Professional Documents
Culture Documents
Display Settings
Backlight
Contrast
Panel Setup Menu Brightness
Main Menu Beep
1.Set Time/Date
1.Network Setup Menu}
2.Display Settings}
2.Panel Setup Menu} Control Settings
3.Control Settings}
3.Service Menu} Temperature Units
4.Change Password
Override Range
Override Timer Control Settings
Filter Time BC Override Max.
More} Recovery SP Stagger
Service Menu
1.Self Test}
2.Detail Data Self Tests
3.Reset Test Clock
4.Software Update Test Screen
5.Restore Factory Test Buttons
Test Network
Test Speaker
Test Memory
08/07 505,374M
*2P0807* Page 1
*P505374M*
Features BUILDING CONTROLLER (BC)
IMC AND NTC CONTROLLERS The user determines the schedule for each output based
The user determines setpoints and occupied modes by as- on the times desired and type of building equipment to be
signing a program to each unit. Programs allow: controlled. Programs allow:
− Up to 6 time periods per day schedule with choice of − Up to 4 time periods per day schedule.
heating setpoint, cooling setpoint, and occupied mode
per time period. − A different day schedule each day of the week and on
− A different day schedule each day of the week and on holidays.
holidays.
− Programmed outputs can be individually overridden.
− A different override setpoint for each program.
− A different relative humidity setpoint for each occupied − Twenty−six programs are available (A−Z) and up to 50
time period used during optional reheat operation (Hu- day schedules are available (1−50). Day schedules 1
miditrol reheat and Supermarket reheat). and 2 and programs A and B are pre−set in the NCP.
− Twenty−six programs are available (A−Z) and up to 99 − *Up to 50 dates can be entered as holidays.
day schedules are available (1−99). Day schedules 1
*When an HVAC unit and a BC are assigned the same pro-
and 2 and programs A and B are pre−set in the NCP.
gram letter, the day schedules can be different, but the hol-
− *Up to 50 dates can be entered as holidays. idays are shared.
Table of Contents
1−Network Set−Up Menu Page 7 C−Brightness Page 14
1−Programming Menu Page 7 D−Beep Page 14
1−Select Holidays Page 7 3−Control Settings Page 15
A−Add a New Holiday Page 7 A−Temperature Units Page 15
B−Edit An Existing Holiday Page 8 B−Override Range Page 15
C−Delete a Holiday Page 8 C−Override Timer Page 15
2−Create Day Schedule Page 8 D−Filter Time Page 15
A−New Day Schedule Page 8 E−BC Override Max Page 15
B−Copy and Edit Schedule Page 9 F−Recovery SP Stagger Page 15
C−Lighting Schedule Page 9 4−Change Password Page 16
D−Delete a Day Schedule Page 9 A−New Password Page 16
3−Create Program Page 9 B−Enter Password Page 16
A−New Program Page 9 C−Enable/Disable Page 16
B−Copy and Edit Program Page 10 D−Unknown or Forgotten Page 17
C−Delete a Program Page 11 3−Service Menu Page 17
4−Assign Program To Address Page 11 1−Self Test Page 17
5−Special Events Page 12 Test Clock Page 17
2−Poll All Addresses Page 12 Test Screen Page 17
3−Change Control Mode Page 13 Test Buttons Page 17
A−Monitoring or Tstat Mode Page 13 Test Network Page 17
B−Control Sensor Mode Page 13 Test Speaker Page 17
C−Start−Up Page 13 Test Memory Page 17
D−NCP Mode Page 13 2−Detail Data Page 17
E−Remove Address Page 13 3−Reset Page 19
4−Descriptions Page 14 4−Software Update Page 19
2−Panel Set−Up Menu Page 14 5−Restore Factory Page 19
1−Set Time/Date Page 14 Sensor Mode Zone Status Screen Details Page 20
2−Detail Data Page 14 T’stat Mode Zone Status Screen Details Page 21
A−Backlight Page 14 Troubleshooting Page 22
B−Contrast Page 14 Worksheets Page 23
NCP Pushbuttons
The IMC and NTC Controller Status Screen in figure 1 is dis-
Use the four pushbuttons underneath the display to move played when the L Series IMC is operating in the zone sensor
between NCP screens and functions or change settings. mode or when the NTC is used. Refer to Change Control
Prompts at the bottom of the screen will change as push- Mode" section to change IMC to zone sensor mode.
button function varies. See figure 1.
