Professional Documents
Culture Documents
Abstract -- This paper introduces the latest IEEE Std. 3002.8 - followed by discussions in separate sections on how to
2018 “Recommended Practice for Conducting Harmonic determine the need for a harmonic-analysis study, how to
Analysis Studies of Industrial and Commercial Power Systems”. assemble the required data and develop computer models,
The standard replaces IEEE Std. 399 (Brown Book) Chapter 10 how to perform studies, how to recognize potential harmonic
“Harmonic analysis studies” with significant enhancements and
problems, and how to apply corrective measures.
additions. The new standard addresses requirements for
performing power system harmonic-analysis studies in The standard contains the following main technical
industrial and commercial power systems due to increasing load sections:
non-linearities and control devices. Recommendations on • Analysis objectives
developing system models to include various harmonic sources • Methodology and standards
and electrical equipment and devices, preparing required data • System simulation and modeling
for modeling and studies, validating model and data, selecting
study cases, and analyzing study results and outputs are • Required data
discussed in detail in the standard. Common mitigation solutions • Data collection and preparation
for harmonic issues are presented and discussed. Features of • Model and data validation
computer aided tools that are used to perform harmonic- • Study scenarios
analysis study are reviewed. The new standard references to the
latest IEEE Std. 519-2014 “Recommended Practices and
• Solutions parameters
Requirements for Harmonic Control in Electrical Power • Results and report
Systems” for harmonic restrictions at PCC, and modeling and • Features of analysis tools
limits to interharmonics. Several examples are provided to • Illustration examples
demonstrate harmonic issues and illustrate analysis process Some main technical concepts and details of these sections
through studies for mitigations. The authors of this paper are
the co-chairs of IEEE Std. 3002.8-2018 working group.
are discussed in this paper.
Index Terms— Industrial and commercial power systems, II. COMPARISON OF NEW STANDARD AND OLD STANDARD
Codes and standards, Power system analysis, Harmonics, 3002.8-2018 Standard is based on and replaces previous
Harmonic distortions, Harmonic modeling and study, Harmonic IEEE Std. 399-1997 “IEEE Recommended Practice for
limits, Harmonic mitigations
Industrial and Commercial Power Systems Analysis” (also
known as Brown Book) [1], Chapter 10 “Harmonic analysis
I. SCOPE OF THE STANDARD
studies”, published in 1997. Twenty-one years after the
Since nonlinear devices represent an ever-increasing publication, IEEE decided to update 399 Standard and
percentage of the total load in industrial and commercial converted it into 3002 Standard series. Chapter 10 of Brown
electrical power distribution systems, harmonic-analysis Book thus is converted into IEEE Std. 3002.8
study becomes an important part of overall system design and “Recommended Practice for Conducting Harmonic Analysis
operation. By modeling power system impedances as a Studies of Industrial and Commercial Power Systems” [2].
function of frequency and harmonic sources as injecting The new standard updates information and provides more
currents or forced voltages, a harmonic study can be made to detailed discussions on basic concepts for harmonic-analysis
determine the level and effect of harmonic distortions in the study, the need for the study, recognition of potential
power system. Unless the harmonics are controlled to problems, and corrective measures. The new standard extends
acceptable limits, the power equipment and, even more so, the scope to cover required data for the study, study
the electronic equipment may be damaged, resulting in costly methodologies, and benefits of using computer as tools in a
system outages. harmonic-analysis study, and other areas.
This IEEE recommended practice describes how to Several sections are created in 3002.8-2018, with the
conduct harmonic-analysis study of industrial and intention to provide complete guidelines for engineers to
commercial power systems. The basic concepts of harmonic- understand detailed procedures and necessary steps to prepare
analysis study are described first in the standard. They are
system models and data to perform harmonic-analysis study
Authorized licensed use limited to: University of Prince Edward Island. Downloaded on June 03,2021 at 12:58:05 UTC from IEEE Xplore. Restrictions apply.
using computer aided tools. These sections are: performance, and protection. The impacts of harmonics in
industrial and commercial power systems are mainly due to
A. Data for Computer Modeling and Study
current / voltage harmonic distortions and resonances, in
As computer model and computer simulation tools have particular parallel resonance.
