AP4807 / AP4007
4 in 1 Mifare Reader Installation sheet
GENERAL
Nedap Mifare interface module suitable for connecting 4 Nedap Mifare antenna’s thus controlling 4
doors. Capable of interfacing with most locks, turnstiles and speed gates on the market. Parameters
are remotely monitored.
4 relays using floating contacts for lock control (with status indication). 8 functionality selectable and
supervised digital inputs. So for each reader one relay and 2 inputs can be available.
The firmware in the AEpack combined with the behaviour components determines the functionality.
The AP4807 is an AP4007 with additional microprocessor board (so acts like AP8001 + AP4007)
AP4x07X is equal to AP4x07, but with optional RS232 serial port and suitable for XScale AEpu.

PCB LAYOUT and INDICATIONS


BE: BUS ERR (red) ST: STATUS (blue)
ON Bus error Slow blinking AEpack assigned to AEpu (operating)
Very fast blinking ALT mode active
AE: ADDR ERR(red)
Fast blinking Downloading or error during loading
ON No AEpu connection (AEpack passive)
1 short flash AEpack not coupled
Flashing 5 Hz No valid AEpack address (or already in use)
2 short flashes Firmware present but not active
Flashing 20 Hz AEpack address being modified
3 short flashes No firmware present
CE: CB ERR(red) PW: POWER (green) ADDRESS SWITCHES
ON AEpu not active ON Power present Turn for correct address
OFF AEpu operational, Status led gives correct state (99 for AP48xx)

AP4807X Processor board AEbus AEbus Termination


ON
AP4007 / AP4807 Tamper switch
BE
CH
CG
CL

PW
+
-

AE
CE ST
ID1 ID3

ID2 ID4
FR
Reset AEpu
to Factory RY1 RY4 RY3
RY2

RY1

RY4

RY3

settings RY2
Battery ALT
RST LINK Rx/Tx 100BT
GND
Tx

Rx

AEpu reset 1 3
button
RS2322 4
Network
LINK (green)
Service port Peripheral connections (4*) ALT mode button
ON Ethernet present port 100BT (yellow)
Rx/Tx (yellow) ON 100 Mbps RY1..4 (green) ID1..4 (green)
Blink Communication on Ethernet OFF 10 Mbps ON Output activated Flashing 0,5 Hz Card detected

PERIPHERAL CONNECTIONS (4*, each connector identical) Blanked connectors are not used
do not connect
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
+5V NC COM NO IN1 GND IN2 ANT GND UL GND NA GND

Power +5VDC Cable shield


Output to GND and UL GND NA
ANTENNA COIL

metal case
UL GREEN

Floating contact Free definable


NA RED

Relay output inputs

Remark: For each connector the numbering is increased


(for connector nr 3: IN5 and IN6 and RY3) RG58U
Antenna: RefleXS 130M

Date : January 17, 2007 Version: 2 Part.no.: 5268591


This information is furnished for guidance, and with no guarantee as to its accuracy or completeness; its publication conveys no licence under any patent or
other right, nor does the publisher assume liability for any consequence of its use; specifications and availability of goods mentioned in it are subject to change
without notice; it is not to be reproduced in any way, in whole or in part, without the written consent of the publisher.

© Nedap N.V., IDEAS P.O. Box 103 NL-7140 AC GROENLO The Netherlands Page 1 of 4
AP4807X / AP4007X
NC
Relay contacts are dry contacts. If supply voltage is needed, COM
NO + Door lock
make interconnections between Power Supply and relay Vlock

All inputs are supervised (software INx


R=4K7
GND -
selectable). See diagram for connections.

R= 4K7
Connect protection diode as near as
GND possible to electrical terminals of lock
Contact
5V GND
NA and UL led: UL – NA: 5V, R=220 included, LED cathode to GND.
R=220
UL/NA

CONNECTIONS
AP4xxx series are NOT hot-swappable, so changing or adding these AEpacks or connections may
only be done when Power is switched OFF.
AP4XXX connector
Cables outside housing: Use always shielded cables and connect shield to
top view
metal case.

