Monitoring ON/OFF Status Monitors ON/OFF status of the respective air conditioners.
only
Alarm Sign Monitors whether air conditioners are operating normally and, if not, sends out an alarm
sign.
Error Code Displays error code if an abnormality occurs in the system.
Operation Mode Monitors status of cooling, heating and ventilation operation.
Room Temperature Monitors room temperature and displays the actual room temperature.
Filter Limit Checks the limit of filters in use and monitors if there is a necessity to replace the filters.
Thermostat Status Monitors whether the thermostat in the air conditioner is operating properly.
Compressor Status Monitors whether compressors in outdoor units are operating properly.
Indoor Fan Status Monitors whether fans in the air conditioners are operating properly.
Heater Operation Status Monitors whether heaters in the air conditioners are operating properly.
PPD data Electric total power (number of indoor unit) as an object of accumulator.
3. System layout
Power Supply Additional Gateways
Gateway HUB
kWh-meter
BMS
DIII [F1/F2]
VRV
4. Compatibility
• Compatibility of Daikin BACnet Gateway with other
BACnet products can be checked by:
– BACnet PICS document
– Updated compatibility list of tested equipment
– Performing Joint Matching Test (JMT)
4. Compatibility
• BACnet PICS document:
– Protocol Implementation Conformance Statement (PICS)
– Statement of interoperability with BACnet building blocks
and standard object types + other supported items
– Latest Gateway application versions 6.10 and 6.20 included
in this syllabus
4. Compatibility
• Compatibility list of tested equipment:
BMS Model Version BMS contact person
deardenr@andovercontrols.com - Ritchie Dearden /
Andover Controls - Continuum ver. 1.6 1.6 harriss@andovercontrols.com - Steve Harris
Cimetrics Sauter - OPC Server angelo.gianelli@it.sauter-bc.com
Honeywell - EBI V2.0 jason.kelly@honeywell.com
Iconix Sauter - OPC Server
Invensys (Sacthwell)) - System Manager
Polar Soft - BACdoor emilshet@analogue.co.hk
Johnson Controls - Metasys BSI V9.01c
Johnson Controls - Metasys N30 dario.sala@jci.com
Priva -? m.polet@privaweb.com
Reliable Systems - Mach rzanotta@staefa.com.br
Siemens - System 600 Apogee Insight V3.2 wayne.moules@au.sibt.com
Siemens - System 600 Apogee Insight V3.4 tim.lo@hk.landisgyr.com
Siemens - Desigo Insight V1.01 andy.hailstone@siemens.com
Siemens - PX Desigo Insight V 2.2 andy.hailstone@siemens.com
TAC Pacific - OPC Server
Trane - Tracer Summit jstojevich@trane.com
Trend -? graham.whiting@trendcontrols.com
Tridium - Niagara Framework 2.301.321.v1 solodkin@ecoprog.ru
Trilogy -?
4. Compatibility
• Joint Matching Test:
– Exchange of documents:
• BACnet PICS
• BACnet Object List and detailed explanation
• Manual of the BMS
– Q&A about documentation
– Actual JMT Test
(with specialists of Daikin and the BMS manufacturer)
5. Possible combinations
Central Unified Schedule Parallel (Win) iTouch intelligent BACnet LON
LC 6 Airnet
Controller ON/OFF Timer Interface DACMS Controller Manager Gateway Gateway
Central
OK OK OK OK OK OK (*) OK (**) OK (**) OK (**) OK
Controller
Unified
OK OK OK OK OK OK OK (**) OK (**) OK OK
ON/OFF
Schedule
OK OK NG NG NG NG NG NG NG OK
Timer
Parallel
OK OK NG NG NG OK NG NG NG OK
Interface
(Win)
OK OK NG NG NG OK NG NG NG OK
DACMS
iTouch
OK (*) OK NG OK OK OK(*) OK (**) OK (**) OK (**) OK
Controller
intelligent
OK (**) OK (**) NG NG NG OK (**) NG OK (***) NG OK
Manager
BACnet
OK (**) OK (**) NG NG NG OK (**) OK (***) NG NG OK
Gateway
LON
OK (**) OK NG NG NG OK(**) NG NG NG OK
Gateway
LC 6 Airnet OK OK OK OK OK OK OK OK OK NG
(*) iTC & LON Gateway can only be used within address range 1-00 ~ 4-15
(**) i-Manager, BACnet & LON Gateway are always the master
(***) on special request; BACnet -> only monitoring capability, not control
S-DBL02 – BACnet Gateway Part 2: System build-up 15