Left Pushbutton: Backs" or exits out of screens.
The IMC Controller Status Screen in figure 2 is displayed
Pushbutton: Move upward through selections. when the IMC is operating in the default Tstat Mode. T’stat
Pushbutton: Move downward through selections. Mode is not an option on units which contain an NTC.
Right Pushbutton: Advances into screens and functions.
NOTE: Hold the pushbutton down to move between num- NOTE − See Change Control Mode" section to confirm the
bers more quickly. appropriate screen is displayed.
ZONE NUMBER
ADDRESS DESCRIPTION
LOBBY HEATING SETPOINT
ADDR 01 Zone 01
UNIT ADDRESS
ZONE TEMPERATURE
80°F Heat 56
COOLING SETPOINT
FIGURE 1
ADDRESS DESCRIPTION
BLOWER
UNIT ADDRESS LOBBY STATUS RETURN AIR
ADDR 01 Zone 01 TEMPERATURE
NUMBER OF COMPRES-
SORS OPERATING Comp SUPPLY AIR
Heat TEMPERATURE
NUMBER OF HEAT
BLOWER OFF OUTDOOR
STAGE OPERATING
ECON 1 PCT OFF RETURN 70
TEMPERATURE
ECONOMIZER STATUS NO NEW ALARMS SUPPLY 64
FILTER OK OUTDOOR 78
CO2 LEVEL
NEW ALARM IDLE CO2 304
TSTAT RH 63
AIR FILTER STATUS UNOCCUPIED RELATIVE HUMIDITY
01/09/2000 Sun 8:30:40A
UNIT OPERATION Network + OCCUPIED OR UN-
OCCUPIED MODE
CONTROL MODE
DATE
PUSHBUTTON PROMPTS TIME
FIGURE 2
BC STATUS SCREENS buttons to highlight the output status and manually turn the
The Building Controller Status Screen in figure 3 is displayed output ON or OFF.
when a BC is installed on the L Connection network.
Refer to the programming section of this manual to assign
The status screen shown in figure 3 displays information a program which will control the output by time of day and
about outputs 1 through 4 (P189 on BC board). To view in- day of week.
formation about additional inputs, use the + pushbutton to
highlight the page number. Use the up arrow to go to page NOTE − The program can be changed from the BC status
2, 3, or 4. screen. Use the pushbuttons to highlight the appropriate
On start−up, all 8 outputs are set to manual. Use the push- output program and assign an existing program.
PUSHBUTTON PROMPTS
FIGURE 3
Output 5 MA
N
Off
Output 6 MA
N
Off
BUILDING CONTROLLER STATUS SCREEN
Output 7 E Off
Page 4 − Analog and Light Sensor Inputs
Output 8 F Off
ALARM OVERRIDE 2:00
Bldg Cntl 1
01/09/2000 Sun 8:30:40A
ADDR 02 Page 04
Network +
Name VALUEMANUAL
FIGURE 4 NEW ALARM OVERRIDE
Analog 1 2.7V TIMER
The page 3 BC status screen, shown in figure 5, displays Analog 2 2.9V
BC temperature inputs T1 through T4 (P187 on BC board). Analog 3 3.0V
Light Sensor LIGHT
BUILDING CONTROLLER STATUS SCREEN ALARM OVERRIDE 2:00
Page 3 − Temperature Inputs
01/09/2000 Sun 8:30:40A
Bldg Cntl 1 Network View Names +
ADDR 02 Page 03
PRESS THE VIEW" PRESS THE + PUSH-
Name TEMP
PUSHBUTTON FOR BUTTON UNTIL ALARM"
Temperature 1 75F ALARM DETAILS IS HIGHLIGHTED
Temperature 2 78F PRESS THE NAMES"
Temperature 3 73F PUSHBUTTON TO EDIT
Temperature 4 73F INPUT/OUTPUT NAMES
ALARM OVERRIDE 2:00
FIGURE 5
The page 4 BC status screen, shown in figure 6, displays BUILDING CONTROLLER STATUS SCREEN
BC analog and light sensor inputs (P188 and P189 on BC Page 4 − Analog and Light Sensor Inputs
board).
