Lindø shipyard NB211-216

HVAC plant

Revision: 1.1

YORK Marine, Controls


Operator manual
Lindø shipyard NB211-216

Lindø shipyard NB211-216

Table of Contents
1 E1071 OPERATOR MANUAL 3
1.1 E1071 in General 3
1.1.1 Hot keys 3
1.1.2 Common objects (symbols) 4
1.1.3 Using the input fields. 6
1.1.4 Password 6
1.1.5 Alarm picture 7
1.1.6 PICTURE HIERARCHY 9

2 PICTURES ON THE E1071 PANEL 10


2.1 Main Menu 10
2.2 HVAC plant picture 11
2.3 Bridge AHU picture 12
2.4 Main AHU picture 13
2.5 Galley AHU picture 14
2.6 ECR 1-2 AHU picture 15
2.7 Workshop AHU picture 16
2.8 Main/Bridge/ECR AHU setup picture 17
2.9 Galley/Workshop AHU setup picture 18
2.10 Main/Bridge/ECR AHU compensation setup picture 19
2.11 AHU supply cooling setup picture 20
2.12 AHU heating setup picture 21
2.13 AHU alarm setup picture 22
2.14 AHU enthalpy exchanger picture 23
2.15 AHU humidity system picture 24
2.15.1 AHU humidity system setup picture 25
2.16 Hot water system picture 26
2.16.1 Hot water system setup picture 27
2.17 Trend choice picture 28
2.17.1 Trend picture 29
2.18 Setup parameter picture 30
2.18.1 Communication network picture 31
2.18.2 Master PLC status picture 32
2.18.3 4-20mA scaling picture 33

3 ALARM LIST 34
Document Revision Record 36

Table of Contents YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 2 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

1 E1071 OPERATOR MANUAL

1.1 E1071 in General


The E1071 operator panel is available on the starter panel and intended for supervision and control of the
chiller plant.

The E1071 is a finger-touch screen where all commands are made. By pressing specific areas on the screen
the display will change pictures, thus commands can be given or parameters can be changed.

1.1.1 Hot keys


By touching one of the icons in the bottom line of the screen it is possible to jump between the plant pictures.

When touching the MAIN icon in the upper left corner, the Main picture will appear on the screen.
Touching the ALARM icon in the upper right corner of the picture enables the alarm list to appear.

Table of Contents YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 3 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

1.1.2 Common objects (symbols)

A movement key.
Tap this key to jump to (in this case) the “PLANT” menu.

A status text.
Example: Status of the compressor.

A monitored value.
Example: Actual temperature.

An input field. Can be a selection box, numeric or an alphanumeric field.


Tap on the field to access the keyboard.
Some fields are protected by a password.

Symbol for a heating and cooling coils.

Symbol for a heating and cooling coils.


This indicates that a sub menu is available.
Tap on the symbol to access the sub menu.

Symbol for a fan motor.

Symbol for a fan motor.


This indicates that a sub menu is available.
Tap on the symbol to access the sub menu.

Symbol for a stop push buttons.


Tap button to activate.

Active Not active

Table of Contents YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 4 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

Symbol for a start push buttons.


Tap button to activate.

Active Not active

Symbol for a start/increase push buttons.


Tap button to activate.

Active Not active

Symbol for a stop/decrease push buttons.


Tap button to activate.

Active Not active

Symbol for a manual/auto mode push buttons.


Tap button to activate.

Manual Auto

PS: Pressure switch. TS: Temperature switch. Closed contact.

PS: Pressure switch. TS: Temperature switch. Open contact.

ƒ The compressor/pump/fan is stopped.


ƒ The compressor/pump/fan is running


ƒ The compressor/pump/fan is interlocked.


ƒ The compressor/pump/fan is ready for start.


ƒ The compressor/pump/fan is stopped due to an error. See alarm list.


Table of Contents YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 5 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

1.1.3 Using the input fields.


There are four different input fields: A selection box, a confirmation, numeric or an alphanumeric field.
To alter a value, tap the field.
This will display the input keyboard or selection box.
Some fields require confirmation of the new value before it is changed.

Numeric input Alphanumeric input

Selection box Confirmation box

1.1.4 Password
Some inputs require a password. This password is “1266”.
A requester similar to the alphanumeric input field pops up when the password is required.

