SUMMARY REPORT OF OUTSTANDING ISSUES

DRUPS SYSTEMS – LSP

Customer Name: LSP Viet Nam RR Reference: K19008


Overview : Service Report Reported by: Dung Tran
PO No. NA Reviewed by: Van Hoang
Customer Contact: Dau Hoang Van <dauhv@lsp.com> Report date: 23 May 2023
Equipment Details: KS5-560-BI-2250KVA 11,5KV 50HZ ( 20 Drups )

- DPC summarizes issues that need to be handled urgently after implementation process maintenance B and
monitoring progress.

 Implementation time : From 10/04/2023 to 29/05/2023.


 Workplace : Drups 6901 → Drups 6920 / LSP

- Outstanding issue :

1/ Enginee Battery .

1.1 / Technical data battery.

No Brand Model Specifications Dimensions Quantity for Quantity for Remark


01 Drups 20 Drups

1 VARTA VARTA 12V 105Ah 800A 330x172x240 18 unit 360 unit


ProMotive HD

1.2/ Battery test results at 20 Drups.

- The following parameters were measured and recorded by us during the maintenance B.

- The stats are relative for each Drups / 18 unit . you can see the details in the Service Report Blank template.

- Measurement Device : Fluke -BT521 & Fluke 62 Max

DRUPS Services Page 1 of 7


SUMMARY REPORT OF OUTSTANDING ISSUES
DRUPS SYSTEMS – LSP

- Measure result :

Value internal resistance > 3.5 mὨ at Specification. The battery temperature is within the allowable range

Value Voltage is within the allowed range

DRUPS Services Page 2 of 7


SUMMARY REPORT OF OUTSTANDING ISSUES
DRUPS SYSTEMS – LSP

No Machine Internal Specification Terminal Battery Temparature Remark


Resistance Project Voltage poles
Actually

1 DRUPS ≥ 4.2 mὨ ≤ 3.5 mὨ 13.27 V NOK 33.5 oC The internal resistance value exceeds the
6901/AC technical standard threshold → Recommend to
replace all ASAP

2 DRUPS ≥ 3.9 mὨ ≤ 3.5 mὨ 13.22 V OK 33.5 oC The internal resistance value exceeds the
6902/AD technical standard threshold → Recommend to
replace all ASAP

3 DRUPS ≥ 4.3 mὨ ≤ 3.5 mὨ 13.08 V OK 34.2 oC The internal resistance value exceeds the
6903/AE technical standard threshold → Recommend to
replace all ASAP

4 DRUPS ≥ 5.0 mὨ ≤ 3.5 mὨ 13.3 V OK 36.5 oC The internal resistance value exceeds the
6904/AF technical standard threshold → Recommend to
replace all ASAP

5 DRUPS ≥ 4.2 mὨ ≤ 3.5 mὨ 13.34 V OK 35.2 oC The internal resistance value exceeds the
6905/AG technical standard threshold → Recommend to
replace all ASAP

6 DRUPS ≥ 4.3 mὨ ≤ 3.5 mὨ 13.27 V OK 35.5 oC The internal resistance value exceeds the
6906/AH technical standard threshold → Recommend to
replace all ASAP

7 DRUPS ≥ 4.2 mὨ ≤ 3.5 mὨ 13.27 V NOK 33.5 oC The internal resistance value exceeds the
6907/AI technical standard threshold → Recommend to
replace all ASAP

8 DRUPS ≥ 4.8 mὨ ≤ 3.5 mὨ 13.38 V OK 37.4 oC The internal resistance value exceeds the
6908/AJ technical standard threshold → Recommend to
replace all ASAP

9 DRUPS ≥ 4.3 mὨ ≤ 3.5 mὨ 13.20 V NOK 36.6 oC The internal resistance value exceeds the
6909/AK → OL technical standard threshold → Recommend to
replace all ASAP

10 DRUPS ≥ 4.9 mὨ ≤ 3.5 mὨ 13.48 V OK 37.3 oC The internal resistance value exceeds the
6910/AL technical standard threshold → Recommend to
replace all ASAP

11 DRUPS ≥ 4.7 mὨ ≤ 3.5 mὨ 13.29 V OK 36.1oC The internal resistance value exceeds the
6911/AM technical standard threshold → Recommend to
replace all ASAP