become a standard to perform power system studies including
harmonic-analysis study, necessary data for constructing A. Sources
computer models and performing studies are described in Basically, devices with nonlinear voltage-current
very detail in the new standard. Typical sources for the data characteristics generate harmonics. The main sources of
and importance of data validation are also discussed. harmonics in industrial and commercial power systems are
static power converters used as rectifiers for various
B. Study Scenarios
industrial applications such as adjustable speed drives (ASD),
After the system model is completed, required data are uninterruptible power system (UPS), chargers, switched-
entered and validated, the next step is to define and create mode supplies, static frequency converter, cycloconverters,
study scenarios for harmonic-analysis study. The new etc. Arc furnaces and saturated magnetic devices are also
standard offers some typical study scenarios to be considered harmonic sources. A sample industrial power system with
from system configurations, to system and equipment multiple harmonic sources is depicted in Fig. 1.
loadings, and harmonic source conditions.
C. Study Results
Recommended study results in different formats are
described and illustrated including study report, plots, study G
Authorized licensed use limited to: University of Prince Edward Island. Downloaded on June 03,2021 at 12:58:05 UTC from IEEE Xplore. Restrictions apply.
C. Harmonic Resonance A. Common Measurements
Harmonic resonance is another issue induced by electrical Commonly used harmonic distortion indices are
system frequency characteristics and harmonic currents. introduced in the standard following 519 Standard. All the
Industrial and commercial power systems are particularly at indices should be readily computed by harmonic-analysis
risk of parallel resonance. A typical parallel resonant circuit study for violation check purpose. The indices are listed in
'∑,- +
*.+ )*
"#$ 100 & 4
)/
(a) Parallel resonant configuration (b) Equivalent circuit
2. Individual Harmonic Distortion:
4∑6 6
as:
̅
1
123 57 5
calculation
5. Telephone Interference Factor:
"< 8
Fig. 3. Impedance magnitude vs. frequency for a parallel circuit
)=
)>?@
where which defines the resonance frequency:
The maximum value of Z appears at a resonance condition
2a
B. Distortion Limits
√
3002.8 Standard adapts 519 Standard for current and
2b
voltage harmonic distortion limits as shown in Tables I-1, I-2,
√
I-3 and Table II below. These limits are specified at the PCC
which is normally at the gird side of main transformer
Considering voltage at the top node of Fig. 2 (b) which is connecting to the industrial or commercial facility.
̅ ̅
given by:
3
TABLE I-1 HARMONIC CURRENT DISTORTION LIMIT FOR VOLTAGE RANGE
120 V TO 69 KV
injection is not zero, then the nodal voltage can
3≤h 11 ≤ h 17 ≤ h 23 ≤ h 35 ≤ h
if at or closer to the resonant frequency harmonic current Isc/IL TDD
< 11 < 17 < 23 < 35 ≤ 50
< 20 4.0 2.0 1.5 0.6 0.3 5.0
present excessive harmonic overvoltage causing damages to
20 < 50 7.0 3.5 2.5 1.0 0.5 8.0
the equipment connected to this node.
50 < 100 10.0 4.5 4.0 1.5 0.7 12.0
100 < 1000 12.0 5.5 5.0 2.0 1.0 15.0
IV. HARMONICS MEASUREMENTS AND LIMITS
> 1000 15.0 7.0 6.0 2.5 1.4 20.0
The new standard provides common measurements for
harmonics, and limitations to harmonic distortions at PCC
points per IEEE Std. 519, and overvoltage limits to capacitor
banks per IEEE Std. 18 [4].
Authorized licensed use limited to: University of Prince Edward Island. Downloaded on June 03,2021 at 12:58:05 UTC from IEEE Xplore. Restrictions apply.
TABLE I-2 HARMONIC CURRENT DISTORTION LIMIT FOR VOLTAGE RANGE V. HARMONIC STUDY OBJECTIVES AT DIFFERENT PHASES
69 KV TO161 KV
3≤h 11 ≤ h 17 ≤ h 23 ≤ h 35 ≤ h
The new standard discusses objectives to perform
Isc/IL TDD harmonic-analysis study and the benefits for the study. Based
< 11 < 17 < 23 < 35 ≤ 50
< 20 2.0 1.0 0.75 0.3 0.15 2.5
on different phases of a power system, objectives and
20 < 50 3.5 1.75 1.25 0.5 0.25 4.0
methodology of conducting harmonic-analysis study has
50 < 100 5.0 2.25 2.0 0.75 0.35 6.0
different focuses.