Table of Contents YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 6 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

1.1.5 Alarm picture

Main

ALARM
Tap
”ALARM”

The following picture presents details of the alarms.

1 2 3 4 5

10

11

12

The Alarm status symbol

Symbol Colour Status


Back ground Text
* Red White Active, Not acknowledged
$ Red Yellow Not active, Not acknowledged
- Grey Yellow Active, Acknowledged
<blank> Grey Black Not active, Acknowledged

By touching the alarm line more information will pop up.

The format of the showing time

Symbol Status
S Time indicating when the alarm was activated
E Time indicating when the alarm was made inactive
A Time indicating when the alarm was acknowledged

Date (see point 2 for the type format)

Time (see point 2 for the type format)

Table of Contents YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 7 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

The alarm text

Escape to previous picture

Scroll up the alarm list

Acknowledge the alarm

Increase the font size

Reserved for expansion

Switch on/off the date and time stamp

Scroll down the alarm list

Table of Contents YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 8 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

1.1.6 PICTURE HIERARCHY

Bridge Alarm
Main
AHU setup

Humidity
Humidity
setup

setup Compensation

Cooling
Heating

Alarm
Main AHU
setup

Humidity
Humidity
setup

Enthalpy

setup Compensation
SETUP NET
Cooling
Heating AD
PLC CPU
Modul 5

Galley Alarm
AHU setup

setup
Cooling
Heating
Trend
ECR 1-2 Alarm
AHU setup
Bridge
AHU
setup Compensation
Main
Cooling
AHU
Heating
Galley
Workshop Alarm AHU
AHU setup
ECR1
AHU
setup
ECR2
Cooling
AHU
HVAC Heating
plant Workshop
AHU
Hot water Setup

Alarm

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 9 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2 PICTURES ON THE E1071 PANEL


The following subsections describe supervision and control of the refrigeration plant from the E1071 panel.
Please refer to other sections of the present instruction.

2.1 Main Menu


The Main Menu (starting picture) is shown below.

8 2 4 3

9 10 5 7 6

The various buttons lead to pictures as follows:

Date and time can be changed from the “Setup parameter picture” on page 30

HVAC plant picture on page 11 Hot water system picture on page 26

Bridge AHU picture on page 11 System setup picture on page 30

Main AHU picture on page 13 Trends picture on page 28

Galley AHU picture on page 14

ECR AHU picture on page 15

Workshop AHU picture on page 15

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 10 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.2 HVAC plant picture


The following picture gives an overview of the AHU and the fan status.

The actual temperature for AHU.

The actual AHU control status


Status Description
OFF The AHU is switch off
Ready cool The AHU is ready for cooling
Heating The heating function is activated
Cooling The supply air regulation function is activated
Sensor error Sensor error
Ventilation The AHU fan is only run

Touching the icon leads to the picture described AHU’s from page 13

The actual chiller pump status.

The actual chiller unit status.

The actual chiller water temperatures.

chiller unit status (REMOTE and LOCAL mode control.)REMOTE = ICS


Press the icon and the HVAC plant will change between the REMOTE and LOCAL mode control.
REMOTE = ICS

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 11 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.3 Bridge AHU picture


The following picture presents an overview of the bridge AHU.

2
5
3

The actual AHU control status

Status Description
Fan off The AHU is switch off
Ready cooling The AHU is ready for cooling
Heating The heating function is activated
Cooling The supply air regulation function is activated
Sensor error Sensor error
Ventilation The AHU fan is only run

The Fan symbols show the status as shown in 1.1.2 Common objects (symbols).

The switch symbols show the status as shown in 1.1.2 Common objects (symbols)

The valve symbols show the status up or downward.

The humidity symbols show the status as shown in 1.1.2 Common objects (symbols).
Touching the icon leads to the setup picture.

Touching the icon leads to the picture described”Main/Bridge/ECR AHU setup picture” on page 16

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 12 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.4 Main AHU picture


The following picture presents an overview of the main AHU.

3 5
7

The actual AHU control status

Status Description
Fan off The AHU is switch off
Ready cooling The AHU is ready for cooling
Heating The heating function is activated
Cooling The supply air regulation function is activated
Sensor error Sensor error
Ventilation The AHU fan is only run

The Fan symbols show the status as shown in 1.1.2 Common objects (symbols).

