as a – FM – Class I, Groups B, C & D, DIV.1 and Class II, Groups
REMOTE/STOP/LOCAL positioner. The switch can be E, F, & G
cycled as “REMOTE-STOP”, “STOP”, or “LOCAL-STOP”. – CSA – Class I, Groups C & D, DIV.1 and Class II, Groups E,
This switch can be padlocked into position using up to a F, & G
1/4” hasp. • ATEX EEx d IIB, SIRA certified for EEx d IIBT4, per EN 50018
– CSL: One spring return-to-center (run position) selector • SAA EEx d IIB T4
switch that functions as a local STOP/RUN/STOP • SAA EEx d IIC T4
positioner. The switch can be padlocked into position
• CE Declarations:
using up to a 1/4” hasp.
– The CS/CSE/CSL complies with European Directive
– CS/CSE/CSL: A second selector switch allows OPEN/
89/336/EEC, Electromagnetic Compatibility.
CLOSE operation of the unit in either inching mode
(momentary contact) or maintained mode (latched contact). – The CS/CSE/CSL complies with European Directive
89/392/EEC, Machinery Directive.
• REMOTE/STOP/LOCAL (CS/CSE), STOP/RUN/STOP (CSL
• The CS/CSE/CSL is completely retro-fittable with existing
only), and OPEN/CLOSE text plate. Decals can be applied
Limitorque field installations.
by the end user and are supplied in five different languages:
French, Spanish, German, Italian, Portuguese.

2 Flowserve.com
Remote CSE Mounting Distance to MX
Internal 24VDC power supplied: Max mounting distance allowed (w/18AWG) = 1200 ft.
External 24VDC (+/- 10%) power supplied: Max mounting distance allowed (w/18AWG) = 500 ft.

OPEN OPEN
R1 RED R1 BLU
FRONT VIEW R 1SIDE VIEW R 1
4.50 5.6

CLOSE CLOSE
R2 BLU R2 RED
LOCAL
G 13 G 13

OPEN SPRING RETURN SS#2 SPRING RETURN


STOP SS#2
OFF TO CENTER OFF TO CENTER
STOP STOP SS#1 STOP STOP SS#1
OFF 4.25 OPEN CLOSE
LOCAL REMOTE OPEN CLOSE LOCAL REMOTE

6.2 STOP
CLOSE RED RED
(1) (2) (1) (2) (1) (2)
(1) (2)
REMOT E
J J
LIMITORQUE
(3) (4) (3) (4) (3) (4) (3) (4)

14 14 10.8 14 14
.406 DIA. THRU BLK BLK
(2) PLACES 10 3.3 10
J J
11 11 4
1.00 4
GRN
.560 ORG BRN GRN ORG BRN
PUR PUR
10.8 REMOTE REMOTE
J (5) (6)
CLOSED J (5) (6)
CLOSED
.135
.440 (7) (8)
REMOTE (7) (8)
REMOTE
OPEN OPEN
J 1.0 J (9)
(9) (10) (10)
YEL REMOTE 3
YEL REMOTE
3
(11) (12) COMMON 1.13 (11) (12) COMMON
BLK BLK
9 9
REMOTE REMOTE
12
WHT INDICATION 12
WHT INDICATION

3/4" N PT
MALE

(11) BRN (11) BRN


CLOSE 5 CLOSE 27
(10) ORG (10) ORG
REMOTE
REMOTE

3.870
INPUTS

26
INPUTS

STOP 6 6.5 STOP


4.750 (4) PUR (4) PUR
OPEN 7 OPEN 25
8 28
CSE WITH REMOTE SURFAC E MOUNTING KIT
COMM ON -Ve COMM ON -Ve
(3) YEL (3) YEL
SEE NOTE
INPUT 2 9 SEE NOTE
INPUT 2 35
2 RESISTOR R2 2
PRINTED CIRCUIT BOARD
(2.21K Ω1/2W) (61-825-1276-2)
0V AC 11 RESISTOR R1

12
CONTROL
CONTROL

(2.0K Ω1/2W)
110V AC
SUPPLY
SUPPLY

(14) GRN (14) GRN


24V DC + Ve 13 SELECTOR 24V DC + Ve 22
SWITCH
0V DC 14 0V DC 21

DEFAU LT SETTING S-2 S-1


DEFAU LT SETTING
(SEE NOTE 1) (SEE NOTE 1)

31 48
10 POSITION
"C LOSE" AS3 (1) RED TERMINAL BLOCK "C LOSE" S1b (13) RED
49
6 1-825- 1276-2
POSITION 32 (TB1)
POSITION