Alarms U−02
BUILDING CONTROLLER STATUS SCREEN
Page 4 − Analog and Light Sensor Inputs < Delete all alarms >
1 02 04/22/02 1:01:00P
Bldg Cntl 1 2 02 04/22/2002 7:37:00A
ADDR 02 Page 04 3 02 01/01/2000 12:00:00A
Name VALUE
Analog 1 2.7V
Analog 2 2.9V
Analog 3 3.0V
Light Sensor LIGHT Exit Select
ALARM OVERRIDE 2:00
FIGURE 8
FIGURE 6
FIGURE 10
3. Press the Select" pushbutton. The month will be high- CREATE DAY SCHEDULE (BC CONTROLLERS)
lighted. Use arrow keys to enter month; press Enter"
pushbutton. The month will be stored and the day will Day Schedule: 03
be highlighted. Use arrow keys to change rest of date
and press Enter" pushbutton after each entry. 12:00:00P LS
11:00:00P Off
NOTE − To prevent the holiday from being entered,
press the Done" pushbutton when ESC" is high- −−: −−:−− −−−
lighted. −−: −−:−− −−−
4. Press the Done" pushbutton to store and display the
holiday. Select a Day Schedule
Exit Select
B−Edit An Existing Holiday
1. Use the arrow pushbuttons to align the cursor with the FIGURE 14
holiday to be revised.
Table 3 shows two factory−default day schedules.
2. Press the Select" pushbutton.
Table 3
3. Press the Edit" pushbutton. Factory Default Day Schedules
4. Use the arrow and Enter" pushbuttons to revise the IMC/NTC BC
date in the same manner as entering a new date. Sche
Start Time Heating Cooling Occu On/Off
dule
5. Press the Done" pushbutton when the revised holiday Setpoint Setpoint pied /LS
is entered.
7:00 a.m. 70 74 Yes On
C−Delete A Holiday 1
5:00 p.m. 60 84 No Off
1. Use arrow pushbuttons to toggle to the holiday to be
2 12:00 a.m. 60 84 No Off
deleted.
A−New Day Schedule
2. Press the Select" pushbutton.
Create new day schedules if schedules other than the fac-
3. Press the Delete" pushbutton. A confirmation screen
tory−default schedules are required.
will appear. Press the Yes" pushbutton to delete the
holiday. 1. Use the arrow pushbutton to toggle to a Day schedule
CREATE DAY SCHEDULE which has no times entered.
2. Press the Select" pushbutton.
From the Main Menu, toggle to the screen shown in figure 13.
3. Press the Edit" pushbutton to edit the first time period
See figure 14 when creating a day schedule for Building
in the day. See figure 15.
Controllers.
4. Use the arrow pushbuttons to enter new times, set-
1−Network Set−Up Menu
points, occupied periods, and/or BC output on and off
1−Programming Menu functions. Press the Done" pushbutton at the end of
1−Select Holidays the line.
2−Create Day Schedule 5. Use arrow pushbuttons to advance to the next time pe-
1 HVAC riod. Add additional times periods; when the last time
2 Building Control period is entered, press the Done" pushbutton to fin-
ish.