The switch symbols show the status as shown in 1.1.2 Common objects (symbols)

The valve symbols show the status up or downward.

The humidity symbols show the status as shown in 1.1.2 Common objects (symbols).
Touching the icon leads to the setup picture.

Touching the icon leads to the picture described”Main/Bridge/ECR AHU setup picture” on page 16

The enthalpy symbols show the status as shown in 1.1.2 Common objects (symbols).
Touching the icon leads to the setup picture.
Error! No text of specified style in document. YORK Marine, Controls
Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 13 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.5 Galley AHU picture


The following picture presents an overview of the galley AHU.

2
3

The actual AHU control status

Status Description
Fan off The AHU is switch off
Ready cooling The AHU is ready for cooling
Heating The heating function is activated
Cooling The supply air regulation function is activated
Sensor error Sensor error
Ventilation The AHU fan is only run

The Fan symbols show the status as shown in 1.1.2 Common objects (symbols).

The switch symbols show the status as shown in 1.1.2 Common objects (symbols)

The valve symbols show the status up or downward.

Touching the icon leads to the picture described “Galley/Workshop AHU setup picture” on page 18

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 14 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.6 ECR 1-2 AHU picture


The following picture presents an overview of the ECR 1-2 AHU.

The actual AHU control status

Status Description
Fan off The AHU is switch off
Ready cooling The AHU is ready for cooling
Heating The heating function is activated
Cooling The supply air regulation function is activated
Sensor error Sensor error
Ventilation The AHU fan is only run

The Fan symbols show the status as shown in 1.1.2 Common objects (symbols).

The valve symbols show the status up or downward.

Touching the icon leads to the picture described”Main/Bridge/ECR AHU setup picture” on page 16

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 15 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.7 Workshop AHU picture


The following picture presents an overview of the workshop AHU

The actual AHU control status

Status Description
Fan off The AHU is switch off
Ready cooling The AHU is ready for cooling
Heating The heating function is activated
Cooling The supply air regulation function is activated
Sensor error Sensor error
Ventilation The AHU fan is only run

The Fan symbols show the status as shown in 1.1.2 Common objects (symbols).

The valve symbols show the status up or downward.

Touching the icon leads to the picture described “Galley/Workshop AHU setup picture” on page 18

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 16 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.8 Main/Bridge/ECR AHU setup picture


The following pictures allow the operator to change parameters:

Fig1.0 Fig1.1

1 1

2 2
9 9

3 3
8 8

4 4
7 7

5 5
6 6

Fig1.0 Actual regulation supply Set point with return compensation (Only reading values)
For more details about the set point see section “System description”

Fig 1.1 Regulation supply Set point with out return compensation (Only modify values)
For more details about the set point see section “System description”

The set point mode can be set.

The parameter for the preheat set point can be set. (Only main AHU)

The limit for started heating can be set.


For more details about the parameter see section “System description”

The limit for started cooling can be set.


For more details about the parameter see section “System description”

Touching the icon leads to the picture described “Main/Bridge/ECR AHU compensation setup
picture” on page 19

Touching the icon leads to the picture”AHU heating setup picture” on page 21

Touching the icon leads to the picture described “AHU supply cooling setup picture” on page 20

Touching the icon leads to the picture described “AHU alarm setup picture” on page 22

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 17 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.9 Galley/Workshop AHU setup picture


The following pictures allow the operator to change parameters:

The parameter for supply set point can be set.


For more details about the parameter see section “System description”

The limit for started heating can be set.


For more details about the parameter see section “System description”

The limit for started cooling can be set.


For more details about the parameter see section “System description”

The limit for started cooling can be set.


For more details about the parameter see section “System description”

Touching the icon leads to the picture described “AHU supply cooling setup picture” on page 20

Touching the icon leads to the picture described “AHU alarm setup picture” on page 22

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 18 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.10 Main/Bridge/ECR AHU compensation setup picture


The following pictures allow the operator to change parameters.

The max and min limit for supply set point can be set.
For more details about the parameter see section “System description”

The parameter for return compensation on the supply set point can be set.
For more details about the parameter see section “System description”

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 19 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.11 AHU supply cooling setup picture


The following pictures allow the operator to change parameters.