POWER CONNECTIONS
AP4xxx can get the power from the AEbus (check maximum power) or from
separate Power Supply. Power for Lock must be connected external to Relay

CH

CG
CL
(see above).

-
+
rear view

NETWORK CONNECTION (AP48xx only)


Network is connected using the RJ-45 network connector. (No indication 10/100 Mbit)

SERVICE CONNECTOR (AP48xx only) AP48xx Function SUB-D


For configuration the serial port on 9 pin SUB-D connector 2 (Tx) Rx (Receive data)
is used. Configuration is done by using hyperterminal. See 5 (GND) GND
AEOS installation manual for more information. 3 (Rx) Tx (Transmit data)
7 (CTS) Clear to send (Output)
8 (RTS) Request to send (Input)
SYSTEM CONFIGURATIONS (how to connect AP4xxx
and AEpacks)
AP4xxx only AP4xxx with single AEpacks

Total bus length: max 1000m. (BitRate: 1) Total bus length: max 5m. (BitRate: 0)

AP4xxx with single AEpacks AX2002 Single AEpacks with AP4xxx

Total bus length: max 300m. (BitRate: 0) Total bus length: max 5m. (BitRate: 0)
Remark: If AP4xxx is only connected and total cable length >300 m, then BitRate of AP48xx must
be set to 1.(AEmon: View – Hardware – AEbusConfiguration - BitRate).
If single AEpacks are connected then BitRate must be 0. (Default setting is 0.)

AEBUS CONNECTIONS
AEbus connections must always be to the identical point of the other AEpack or AX2002. The
AP4xxx has a single AEbus connector, so two cables must be mounted on one connector. (For
detailed connections see next page.)

© Nedap N.V. AP4807X / AP4007X Installation sheet Page 2 of 4


AP4807X / AP4007X

1 AP4xxx to AP4xxx 2 AP4xxx to AEpacks 3 AP4xxx to AX2002


AEbus connectors AEbus connectors AEbus connectors
rear view rear view rear view

CGND
GND
VIN
CG
CH

CH

CG

CH

CG
CL

CL

CL
CG
CH

CH
CH

CG
CL

CL
CL
-
+

-
+

+
-
+

-~
+~
AP4xxx n AP4xxx AP4xxx n AEpack n+1 AP4xxx n AX2002
+1
Remark: If Power is locally supplied on the next AP4xxx connect only CH, CL and CG (CGND).

Going outside AEpacks housing: shielded cable must be used; CH and CL must be one twisted pair.
From other pair one conductor is used for CGND. Shield must be connected to metal housing, (to
which also the metal mounting rail of the AEpacks is connected). (CH Æ CH and CL Æ CL)

Attention: The communication line must be terminated correctly, see chapter Termination Switch.

TERMINATION SWITCH AEbus connector


top view AEbus termination
The AEbus must be terminated correctly at the first and the last switch
AEpack. For this purpose the switch beside the AEbus connector is
OFF ON
used. See text at switch for correct ON and OFF position. See figure
below, also for combination with AX2002.
Resistor ON for Resistor OFF for Resistor ON for
first and last Cable shield to earth all between first and last
on both sides
AP4xxx first AP4xxx between AX2002 AX2002 last
ON OFF OFF
OFF ON

AEbus (extender) connectors


CH

CG

CH

CG
CL

CH

CG
CL

CL
-
+

rear view
-
+

-
+

CONNECTIONS TO ANTENNA’S (see specifications)


Only use Nedap antenna’s RefleXS 130M. To connect antenna use coax RG58U for antenna signal
and separate cable for LED’s

RS232 PORT: Depending of the used firmware the additional Function from AP4x03
RS232 port be used. 1 Tx Transmit data
2 GND GND
3 Rx Receive data
ADDRESS SETTING
AP48xx: address must be 99 (AP48xx only).
The Address switch gives address of AEpack. Left: units of 10, right: units of 1.
BUS ERR and ADDR ERR LED’s indicates address status. Address valid: both LED’s must be off.
New installation: select free address; Replacing AEpack: use the same address.
The address is used for configuring the AEpack (software settings) so write it down.
Address 00 is used to set the AEpack off-line (isolation of AEpack).