CREATE DAY SCHEDULE (HVAC UNITS)
OPEN DAY SCHEDULE
Day Schedule: 01
Day Schedule: 03
Heat Cool OCP
Heat Cool OCP
7:00:00A 70 74 Y
−−: −−:−− 0 0 Y
5:00:00P 60 84 N
−−: −−:−− 0 0 N
−−: −−:−− 0 0 N
−−: −−:−− 0 0 N
−−: −−:−− 0 0 N
−−: −−:−− 0 0 N
−−: −−:−− 0 0 N
−−: −−:−− 0 0 N
−−: −−:−− 0 0 N
−−: −−:−− 0 0 N
Select a Day Schedule
Select a Line to Edit
Exit Select
Done Edit
FIGURE 13
FIGURE 15
4. Use the arrow pushbuttons to change the highlighted SELECT EXISTING PROGRAM
day schedule.
NOTE − There are two default day schedules. Refer to Program: A
Create Day Schedule" section to create additional Mon Tue Wed Thu Fri Sat Sun H
day schedules. 1 1 1 1 1 1 1 1
5. Press Enter" to store the day schedule; the next day
schedule is highlighted. Once the Monday program is Override H:70 C:74
entered, the rest or the day programs must also be en- RH Setpoint: 60
tered; the Done" pushbutton does not exit.
6. Press the Done" pushbutton when all day schedules
are entered.
7. Modify schedule, override, or holidays if necessary.
Press Done" when schedule is final. Select a Program
IMPORTANT − The new program must be assigned to Esc Copy Edit
activate the schedule. Refer to Assign Program" sec-
tion. FIGURE 21
B−Copy And Edit An Existing Program3 3. Press the Copy" pushbutton to copy the existing pro-
If Program A or B is close to the the desired schedule, ei- gram to a new program.
ther may be copied to a new program and modified. 4. Use the arrow pushbuttons to toggle to the new pro-
gram. Figure 22 shows Program A ready to be copied
1. Determine which existing program to copy and use ar-
to Program C.
row keys to toggle to the appropriate program. Figure
20 shows Program A as the existing program.
SELECT NEW PROGRAM
COPY AND EDIT EXISTING PROGRAM Program: A
Mon Tue Wed Thu Fri Sat Sun H
Program: A − − − − − − − −
Mon Tue Wed Thu Fri Sat Sun H
1 1 1 1 1 1 1 1
Override H: 0 C: 0
RH Setpoint: 60
Override H:70 C:74
RH Setpoint: 60
Copy to program:C
Select a Program
Select a Program
Exit Select
Esc Copy Edit
FIGURE 22
FIGURE 20
5. Press the Copy" pushbutton. A new Program C will be
2. Press the Select" pushbutton. See figure 21. displayed.
6. Press the Select" and Edit" pushbutton to modify the 2. Press the Delete" pushbutton to delete the program.
schedule, override, or holidays. See figure 23. A prompt will appear to confirm the program will be de-
leted. Press the Yes" or No" pushbutton.
COPY AND EDIT EXISTING PROGRAM 3. Press the Select" pushbutton.
Program: C
Mon Tue Wed Thu Fri Sat Sun H ASSIGN PROGRAM TO ADDRESS
1 1 1 1 1 1 1 1
From the Main Menu, toggle to the screen shown in figure
25.
Override H:70 C:74
RH Setpoint: 60 1−Network Set−Up Menu
Modify Schedule
1−Programming Menu
Modify Parameters
Modify Holidays 1−Select Holidays
2−Create Day Schedule
Select one of the above
Done Select 3−Create Program
SPECIAL EVENTS 3. Press the Done" pushbutton to assign the event to the
From the Main Menu, toggle to the screen shown in figure selected address.
26. 4. Use the arrow pushbuttons to move to the next ad-
dress and assign further events.
1−Network Set−Up Menu 5. Press the Exit" pushbutton to return to Main Menu.