The parameter for supply regulation of the expansion valve can be set.
For more details about the parameter see section 4 “System description”

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 20 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.12 AHU heating setup picture


The following pictures allow the operator to change parameters.

The parameter for Preheat regulation of the motor valve can be set. (Only main AHU)
For more details about the parameter see section “System description”

The parameter for main heat regulation of the motor valve can be set.
For more details about the parameter see section “System description”

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 21 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.13 AHU alarm setup picture


The following pictures allow the operator to change parameters.

The alarm limit for supply temperature can be set.


For more details about the parameter see section “System description”

The alarm limit for return or exhaust temperature can be set.


For more details about the parameter see section “System description”

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 22 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.14 AHU enthalpy exchanger picture


The following pictures allow the operator to change parameters and commands.

When push on the “OFF” icon, a stop command will be send to the exchanger starter.
When push on the “ON” icon, a start command will be send to the exchanger starter.
When push on the “AUTO” icon, the exchange will be started/stopped from the control.

The Fan symbols show the status as shown in 1.1.2 Common objects (symbols).

Show the status of the exchanger

text description
STOPPED The exchanger is stopped
RUNNING The exchanger are running
READY The exchanger are ready for run
ALARM The exchanger in alarm

The high outdoor temperature limit for started the exchanger can be set.

The low outdoor temperature limit for started the exchanger can be set.

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 23 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.15 AHU humidity system picture


The following pictures allow the operator to change parameters and commands.

When push on the “OFF” icon, a stop command will be send to the humidity controller.
When push on the “ON” icon, a start command will be send to the humidity controller.

The actual humidity control status


text description
STOPPED The humidity control is stopped
RUNNING The humidity control are running
READY The humidity control are ready for run
ALARM The humidity control in alarm

The parameter for humidity set point can be set.


For more details about the parameter see section “System description”

The limits for starting humidity control can be set.


For more details about the parameter see section “System description”

The PLC control signal to humidity unit.

Touching the icon leads to the picture described “AHU humidity system setup picture” on page 24

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 24 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.15.1 AHU humidity system setup picture


The following pictures allow the operator to change parameters

The parameter for humidity control can be set.


For more details about the parameter see section “System description”

The high alarm limit for humidity can be set.


For more details about the parameter see section “System description”

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 25 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.16 Hot water system picture


The following picture presents an overview of the hot water

The Pumps symbols show the status as shown in 1.1.2 Common objects (symbols).

The Valve symbols show the status as shown in 1.1.2 Common objects (symbols).

Touching the icon leads to the picture described, “Hot water system setup picture” on page 27

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 26 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.16.1 Hot water system setup picture


The following pictures allow the operator to change parameters.

The parameter for hot water regulation of the motor valve can be set.
For more details about the parameter see section “System description”

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 27 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.17 Trend choice picture


In the following picture the required trend can be chosen

Touching the icon leads to the picture described “Trend picture” on page 29

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 28 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.17.1 Trend picture


The following is an example of a trend picture:

Touching will open the history trend picture, where date and time can be changed.

Shows the actual value, and the colour for the trends.

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 29 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.18 Setup parameter picture


In the following picture you can make common settings for the plant.

1 2 3

Touching the button will bring you to the “Matser PLC status picture” on page 39.

Touching the button will bring you to the display status.

Touching the button will bring you to the “communication network picture” on page 31.

The operator panel Time and date can be set.

HMI software version:


PLC software version:
Project number: The internal YORK Marine project number.

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 30 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.18.1 Communication network picture


The following picture shows the network status.

Press to see status of the Masters PLC.

Press to see status of the Slave PLC and the analogue sensors setup.

The Profibus communication line status

Colour Description
Red The communication is offline (PLC in stop mode, master disconnected or cable broken)
Grey The communication is online

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 31 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.18.2 Master PLC status picture


The following picture presents details of the PLC modules.

Error code
Normal condition: Value = 0.
Contact YORK in all other cases.

CPU
Normal condition is “running”.
Condition “stopped”:
To the left of the circular plug is placed a “Run / Stop” switch.
The switch must be in “Run” position.

