HVAC plant
Revision: 1.1
Table of Contents
1 E1071 OPERATOR MANUAL 3
1.1 E1071 in General 3
1.1.1 Hot keys 3
1.1.2 Common objects (symbols) 4
1.1.3 Using the input fields. 6
1.1.4 Password 6
1.1.5 Alarm picture 7
1.1.6 PICTURE HIERARCHY 9
3 ALARM LIST 34
Document Revision Record 36
The E1071 is a finger-touch screen where all commands are made. By pressing specific areas on the screen
the display will change pictures, thus commands can be given or parameters can be changed.
When touching the MAIN icon in the upper left corner, the Main picture will appear on the screen.
Touching the ALARM icon in the upper right corner of the picture enables the alarm list to appear.
A movement key.
Tap this key to jump to (in this case) the “PLANT” menu.
A status text.
Example: Status of the compressor.
A monitored value.
Example: Actual temperature.
Manual Auto
1.1.4 Password
Some inputs require a password. This password is “1266”.
A requester similar to the alphanumeric input field pops up when the password is required.
Main
ALARM
Tap
”ALARM”
1 2 3 4 5
10
11
12
Symbol Status
S Time indicating when the alarm was activated
E Time indicating when the alarm was made inactive
A Time indicating when the alarm was acknowledged
Bridge Alarm
Main
AHU setup
Humidity
Humidity
setup
setup Compensation
Cooling
Heating
Alarm
Main AHU
setup
Humidity
Humidity
setup
Enthalpy
setup Compensation
SETUP NET
Cooling
Heating AD
PLC CPU
Modul 5
Galley Alarm
AHU setup
setup
Cooling
Heating
Trend
ECR 1-2 Alarm
AHU setup
Bridge
AHU
setup Compensation
Main
Cooling
AHU
Heating
Galley
Workshop Alarm AHU
AHU setup
ECR1
AHU
setup
ECR2
Cooling
AHU
HVAC Heating
plant Workshop
AHU
Hot water Setup
Alarm
8 2 4 3
9 10 5 7 6
Date and time can be changed from the “Setup parameter picture” on page 30
Touching the icon leads to the picture described AHU’s from page 13
2
5
3
Status Description
Fan off The AHU is switch off
Ready cooling The AHU is ready for cooling
Heating The heating function is activated
Cooling The supply air regulation function is activated
Sensor error Sensor error
Ventilation The AHU fan is only run
The Fan symbols show the status as shown in 1.1.2 Common objects (symbols).
The switch symbols show the status as shown in 1.1.2 Common objects (symbols)
The humidity symbols show the status as shown in 1.1.2 Common objects (symbols).
Touching the icon leads to the setup picture.
Touching the icon leads to the picture described”Main/Bridge/ECR AHU setup picture” on page 16
3 5
7
Status Description
Fan off The AHU is switch off
Ready cooling The AHU is ready for cooling
Heating The heating function is activated
Cooling The supply air regulation function is activated
Sensor error Sensor error
Ventilation The AHU fan is only run
The Fan symbols show the status as shown in 1.1.2 Common objects (symbols).
The switch symbols show the status as shown in 1.1.2 Common objects (symbols)
The humidity symbols show the status as shown in 1.1.2 Common objects (symbols).
Touching the icon leads to the setup picture.
Touching the icon leads to the picture described”Main/Bridge/ECR AHU setup picture” on page 16
The enthalpy symbols show the status as shown in 1.1.2 Common objects (symbols).
Touching the icon leads to the setup picture.
Error! No text of specified style in document. YORK Marine, Controls
Revision: 1.1 · Updated: 080326 Author: Morten Bech-Nielsen · Owner: Morten Bech-Nielsen
Project 660953: HVAC plant Page 13 of 36
File: h:\ac\660953-lindo nb 211-216\manuals\operator manual\operator manual.doc
Lindø shipyard NB211-216
2
3
Status Description
Fan off The AHU is switch off
Ready cooling The AHU is ready for cooling
Heating The heating function is activated
Cooling The supply air regulation function is activated
Sensor error Sensor error
Ventilation The AHU fan is only run
The Fan symbols show the status as shown in 1.1.2 Common objects (symbols).
The switch symbols show the status as shown in 1.1.2 Common objects (symbols)
Touching the icon leads to the picture described “Galley/Workshop AHU setup picture” on page 18
Status Description
Fan off The AHU is switch off
Ready cooling The AHU is ready for cooling
Heating The heating function is activated
Cooling The supply air regulation function is activated
Sensor error Sensor error
Ventilation The AHU fan is only run
The Fan symbols show the status as shown in 1.1.2 Common objects (symbols).
Touching the icon leads to the picture described”Main/Bridge/ECR AHU setup picture” on page 16
Status Description
Fan off The AHU is switch off
Ready cooling The AHU is ready for cooling
Heating The heating function is activated
Cooling The supply air regulation function is activated
Sensor error Sensor error
Ventilation The AHU fan is only run
The Fan symbols show the status as shown in 1.1.2 Common objects (symbols).