DRUPS Services Page 3 of 7


SUMMARY REPORT OF OUTSTANDING ISSUES
DRUPS SYSTEMS – LSP
12 DRUPS ≥ 4.2 mὨ ≤ 3.5 mὨ 13.41 V OK 34.5 oC The internal resistance value exceeds the
6912/AN technical standard threshold → Recommend to
replace all ASAP

13 DRUPS ≥ 3.8 mὨ ≤ 3.5 mὨ 13.23 V OK 33.5 oC The internal resistance value exceeds the
6913/AO technical standard threshold → Recommend to
replace all ASAP

14 DRUPS ≥ 3.8 mὨ ≤ 3.5 mὨ 13.21 V OK 34.8 oC The internal resistance value exceeds the
6914/AP technical standard threshold → Recommend to
replace all ASAP

15 DRUPS ≥ 4.5 mὨ ≤ 3.5 mὨ 13.26 V OK 36.4 oC The internal resistance value exceeds the
6915/AQ technical standard threshold → Recommend to
replace all ASAP

16 DRUPS ≥ 4.1 mὨ ≤ 3.5 mὨ 13.41 V OK 37.5 oC The internal resistance value exceeds the
6916/AR technical standard threshold → Recommend to
replace all ASAP

17 DRUPS ≥ 4.0 mὨ ≤ 3.5 mὨ 13.37 V OK 35.5 oC The internal resistance value exceeds the
6917/AS technical standard threshold → Recommend to
replace all ASAP

18 DRUPS ≥ 4.3 mὨ ≤ 3.5 mὨ 13.27 V OK 35.3 oC The internal resistance value exceeds the
6918/AT technical standard threshold → Recommend to
replace all ASAP

19 DRUPS ≥ 4.1 mὨ ≤ 3.5 mὨ 13.31 V OK 34.7 oC The internal resistance value exceeds the
6919/AU technical standard threshold → Recommend to
replace all ASAP

20 DRUPS ≥ 4.2 mὨ ≤ 3.5 mὨ 13.37 V OK 34.5 oC The internal resistance value exceeds the
6920/AV technical standard threshold → Recommend to
replace all ASAP

Note : DPC recomment need to replace all Battery for 20 Drups , ensure stable system
operation

DRUPS Services Page 4 of 7


SUMMARY REPORT OF OUTSTANDING ISSUES
DRUPS SYSTEMS – LSP

2/ PLC Battery .

2.1 Technical data PLC battery.

No Brand Model Specifications Dimensions Quantity Quantity Remark


for 01 for 20
Drups Drups

1 Sonnenschein A512/40 G6* 12V 40Ah 1069A 210x175x175 02 unit 40 unit

2.2/ PLC Battery test results at 20 Drups.

No Machine Internal Specification Terminal Battery Remark


Resistance Project Voltage poles
Actually

Battery COP panel leaking water, oxidized


battery poles, have value internal resistance > 11
1 Drups 6901 → Drups 6920 ≥ 11 mὨ ≤ 3.5 mὨ 13.37 V NOK
mὨ → Need replace all ASAP.

Note : DPC recomment need to replace all PLC Battery for 20 Drups systems .

DRUPS Services Page 5 of 7


SUMMARY REPORT OF OUTSTANDING ISSUES
DRUPS SYSTEMS – LSP
3/ The air filter inlet.

- According to our observations , The condition of the air filter inlet is badly damaged, a lot of dust forms in
patches, the air filter is rotten and cannot be cleaned → seriously affect the inlet air flow,the temperature in the
container is high , so it needs to be replaced urgently.

Note : DPC recomment need to replace all air filter inlet for 20 Drups systems .
DRUPS Services Page 6 of 7
SUMMARY REPORT OF OUTSTANDING ISSUES
DRUPS SYSTEMS – LSP

4/ Coolant water for Engine.

- Currently, as check by us coolant water at Engine 20 Drups is level low .


- For detailed data, please refer to Service Report Blank template and Report mantenance B .
- DPC recomment need to add more coolant water for Engine _ 20 Drups systems

DRUPS Services Page 7 of 7