Battery
Status for battery

Touching the button brings you to the picture described in “4-20mA scaling picture”,

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 32 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

2.18.3 4-20mA scaling picture


In the following picture the 4-20mA scaling for analogue input modules has to be set.

1 2 3

4mA for the analogue sensors can be set.

20mA for the analogue sensors can be set.

The actual analogue value.

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 33 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

3 ALARM LIST
Alarm text Description
AHU Main Enthalpy run error The motor has tripped the over current relay.
The relay must be manually reset inside the switchboard.
AHU Main humidity sensor Error Humidity sensor failing or missing signal.
Check sensor and wires.
AHU Main high humidity Alarm Humidity is higher than alarm limit.
AHU Main high return temp Alarm Return air temperature is higher than alarm limit.
AHU Main low return temp Alarm Return air temperature is lower than alarm limit.
AHU Main return temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU Main high supply temp Alarm Supply air temperature is higher than alarm limit.
AHU Main low supply temp Alarm Supply air temperature is lower than alarm limit.
AHU Main supply temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU Main KP61 low temp Alarm Temperature on heating coil is too cold.
Risk of severe freezing damage to the coil is imminent.
AHU Bridge humidity sensor Error Humidity sensor failing or missing signal.
Check sensor and wires.
AHU Bridge high return temp Alarm Return air temperature is higher than alarm limit.
AHU Bridge low return temp Alarm Return air temperature is lower than alarm limit.
AHU Bridge return temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU Bridge high supply temp Alarm Supply air temperature is higher than alarm limit.
AHU Bridge low supply temp Alarm Supply air temperature is lower than alarm limit.
AHU Bridge supply temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU Bridge KP61 low temp Alarm Temperature on heating coil is too cold.
Risk of severe freezing damage to the coil is imminent.
AHU Bridge high humidity Alarm Humidity is higher than alarm limit.
AHU Galley high supply temp Alarm Supply air temperature is higher than alarm limit.
AHU Galley low supply temp Alarm Supply air temperature is lower than alarm limit.
AHU Galley supply temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU Galley KP61 low temp Alarm Temperature on heating coil is too cold.
Risk of severe freezing damage to the coil is imminent.
AHU Workshop high supply temp Alarm Supply air temperature is higher than alarm limit.
AHU Workshop low supply temp Alarm Supply air temperature is lower than alarm limit.
AHU Workshop supply temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU ECR1 high supply temp Alarm Supply air temperature is higher than alarm limit.
AHU ECR1 low supply temp Alarm Supply air temperature is lower than alarm limit.
AHU ECR1 supply temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU ECR2 high supply temp Alarm Supply air temperature is higher than alarm limit.
AHU ECR2 low supply temp Alarm Supply air temperature is lower than alarm limit.
AHU ECR2 supply temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU ECR12 high return temp Alarm Return air temperature is higher than alarm limit.
AHU ECR12 low return temp Alarm Return air temperature is lower than alarm limit.
AHU ECR12 return temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 34 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

Alarm text Description


Hot water temp sensor error Temperature sensor failing or missing signal.
Check sensor and wires.
Chiller supply temp sensor error Temperature sensor failing or missing signal.
Check sensor and wires.
Chiller return temp sensor error Temperature sensor failing or missing signal.
Check sensor and wires.
Chiller unit compressor 1 alarm
Chiller unit compressor 2 alarm
Chiller pump 1-2 alarm
Profibus communication error ICS Communication error to Master Profibus PLC in ICS.
Profibus communication error I/O Communication error to I/O Profibus PLC in panel
PLC Battery low - To be replaced The PLC CPU memory backup battery is low on power.
Replace according to the panel manual.
PLC CPU Error The PLC CPU is failing. Contact YORK.
PLC CPU is not in run-mode The PLC CPU is stopped.
To the left of the circular plug is placed a “Run / Stop”
switch.
The switch must be in “Run” position.
Flipping the switch from “Run” to “Stop” and back may
solve the problem.

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 35 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216

Document Revision Record


Rev. Date Author Brief description of change Pages affected
1.0 070903 MNI Original issue All
1.1 080326 MNI Reissue 11-16

Error! No text of specified style in document. YORK Marine, Controls


Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 36 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc