You are on page 1of 1

Technology Department

132 kV, XLPE POWER CABLE

1X1200/261 mm2 Cable Cross section Drawing


Cable ID: 35010212

Reference standard: IEC 60840

1. Conductor: Copper, Milliken (Segmental) Conductor (Fully watertight).


Approximate diameter: 43.4 mm
2. Conductor Moisture Impervious layer: Semi-Conductive Water Swellable Tape.
Approximate thickness: 0.36 mm / Approximate diameter: 46.04 mm
3. Conductor Screen: Extruded Semi-Conducting Thermosetting Compound.
Nominal thickness: 1.5 mm / Approximate diameter: 49.04 mm
4. Insulation: Extruded Cross-linked Polyethylene (XLPE).
Nominal thickness: 18 mm / Approximate diameter: 85.04 mm
5. Insulation Screen: Extruded Semi-Conducting Thermosetting Compound
Nominal thickness: 1.5 mm / Approximate diameter: 88.04 mm
6. Longitudinal Moisture Barrier: Semi-Conductive Water Swellable Tape
Approximate thickness: 0.5 mm / Approximate diameter: 89.2 mm
7. Metallic Screen: Copper Wires + Copper Tape (open Helix)
Nominal cross-section: 261 mm2 / Approximate diameter: 93.6 mm
8. Longitudinal Moisture Barrier: Non-Conductive Water Swellable Tape
Approximate thickness: 0.25 mm / Approximate diameter: 94.1 mm
9. Radial Moisture Barrier: Laminated Aluminium Tape
Nominal thickness: 0.3 mm / Approximate diameter: 95.0 mm
10. Outer Sheath: Extruded HDPE (Graphite Coating)
Nominal thickness: 4.5 mm / Approximate Overall diameter: 104.2 mm

You might also like