1−Programming Menu MODIFY SPECIAL EVENT
1−Select Holidays
2−Create Day Schedule A Z Date Time Hrs
01 0 07/04/04 8:00P 4:00
3−Create Program 02 0 06/21/04 7:00P 8:00
4−Assign Program To Address
5−Special Events
1. Use the arrow pushbuttons to move the cursor to the
appropriate address. ____________________________________________
2. Press the Select" and Edit" pushbutton to modify the Esc Delete Edit
date, time, and duration of the special event. See fig-
ure 26. FIGURE 26
From the Main Menu, toggle to the screen shown in figure 27.
POLL ALL ADDRESSES
1−Network Set−Up Menu
1−Programming Menu
1−Select Holidays
2−Create Day Schedule Searching . . .
3−Create Program
4−Assign Program To Address
2−Poll All Addresses
Confirms communication to units. Use when adding a new
address or additional zones to the network. FIGURE 27
At the Main Menu, toggle to the screen shown in figure 28. IMPORTANT − Once the ECTO parameter is set correctly,
1−Network Set−Up Menu exit the new" screen and re−enter the new" screen to con-
firm the NCP recognizes the updated mode.
1−Programming Menu
1−Select Holidays CHANGE CONTROL MODE
2−Create Day Schedule A Mode NCP Mode
< Remove all addresses >
3−Create Program 1 Zone S RAS Control
4−Assign Program To Address 2 Tstat Monitor
3 Bldg Control Control
2−Poll All Addresses
3−Change Control Mode
L Series Units
The IMC System Mode parameter 6.01 determines wheth-
er the unit is controlled by the NCP or whether the unit is
monitored by the NCP.
A−Monitoring or Tstat Mode ___________________________________ __
L Series units are shipped in the Local Thermostat" or Exit Select
monitoring mode (ECTO 6.01 set to 0). The NCP will dis- FIGURE 28
play unit function but will not have control over setpoints or
schedules. All Units
B−Control or Zone Sensor Mode A−NCP Mode
ECTO parameter 6.01 must be set to IMC Zone Sensor" Units in Zone Sensor mode may be changed between
value 1, 2, or 3, to configure the rooftop unit to control to the monitor and control.
NCP setpoints and schedules. 1. Use arrow keys to align cursor to unit to be monitored.
NOTE − Non−L series units which use the NTC will only op- 2. Press the Select" pushbutton to highlight the NCP
erate in the Zone Sensor Mode; NTC parameters do not mode.
have to be changed. 3. Use arrow keys to toggle to Monitor" or Control".
C−Start−Up 4. Press the Enter" pushbutton to enter new mode.
On start−up, go to the new" screen and check for proper
NOTE − NCPs which have been set in the passive
control mode of each unit. See figure 28. If a unit is set in- mode cannot be set to control. Refer to NCP installa-
correctly, change ECTO parameter 6.01. See NCP instal- tion instruction.
lation instruction.
B−Remove Address
IMC When a controller is disconnected from the NCP network,
MODE DESCRIPTION
ECTO the new" list will continue to display the removed controller
0 TSTAT Room Thermostat address. To remove address from listing:
1. Use arrow keys to align cursor to removed address.
1 ZONE S Zone Sensor w/ No Back−Up
2. Press the Select" pushbutton to highlight the NCP
Zone Sensor w/ Thermostat mode.
2 ZONE S LT
Back−Up
3. Use arrow keys to toggle to Remove".
Zone Sensor w/ Return Air 4. Press the Enter" pushbutton to remove the address
3 ZONE S RAS
Back−Up from the list.
A−Backlight: Backlight ON
4. Press the Enter" pushbutton to store the new setting. Filter Time
A−Temperature Units − More Settings
Choose temperature in degrees Fahrenheit or Celsius. _____________________________________
Exit Select
B−Override Range −
Determines the range that the heating and cooling set- FIGURE 31
points may be adjusted at the NCP. If set at 0", setpoints
cannot be adjusted from the NCP. CONTROL SETTINGS
C−Override Timer − Display Settings
Determines how long override setpoint adjustment at NCP BC Override Max 1:00 hrs
is in effect.
