Professional Documents
Culture Documents
net/publication/252044181
CITATIONS READS
10 940
7 authors, including:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Sonja Monica Berlijn on 27 May 2014.
I. INTRODUCTION
Fig. 3 Three insulators that are monitored to be able to check the ice accretion
of insulators in real life, and to check swing angle calculations.
Fig. 4 A typical I-string used in 300 kV lines. In 300 kV lines the number of
insulators is typically 14-15, but can be more in locations with heavy ice Fig. 7 Live line working in 300 kV lines. On the right hand side of the V-
loads. chain the 4 new inserted glass insulators can clearly be seen.
3
IV. LOAD CASES The requirement for the extreme wind condition that only
In [1] generally three load cases are considered: occurs for 2-5 seconds per 50 year, is of course that it can
1) Still wind conditions withstand AC overvoltages given by (3).
2) 3 year return time wind conditions The requirements (1), (2) and (3) only consider external
3) 50 year return time wind conditions clearances. Internal clearances might be decreased since they
For each of these conditions different air clearances are only have an effect on the system outages. Therefore internal
required, see next section for more details. clearances can be reduced.
The most frequently occurring load case will be the one in As can be seen from (1) the insulator length choosen will
between the three year return time and the still wind load case. have a direct effect on the required/needed air clearances. A
This will occur for 99,95% of the time. Wind over the three 15 cm shorter insulator, will result in a 15 cm shorter required
year return time will occur only for 0,05% of the time (around clearance and therefore 30 cm total distance will be gained.
4 hours per year). The 50 year return time represents extreme For new lines this is within the building uncertainty, but when
wind conditions (2-5 seconds per 50 years). voltage upgrading this will be the difference between feasible
The three load conditions and their distance requirements or not feasible.
are visualized in Fig. 8. For these three wind conditions the 1 K g _ ff _ is
swing angle of the lines/insulators will be different, as can be Del = ⋅ d is (1)
seen in the same figure. K a K g _ ff
1 ⎛⎜ 1080⋅K a ⋅K z _ sf ⋅K g _ sf ⎞
K cs ⋅U e 2% _ sf
Del = ⋅ e − 1⎟ (2)
0,46 ⎜ ⎟
⎝ ⎠
1 ⎛⎜ 750⋅ 3⋅K a ⋅K z _ pf ⋅K g _ pf ⎞
⋅U s
D pp = ⋅ e − 1⎟ (3)
0,55 ⎜ ⎟
⎝ ⎠
Fig. 12 Failure contributions of the different failure types and the rate and
successful auto reclosing rate, with two surge arresters