20 PIN HEADER
SIDE VIEW 42 BACK VIEW (P1) 50
AS4 S2b
"O PEN"
POSITION
CSE
(13) BLU "O PEN"
POSITION
(1) BLU
43 51
L-782 REV-A 4/26/93 NOTE NOTE
1. CONTACTS SHOWN WITH 1. CONTACTS SHOWN WITH
VALVE FULLY CLOSED. VALVE FULLY CLOSED.
2. INPUT 2 MUST BE 2. INPUT 2 MUST BE
CONF IGURED FOR "C SE" CON FIGURED FO R "CSE"
REMOT E SELECTED INDICATION. REMOT E SELECTED INDICATION.

MX TERMINAL BLOCK LEGEND MX TERMINAL BLOCK LEGEND


(4 WIRE CONTROL) TERMINAL LOCATED ON
(4 WIRE CONTROL) TERMINAL LOCATED ON
(INTERNAL SUPPLY 24VDC) TERMINAL BLOCK TB1 OF (INTERNAL SUPPLY 24VDC) TERMINAL BLOCK TB1 OF
CONT ROL STATION CSE. CONT ROL STATION CSE.
J INTERNAL JUMPER NOT J INTERNAL JUMPER NOT
REMOVABL E. REMOVABLE.

WIRING TO MX TERMINAL BLOCK WIRING TO MX-A TERMINAL BLOCK


DRAWN DATE DRAWN DATE
LIMITORQU E CORPORATION
ADD ED INPUT 2 & DKA
E NOTE 2 1/11/05 R

REVISED "AS" DKA WHC 12/04/02 DKA 2/22/07 Limito rqu e Actua tion Systems
D CONTACT WIRING 5/12/04 TITLE CSE WITH REMOTE SURFACE MOUNTING KIT 5114 WOO DALL ROAD, LYNCHBURG, VIRGINIA 24506-1318

CHECKED DATE CHECKED DATE


C ADD ED COND UIT KIT
AND DIM
DKA
1/14/04 WIRED TO MX ACTUATOR TERMINAL BLOCK TITLE CSE WITH REMOTE SURFACE MOU NTING KIT
BSW 12/06/02
B
REMOV E REMOTE STOP DKA WIRED TO MX-A ACTUATOR TERMINAL BLOCK
FIELD WIRING 11/6/ 03
APPROVED DATE 1ST ORDER NO. DRAWING NO. REV SHEET APPROVED DATE 1ST ORDER NO. DRAWING N O. REV SHEET
NO. DESCRIPTION DATE NO. DESCRIPTION DATE

REVISION BSW 12/06/02 STANDARD 19-499-0071-3 E 1 OF 1 REVISION


----- 19-499-0086-3 1 OF 1

LimitorqueTM CS/CSE/CSL 3
Flowserve Corporation Flowserve Corporation has established industry leadership in the design and manufacture of its products. When
properly selected, this Flowserve product is designed to perform its intended function safely during its useful life.
5215 North O’Connor Blvd. However, the purchaser or user of Flowserve products should be aware that Flowserve products might be used
in numerous applications under a wide variety of industrial service conditions. Although Flowserve can provide
Suite 700 general guidelines, it cannot provide specific data and warnings for all possible applications. The purchaser/user
must therefore assume the ultimate responsibility for the proper sizing and selection, installation, operation, and
Irving, Texas 75039-5421 USA maintenance of Flowserve products. The purchaser/user should read and understand the Installation
Instructions included with the product, and train its employees and contractors in the safe use of Flowserve
Telephone: +1-937-890-5839 products in connection with the specific application.
While the information and specifications contained in this literature are believed to be accurate, they are supplied
for informative purposes only and should not be considered certified or as a guarantee of satisfactory results by
reliance thereon. Nothing contained herein is to be construed as a warranty or guarantee, express or implied,
regarding any matter with respect to this product. Because Flowserve is continually improving and upgrading its
product design, the specifications, dimensions and information contained herein are subject to change without
notice. Should any question arise concerning these provisions, the purchaser/user should contact Flowserve
Corporation at any one of its worldwide operations or offices.
©2022 Flowserve Corporation. All rights reserved. This document contains registered and unregistered
trademarks of Flowserve Corporation. Other company, product, or service names may be trademarks or service
VABR000652-01 (EN/AQ) July 2022 marks of their respective companies.

flowserve.com

You might also like