D−Filter Time − Recovery SP Stagger 0:00 min
Zone status screens read filter OK" until the user specified
number of days elapses. Enter a 0" to disable the check
filter" message.
_____________________________________
E−BC Override Max
Exit Select
The maximum override time, in hours, the NCP is allowed
to override a BC output ON or OFF. FIGURE 32
2−Display Settings
______________________________
3−Control Settings Esc Change Enable Disable
5. Press the Exit" pushbutton to return to the Panel Set- PASSWORD SAVED AND ENABLED
up Menu.
IMPORTANT
Panel is sensitive to static electricity. Care must be FIGURE 37
taken in handling. Hold panel by the edges and
avoid touching any components. SELF TESTS
Self Tests
NOTE The switch does not need to be returned to the origi-
nal position; only a change of position is required. Test Clock
At the Main Menu, toggle to the screen shown in figure 38. Test Screen
Test Buttons
3−Service Menu Test Network
Test Speaker
1−Self Test Test Memory
3. Use arrow pushbuttons to align the cursor with the
self−test to be initiated.
Exit Select
4. Press the Select" pushbutton to initiate the corre-
sponding test. FIGURE 38
Detail Data 3−Service
At the Main Menu, toggle to the screen shown in figure 39 The Detail Data screen provides detailed information on
for L Series units, figure 40 for NTC controllers, and figure unit function.
41 for BC controllers. 1. Use arrow pushbuttons to view different units.
3−Service Menu 2. Press the Alarms" pushbutton to display a list of
alarms.
1−Self Test
3. Press the Select" pushbutton to display details on
2−Detail Data each error code.
EMPTY BOXES INDI- DETAIL DATA − L SERIES UNITS FILLED BOXES INDICATE
CATE NUMBER OF FANS, BLOWERS, COM-
FANS, BLOWERS, TYPE OF UNIT IMC SOFTWARE VERSION PRESSORS, OR HEAT
COMPRESSORS, SECTIONS ARE OPERAT-
OR HEAT SECTIONS LOBBY ING
PRESENT UNIT Unit 01 LCx 3.04
Fans Blower
CONDENSER FANS BLOWER OPERATION
Comp
COMPRESSORS Heat RETURN AIR TEMPERATURE
GAS OR ELECTRIC HEAT ECON 1 PCT OFF RETURN 70 SUPPLY AIR TEMPERATURE
ECONOMIZER ALARM SUPPLY 64
OPERATION OUTDOOR 78 OUTDOOR TEMPERATURE
CO2 304
NEW ALARM IDLE RH 44 CO2 LEVEL
OCCUPIED
UNIT OPERATION RELATIVE HUMIDITY
ZONE AIR / RETURN BACKUP UNOCCUPIED
CONTROL MODE MOST RECENT ALARM: 94 12/08/1999 5:08:00P_____________
Done Alarms OCCUPIED OR UNOCCUPIED
ALARM, DATE, AND TIME TIME PERIOD
PUSHBUTTON PROMPTS
FIGURE 39
FIGURE 40
FIGURE 41
At the Main Menu, toggle to the screen shown in figure 42. RESET NCP
3−Service Menu
1−Self Test
Reset Panel?
2−Detail Data
3−Reset While viewing this screen,
all communications to units
Go to this screen to disable the NCP while running Service have stopped.
Software versions 1.07 and earlier.
___________________________________
Yes No
FIGURE 42
Software Update 3−Service
At the Main Menu, toggle to the screen shown in figure 43. SOFTWARE UPDATE
3−Service Menu Software Version
1−Self Test
1.15
2−Detail Data
3−Reset Select Load to download a new
version of software.
4−Software Update Upon successful download, the
The Software Update screen will display the current NCP NCP will reset itself.
software version. A PC and special cable is required to Otherwise, it will need to be
load a new program. reset manually.
___________________________________
Exit Load
FIGURE 43
Restore Factory 3−Service
At the Main Menu, toggle to the screen shown in figure 44. RESTORE FACTORY
3−Service Menu
Restoring factory defaults
1−Self Test will clear all programs
and other user selections.