Touching the icon leads to the picture described “Galley/Workshop AHU setup picture” on page 18
Fig1.0 Fig1.1
1 1
2 2
9 9
3 3
8 8
4 4
7 7
5 5
6 6
Fig1.0 Actual regulation supply Set point with return compensation (Only reading values)
For more details about the set point see section “System description”
Fig 1.1 Regulation supply Set point with out return compensation (Only modify values)
For more details about the set point see section “System description”
The parameter for the preheat set point can be set. (Only main AHU)
Touching the icon leads to the picture described “Main/Bridge/ECR AHU compensation setup
picture” on page 19
Touching the icon leads to the picture”AHU heating setup picture” on page 21
Touching the icon leads to the picture described “AHU supply cooling setup picture” on page 20
Touching the icon leads to the picture described “AHU alarm setup picture” on page 22
Touching the icon leads to the picture described “AHU supply cooling setup picture” on page 20
Touching the icon leads to the picture described “AHU alarm setup picture” on page 22
The max and min limit for supply set point can be set.
For more details about the parameter see section “System description”
The parameter for return compensation on the supply set point can be set.
For more details about the parameter see section “System description”
The parameter for supply regulation of the expansion valve can be set.
For more details about the parameter see section 4 “System description”
The parameter for Preheat regulation of the motor valve can be set. (Only main AHU)
For more details about the parameter see section “System description”
The parameter for main heat regulation of the motor valve can be set.
For more details about the parameter see section “System description”
When push on the “OFF” icon, a stop command will be send to the exchanger starter.
When push on the “ON” icon, a start command will be send to the exchanger starter.
When push on the “AUTO” icon, the exchange will be started/stopped from the control.
The Fan symbols show the status as shown in 1.1.2 Common objects (symbols).
text description
STOPPED The exchanger is stopped
RUNNING The exchanger are running
READY The exchanger are ready for run
ALARM The exchanger in alarm
The high outdoor temperature limit for started the exchanger can be set.
The low outdoor temperature limit for started the exchanger can be set.
When push on the “OFF” icon, a stop command will be send to the humidity controller.
When push on the “ON” icon, a start command will be send to the humidity controller.
Touching the icon leads to the picture described “AHU humidity system setup picture” on page 24
The Pumps symbols show the status as shown in 1.1.2 Common objects (symbols).
The Valve symbols show the status as shown in 1.1.2 Common objects (symbols).
Touching the icon leads to the picture described, “Hot water system setup picture” on page 27
The parameter for hot water regulation of the motor valve can be set.
For more details about the parameter see section “System description”
Touching the icon leads to the picture described “Trend picture” on page 29
Touching will open the history trend picture, where date and time can be changed.
Shows the actual value, and the colour for the trends.
1 2 3
Touching the button will bring you to the “Matser PLC status picture” on page 39.
Touching the button will bring you to the “communication network picture” on page 31.
Press to see status of the Slave PLC and the analogue sensors setup.
Colour Description
Red The communication is offline (PLC in stop mode, master disconnected or cable broken)
Grey The communication is online
Error code
Normal condition: Value = 0.
Contact YORK in all other cases.
CPU
Normal condition is “running”.
Condition “stopped”:
To the left of the circular plug is placed a “Run / Stop” switch.
The switch must be in “Run” position.
Battery
Status for battery
Touching the button brings you to the picture described in “4-20mA scaling picture”,
1 2 3
3 ALARM LIST
Alarm text Description
AHU Main Enthalpy run error The motor has tripped the over current relay.
The relay must be manually reset inside the switchboard.
AHU Main humidity sensor Error Humidity sensor failing or missing signal.
Check sensor and wires.
AHU Main high humidity Alarm Humidity is higher than alarm limit.
AHU Main high return temp Alarm Return air temperature is higher than alarm limit.
AHU Main low return temp Alarm Return air temperature is lower than alarm limit.
AHU Main return temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU Main high supply temp Alarm Supply air temperature is higher than alarm limit.
AHU Main low supply temp Alarm Supply air temperature is lower than alarm limit.
AHU Main supply temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU Main KP61 low temp Alarm Temperature on heating coil is too cold.
Risk of severe freezing damage to the coil is imminent.
AHU Bridge humidity sensor Error Humidity sensor failing or missing signal.
Check sensor and wires.
AHU Bridge high return temp Alarm Return air temperature is higher than alarm limit.
AHU Bridge low return temp Alarm Return air temperature is lower than alarm limit.
AHU Bridge return temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU Bridge high supply temp Alarm Supply air temperature is higher than alarm limit.
AHU Bridge low supply temp Alarm Supply air temperature is lower than alarm limit.
AHU Bridge supply temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU Bridge KP61 low temp Alarm Temperature on heating coil is too cold.
Risk of severe freezing damage to the coil is imminent.
AHU Bridge high humidity Alarm Humidity is higher than alarm limit.
AHU Galley high supply temp Alarm Supply air temperature is higher than alarm limit.
AHU Galley low supply temp Alarm Supply air temperature is lower than alarm limit.
AHU Galley supply temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU Galley KP61 low temp Alarm Temperature on heating coil is too cold.
Risk of severe freezing damage to the coil is imminent.
AHU Workshop high supply temp Alarm Supply air temperature is higher than alarm limit.
AHU Workshop low supply temp Alarm Supply air temperature is lower than alarm limit.
AHU Workshop supply temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU ECR1 high supply temp Alarm Supply air temperature is higher than alarm limit.
AHU ECR1 low supply temp Alarm Supply air temperature is lower than alarm limit.
AHU ECR1 supply temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU ECR2 high supply temp Alarm Supply air temperature is higher than alarm limit.
AHU ECR2 low supply temp Alarm Supply air temperature is lower than alarm limit.
AHU ECR2 supply temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU ECR12 high return temp Alarm Return air temperature is higher than alarm limit.
AHU ECR12 low return temp Alarm Return air temperature is lower than alarm limit.
AHU ECR12 return temp sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.