100 < 1000 6.0 2.75 2.5 1.0 0.5 7.5 A. Basic Objectives
> 1000 7.5 3.5 3.0 1.25 0.7 10.0
The standard lists following situations that may necessitate
TABLE I-3 HARMONIC CURRENT DISTORTION LIMIT FOR VOLTAGE RANGE a harmonic study:
GREATER THAN 161 KV 1. To comply with IEEE Std. 519, which defines the
3≤h 11 ≤ h 17 ≤ h 23 ≤ h 35 ≤ h current distortion limits a user should meet at PCC
Isc/IL TDD
< 11 < 17 < 23 < 35 ≤ 50 with the utility
< 25 1.0 0.5 0.38 0.15 0.1 1.5 2. To evaluate impact on the system due to utility
25 < 50 2.0 1.0 0.75 0.3 0.15 2.5 voltage harmonic distortion specified in IEEE Std.
≥ 50 3.0 1.5 1.15 0.45 0.22 3.75 519
3. To investigate root causes of a system with history
where of harmonic-related problems, such as failure of
Isc/IL is the ratio of short-circuit current in percent power-factor compensation capacitors, overheating
available at PCC to the maximum fundamental of cables, transformers, motors, and other
load current equipment, or misoperation of protective relays or
TDD is total demand distortion defined as a ratio of the control devices
root mean square of the harmonic content, 4. To plan and simulate a system expansion where
considering harmonic components up to the 50th significant nonlinear loads are added or where
order (order greater than 50 may be included significant amount of capacitance is added
when necessary) and specifically excluding 5. To design a new facility or power system where the
interharmonics, expressed as a percent of the load flow, power factor compensation, and harmonic
maximum demand current analysis are considered as one integrated study
B. Special Objectives at Design Phases
TABLE II HARMONIC VOLTAGE DISTORTION LIMIT
Bus voltage at PCC IHD (%) THD (%) During system design phase, the following factors are to
V ≤ 1.0 kV 5.0 8.0 be considered in the study:
1 kV < V ≤ 69 kV 3.0 5.0
1. Model harmonic sources from nonlinear loads and
69 kV < V ≤ 161 kV 1.5 2.5
power electronics devices, simulate their impacts,
161.001 kV < V 1.0 1.5a
and assess harmonic voltage and current distortion
levels
C. Resonance Limits 2. Calculate harmonic distortion indices for both
One of the focuses on parallel resonance is for capacitor voltage and current
banks. IEEE Std. 18 specifies voltage limitations to shunt 3. Compare distortion levels and harmonic indices with
capacitor banks in terms of manufacturer limits or the the standard and code limits to see if there are any
maximum rating permitted: violations
1. Continuous operating voltage ≤ 110% of the rated 4. Identify system parallel or series resonance
voltage frequencies and locations
2. rms crest voltage ≤ 1.2 times the rated rms voltage 5. Check if there are any harmonic source frequencies
3. kvar ≤ 135% of the rated kvar at or near the system parallel resonance points
4. Current ≤ 180% of the rated rms currents 6. If there are harmonic source frequencies at or near
Where continuous operating voltage, rms crest voltage, and the system parallel resonance points, assess the
current should include harmonic components, especially overvoltage conditions at these frequency points
resonance voltage. 7. If there are harmonic source frequencies at or near
Relocate the capacitors or change the bank ratings if they the system series resonance points, assess the
are found to exceed their ratings; apply a detuning reactor if a overcurrent conditions
resonance condition is found. 8. If necessary, design and test harmonic mitigation
methods such as:
• Install harmonic filters to reduce the harmonic
distortion levels and shift resonance frequencies
Authorized licensed use limited to: University of Prince Edward Island. Downloaded on June 03,2021 at 12:58:05 UTC from IEEE Xplore. Restrictions apply.
to less harmful regions A. Modeling of Harmonic Sources
• Use transformer phase shift to cancel harmonics Most harmonic sources present themselves to the rest of
and obtain overall harmonic distortion reduction system as current sources. Based on non-linear device
9. Simulate the final system for overall harmonic characteristics, harmonic current sources can be modeled
voltage and current distortions after harmonic differently.
mitigations are implemented 1. Characteristic harmonics
C. Special Objectives at Operation Phase Harmonics generated by pulse converters are well-
known. The magnitude of the harmonic current is given
For systems in operation phase, harmonic-analysis study
by [1]:
B 9
C/
should be done to simulate various operating conditions and
B
configurations to verify if there are any excessive harmonic
distortions and harmful parallel resonances under all possible
10. Test transformer phase shift and analyze its effects Harmonic Spectrum
to harmonic current cancellation and harmonic 100
distortion deduction
Magnitude (%)
80
11. Test other harmonic mitigation designs and 60
performance 40
20
VI. COMPUTER MODELING FOR 0
HARMONIC-ANALYSIS STUDIES 1 5 7 11 13 17 19 23 25 29 31 35 37
Order (h)
Harmonic sources are the reason why harmonic-analysis
study need to be done. Depending on their types, harmonic Fig. 4. Harmonic magnitude spectrum
sources can be presented as characteristic harmonics and
interharmonics. From system modeling point of view, 2. Interharmonics
harmonics generally are represented as injected currents into Some devices and equipment in power systems can
the system. generate currents that contain components that are non-
Authorized licensed use limited to: University of Prince Edward Island. Downloaded on June 03,2021 at 12:58:05 UTC from IEEE Xplore. Restrictions apply.
integer multipliers to the fundamental frequency. These or published data
components are called interharmonics. Devices and When multiple harmonic sources exist in the same
situations that can result in interharmonics in industrial system, phase angles between the harmonics of the same
and commercial power systems are cycloconverters, order can change study results. Determination of phase
ASDs, and loads that do not pulsate synchronously with angles of harmonics can be quite complex but should not
the fundamental power system frequency. Arc furnaces be ignored.
and some other loads can also produce interharmonics. For unbalanced three-phase systems, it is desirable to
Interharmonics generated from the first group of determine the harmonics generated in all three phases.
devices and situations can be expressed in Eq. (10) per
B. Modeling of Network Equipment
reference [3]:
[ VW ± 1 5 ± !W \
Modeling of each power system component and device
(10) must be properly done in harmonic-analysis study. The new
dB d√ℎ
The phase sequence of interharmonics requires
e"g "h i
B ℎ , or B
special attention to determine, because it is important in
harmonic power flow studies. Details on interharmonics, R is machine resistance derived from
their origin, phase sequence, and special issues in the machine power loss at fundamental
dB d= √ℎ
(b) Waveform including interharmonics
B ℎ=
Fig. 5. Interharmonic voltages from an ASD
Authorized licensed use limited to: University of Prince Edward Island. Downloaded on June 03,2021 at 12:58:05 UTC from IEEE Xplore. Restrictions apply.
d ,
l+ l+
m n
in typical industrial and commercial power systems. As
dB d√ℎ, B ℎ system modeling and data collection are vital to harmonic-
d and are equivalent load resistance analysis study, Table IV also shows recommended data
: and o are active and reactive load on
and reactance sources for data collection.
the bus
TABLE IV
Fig. 8. Modeling of passive loads
REQUIRED DATA FOR HARMONIC-ANALYSIS
Component Data Source
4. Shunt capacitor Single-line diagram of the power
Shunt capacitors are modeled by capacitor impedance System
system; System configurations; Design and maintenance
Maximum expected operating documentation
(or admittance) and existing loss and discharge resistance voltages at nonlinear loads
in Fig. 9. Bus nominal voltage, harmonic
Manufacturer provided
z1
commissioning test
v 0.05012y
djr
Machine manufacturer-
= length (m)
cylindrical wire Transmission Length, sequence impedance and Manufacturer provided
+ (Ω/m)
Long line:
line admittance, frequency data sheet plus any testing
+ (S/m)
Cable characteristics of impedance data
r y
Bus duct
Current
Sequence impedance, and Manufacturer provided
r !ℎu
limiting
frequency characteristics of data sheet plus any testing
1 u
reactor
!ℎ
impedance. data
2 r 2
Other circuit
element
Fig. 10. Modeling of lines and cables MVA/kVA rating, rated voltages,
sequence impedance and X/R ratio,
three-phase connection and
6. Other equipment Transformers grounding types. If the transformer
Nameplate plus any
testing data
Other system components are modeled with harmonics due to in-rush or
saturation are to be considered, then
necessary frequency adjustments for resistive and harmonic spectrum
inductive impedance. Shunt
The three-phase connections, kvar, Manufacturer provided
capacitors
C. Required Data for Modeling and Analysis Shunt
and kV ratings, sequence data sheet plus any testing
impedance or admittance data
To help engineers understand data requirement for system reactors
Bus connection, rated MVA/kVA,
modeling and study, standard recommends required data for rated voltage, initial loading, phase Load name plate plus any
harmonic-analysis study and suggested sources for data Loads
connection and grounding type, testing data
information. Since both characteristic harmonic and frequency characteristics of the load
Authorized licensed use limited to: University of Prince Edward Island. Downloaded on June 03,2021 at 12:58:05 UTC from IEEE Xplore. Restrictions apply.
test data concerned buses. The peak points on the curves indicate
Type and structure, resistance,
resonance conditions with bus and frequency information.
reactance, and capacitance for all At the identified resonance frequencies, bus impedances
There are two basic study types for harmonic-analysis When , [ is called self-impedance; otherwise is
study. Both are important with different emphasis and called transfer-impedance.
purpose. The analysis then computes total harmonic voltages at
A. Harmonic Power Flow Study these buses by multiplying the bus impedances with harmonic
Harmonic power flow study models harmonic generation current injections from the entire network at the
from nonlinear power system devices by injecting harmonic corresponding frequencies.
currents into the network. Harmonic current sources are C. Typical Harmonic Study Scenarios
expressed in a series of harmonics. The electrical system is Harmonic-analysis study should cover operations in both
modeled as a network based on impedance at the given normal and abnormal conditions, especially the worst cases,
harmonic. A nodal voltage equation is formulated to solve in order to better understand system situations from a
nodal voltages as shown in Eq. (11). harmonic perspective. This is achieved by defining and
11
modes. Usually, the worst operating condition needs to be
determined, and the design should be based on the “worst-
generated” harmonics case. It needs to be recognized that
[ ℎ is Y-Bus matrix element corresponding to branch
where
even with the “worst-generated” harmonic case, the harmonic
flows within different elements of the network can be
admittance between nodal i and nodal j at harmonic different, depending on system configuration. This
[ ℎ is nodal voltage at nodal i at harmonic h
h necessitates that the “worst-generated” case at the “worst-
A more detailed description of power flow type harmonic- Harmonic Design and tune mitigation configurations and parameters,
mitigations and evaluate improvement in harmonic distortions and
analysis method can be found in chapter 7 of “Tutorial on resonances
harmonics modeling and simulation” by IEEE Power Equipment rating Study and evaluate impacts of system equipment ratings and
Engineering Society. [6]. and impedance impedance to harmonic distortions and resonances
Authorized licensed use limited to: University of Prince Edward Island. Downloaded on June 03,2021 at 12:58:05 UTC from IEEE Xplore. Restrictions apply.
modeling and studies, violation evaluation, and necessary
mitigation actions. High-pass C-
Rerun of complete system studies with selected type filter
(third order)
mitigations are very important for validating and tuning
parameters in mitigation designs. This loop may take a few
iterations.
A single-tuned filter is used to suppress a specific
Single-Line harmonic at or near the tuned frequency. High-pass filters can
Diagram
be of first, second, or third order. The second-order filter is
Utility Data
Harmonic Source Equipment Data Harmonic
Limitations
often used to suppress higher frequencies. A C-type high-pass
Data
filter is becoming popular due to its exhibiting smaller losses
Computer Model at the fundamental frequency.
Load Flow Study Generally, filters are tuned at one of the dominant
for Max Load harmonics starting from the lowest order. Ideally, the filters
Harmonic Study should be tuned to the exact harmonic order; however, the
Cases
practical considerations may require tuning it slightly below
Harmonic
the desired frequency.
Harmonic Power Frequency Scan
Flow Study Study
The two main components of passive filters are capacitors
and reactors. Be aware that capacitor voltage can increase
Harmonic Harmonic (above the bus voltage) due to impedance cancellation at the
Distortions Resonance
tuned frequency and make sure proper voltage ratings for
Yes Harmonic capacitors being selected. Once the harmonic study is
Violations? Mitigations
completed and the filter selection has been made, the
No capacitor rating with respect to operating voltage, current,
Fig. 11. Harmonic study procedures and kvar under harmonics should be checked. All these
ratings need to be satisfied independently according to IEEE
VIII. HARMONIC MITIGATIONS Std. 18. Also, similar importance is to pay attention to total
The new standard discusses a few commonly used current that reactors need to carry including harmonic
harmonic mitigation methods. currents so that the reactors are sized correspondingly.
TABLE VI
FILTERS COMMONLY USED FOR HARMONIC MITIGATION
Type Structure Impedance vs. frequency
Single-tuned
filter
High-pass filter
(second order)
Fig. 12. Multipulse converter arrangements
Authorized licensed use limited to: University of Prince Edward Island. Downloaded on June 03,2021 at 12:58:05 UTC from IEEE Xplore. Restrictions apply.
TABLE VII
CHARACTERISTIC AC LINE HARMONIC CURRENTS IN MULTIPULSE SYSTEMS
Rectifier system pulse Harmonic Harmonic current in
Harmonic number percent of fundamental
Frequency
(Hz)
6 12 18 24 Theoretical Typical
35 x x x 2100 2.86 1.10 Typical voltage harmonic spectrum is assumed for the arc
37 x x x 2220 2.70 1.00
furnace (Fig. 14), and typical IEEE 6-pulse current harmonic
spectrum is assumed for the ASD (Fig. 15).
41 x 2460 2.44 0.90
IX. ILLUSTRATION EXAMPLES Fig. 15. ASD current harmonic spectrum (IEEE typical 6-pulse)
Sample system 3 in the new standard is a sample industry Initial harmonic power flow study shows excessive
complex (Fig. 13). The system contains nonlinear loads of arc harmonic distortions both in voltage and current in the
furnace connected to Bus A and ASD to Bus B. There are system. As mitigations, passive filtering is selected for the arc
power factor–correcting capacitor banks (inside subsystem) furnace, and transformer phase shifting is selected for the
too. ASD. Fig. 16 shows configurations of the mitigations.
Authorized licensed use limited to: University of Prince Edward Island. Downloaded on June 03,2021 at 12:58:05 UTC from IEEE Xplore. Restrictions apply.
adds discussions on common study cases and typical study
results. 3002.8-2018 further addresses a number of important
issues including interharmonics and the latest IEEE 519
recommended harmonic limits at PCC, and some useful
features in computer software for performing harmonic-
analysis study. The new standard provides three cases as
comprehensive illustrations of harmonic-analysis study. The
new standard also offers very detailed step by step guidelines
for engineers who need to conduct harmonic-analysis study.
REFERENCES
[1] IEEE Recommended Practice for Industrial and Commercial Power
(a) Arc Furnace mitigation by filters (b) ASD mitigation by transformer Systems Analysis, IEEE Standard 399, 1997.
Fig. 16. Harmonic mitigation for arc furnace and ASD [2] IEEE Recommended Practice for Conducting Harmonic Studies and
Analysis of Industrial and Commercial Power Systems, IEEE Standard
3002.8, 2018.
Based on study results before the filters are installed, 2nd, [3] IEEE Recommended Practice and Requirements for Harmonic Control
5 , and 7th harmonics have the higher magnitude for arc
th
in Electric Power Systems, IEEE Standard 519, 2014.
furnace. Thus, three single-tuned filters at these frequencies [4] IEEE Standard for Shunt Capacitors, IEEE Standard 18, 2012.
are designed and installed. Using harmonic power flow study, [5] IEEE Task Force on Harmonics Modeling and Simulation,
“Interharmonics: theory and modeling,” IEEE Transactions on Power
the mitigations can be validated. Fig. 17 compares Arc Delivery, vol. 22, no. 4, pp. 2335–2347, Oct. 2007.
Furnace feeder current distortion with (in red) and without (in [6] M. Halpin, P. Ribeiro, and J.J. Dai, Chapter 7, “Frequency-Domain
blue) the filters. Harmonic-analysis Methods”, IEEE Power Engineering Society,
Tutorial on harmonics modeling and simulation, IEEE catalog no.
98TP125-0, 1998.
Authorized licensed use limited to: University of Prince Edward Island. Downloaded on June 03,2021 at 12:58:05 UTC from IEEE Xplore. Restrictions apply.