2−Detail Data
Restore factory defaults?
3−Reset (Press YES 3 times)
4−Software Update
___________________________________
5−Restore Factory Yes No
Use Restore Factory" function to clear all user settings
and return to factory−default settings. FIGURE 44
FIGURE 45
NOTE − On L series units ECTO 6.01 must be set to 1, 2, or The NCP also displays a recommended number of days to
3 for zone sensor mode. Default setting ECTO is t’stat. change−out the filter. The NCP will display 0" number of
Heating and Cooling Setpoints days until a Filter Time" is entered; see the Control Set-
tings" section. Press the Yes" pushbutton to reset the
Use the +" pushbutton to highlight the heating or cooling
number of days to zero.
setpoint. Use the arrow pushbuttons to increase or de-
crease the setpoint for 1 hour (default). See Control Set- Unit Operation
tings" section to change the override length of time. 1. Offline − Unit not communicating with the network.
In the default manual mode the new setpoints are in effect 2. Off − Unit manually turned off at the NCP. Set NCP DIP
until a program is assigned. switch #5 to OFF" to enable this feature.
Address 3. Smoke − Unit smoke detector senses smoke.
Use the +" pushbutton to highlight the unit address. Press 4. Unit Lockout − Unit de−energized by control system.
the arrow pushbuttons to display the zone status of addi- 5. Lockout 1, 2, 3, or 4 − Displays the number of compres-
tional units on the network. sor locked−out.
Alarms 6. Reheat − Unit operating in the supermarket reheat or
Use the +" pushbutton to highlight alarms. Press the Humiditrolt mode.
View" pushbutton to display a list of the alarms and the 7. Defrost 1 or 2 − Heat pump units only;
date and time of the alarms. Press the Select" pushbutton 8. Warm−up − Warm−up operation.
to view a detailed explanation of each alarm.
9. Heating − Unit operating in heating mode.
Use the Beep−Off" pushbutton to disable the beep for two
10. Cooldown − Cooldown operation.
hours. See Display Settings" in Panel Set−Up menu to turn
alarm beep off. 11. Cooling − Unit operating in cooling mode.
Filter Status 12. Idle − No demand for heating or cooling.
13. FAT Heat − Fresh Air Tempering − Heating
Use the +" pushbutton to highlight the filter status. Press
the View" pushbutton to display the number of days the 14. FAT Cool
filter has been in use. 15. FAT Reheat
DESCRIPTION ENTERED
BY USER; SEE ADDRESS
UNIT ADDRESS DETER- DESCRIPTIONS" SECTION BLOWER
MINED BY IMC DIP SWITCH STATUS
*The outdoor temperature displayed on the detail data screens shown in Detail Data"
section are actual outdoor temperatures for the corresponding IMC.
FIGURE 46
Holidays are automatically enabled when entered in Select Holidays" section. Use an X mark to indicate which programs have a holiday
disabled. Enable/disable feature is carried over when a holiday is edited. Edit a holiday ("Modify Holiday" section) when the same pro-
grams are disabled, instead of creating a new holiday ("Select Holiday" section).
HVAC DAY SCHEDULE 1 EXAMPLE HVAC DAY SCHEDULE 2 EXAMPLE
Heating Cooling Occupied Heating Cooling Occupied
Time Time
Setpoint Setpoint Mode Setpoint Setpoint Mode
7:00a.m. 70 74 Yes 12:00a.m. 60 84 No
5:00p.m. 60 84 No
*Relative humidity setpoint is used only in reheat operation. Default setting 100" disables reheat operation.
BC Programs Example
Day of Week Holiday
Address Program
M T W T F S S H
03 A 1 1 1 1 1 1 1 1
03 B 2 2 2 2 2 2 2 2
Output Actions: On, off, light sensor (LS), smoke (SMK), lockout (LKO), and service output (SVC).