© Nedap N.V. AP4807X / AP4007X Installation sheet Page 3 of 4


AP4807X / AP4007X

BATTERY (AP48xx only)


Battery must be enabled by removing plastic isolator that is put between its contacts. (Battery is used
for real time clock on AP48xx)

TAMPER SWITCH
Tamper switch can be read by the software and thus generating an alarm if enclosure is opened.

AEPACK LOCAL TEST (ALT MODE)


ALT mode allows a simple test of the basic functions of AEpack. Switching on/off ALT mode is
logged on server!
Start ALT mode: Press ALT button more than 3 seconds. Status LED blinks fast.
Back to normal operation: No action in ALT mode during 15 minutes or ALT switch pressing again
for 3 seconds. After returning to operation mode the situation from before starting the ALT mode is
restored.
ALT mode for AP4x07: Short activating button will cause a new test situation, tests will loop around:
1 Reads card: ID led blinks, UL led acts like ID led, activates relay 1
2 Relay 1 ON NA and UL led ON, UL led flashes during reading card
3 Relay 1 OFF
Steps 1,2,3 are repeated for all four outputs.

FIRMWARE
Pay attention that the firmware loaded in AEpack and AEpu determines functionality and protocols.

SPECIFICATIONS AP4807X (Product nr. 9854800) AP4007X (Product nr. 9854770)


Dimensions: 230 x 345 x 70 mm Weight: ± 900 gr
Power input: 10 – 35VDC AP4807: Min. AEpack power consumption: 700mA@24VDC / 1000mA@12VDC
AP4007: Min. AEpack power consumption: 600mA@24VDC / 750mA@12VDC
Environment: Temperature: Operating: 0 – 55 °C, Storage: -30 – 65 °C Relative humidity: 10 – 93% non condensing
Lock supply: External Additional supply: +5VDC ±10% max 100mA (total)
Inputs: 8: Intended for dry contact or open collector, optional supervised (software selectable)
Outputs: 4: Dry contact (normally open, common, normally closed).
Contact ratings: (Suitable for switching inductive loads, clean relay contacts)
Switching voltage: 24VAC, 48VDC
Continuous current and switching current: 6A (AC and DC)
Contact lifetime: min 500.000 times at given ratings
Indications: 4* UL and NA led for antenna: max 20 mA
Communication: AP48xx Ethernet: UTP 100/10 Mbps (auto detection)
Service port RS232 (Rx, Tx, GND, RTS, CTS)
AEbus: Isolated, Bitrate: high/low
1* RS232 (Tx, Rx, GND) for optional use
Battery: CR2032 (lifetime 2 years if no power present)
Antennas: 13,56 MHz/50 Ω Nedap proximity antenna’s only for Mifare (e.g RefleXS130M)
UL and NA led for antenna: max 20 mA, (5VDC; R=220E)
Detection distance: RefleXS130M – Standard Mifare: max 40 mm, Combi Mifare: 20 mm

CABLE SPECIFICATIONS
Inputs: 2 x 0,25mm², max cable length: 100 meter, cable capacity <= 100pF/meter
Antenna: Antenna signals to RefleXS130M: RG58U, max cable length: 30 meter
Led signals: 3 x 0,25mm² shielded, max cable length: 30 meter
Communication AEbus: only AP4xxx (including power): 3 x 2 x 0,5mm² shielded, max cable length: 1000 meter
only AP4xxx (CL,CH,CGND): 2 x 2 x 0,5mm² shielded, max cable length: 1000 meter
AP4xxx + AEpacks: 5 x 0,5mm² shielded, max cable length 5 meter
AP4xxx + AEpacks + AX2002: 2 x 2 x 0,5mm² shielded, max cable length 300 meter
Cable shield to metal case
Ethernet: UTP CAT 5

MORE INFORMATION: For more detailed information contact your local Nedap supplier or check the internet site.

© Nedap N.V. AP4807X / AP4007X Installation sheet Page 4 of 4