Professional Documents
Culture Documents
net/publication/241191230
CITATIONS READS
16 6,327
5 authors, including:
Some of the authors of this publication are also working on these related projects:
Modeling and Analysis of Active Distribution Networks and Microgrids View project
All content following this page was uploaded by Grigoris Papagiannis on 05 November 2015.
978-1-4244-8417-1/11/$26.00 ©2011
2
• Arrangement d, where cable sheaths are grounded at grounded at both ends the induced currents become relatively
intermediate points along the cable length. high, reaching up to 90 A for grounding resistance equal to 1
In all cases the use of different grounding resistances has Ohm, thus causing increased cable losses.
been also examined. All the above cable arrangements are The application of cross-bonding significantly reduces the
shown in Fig. 5, for one of the three 3-phase cable systems. induced sheath voltage to a maximum of 120 V for 2
For each configuration and examined case the induced cross-bondings and 60 V for 5 cross-bondings, respectively, as
voltages and currents at the cable sheaths are calculated. shown in Figs 8 and 9. Voltages at the cable terminals are also
small, below 50 V in accordance to [7]. The respective
induced sheath currents are minimized and are in all cases
below 10 A, thus reducing the respective cable losses.
Fig. 6. Induced voltage at the cable sheaths. Sheaths are grounded only at one
end (PPC side) using different grounding resistances.
Fig. 7. Induced voltage at cable sheaths. Sheaths are grounded at both ends
using different grounding resistances.
Figs. 6 – 9 illustrate the voltage distribution at the cable Fig. 8. Induced voltage at sheaths. Cable sheaths are grounded at both ends
sheaths for each of the examined arrangements. It is shown, using different grounding resistances and sheaths are cross-bonded at two
that in the cases of cable sheath grounding either at one or at points (every 6120 m).
both ends, without cross-bonding, the induced voltages at the
cable sheaths can be significant, especially at the cable In cases where cross-bonding is used, the value of the
terminals, depending on the value of the grounding grounding resistance has minor effects on the induced sheath
resistances. Typical values for grounding resistances at 1 Ohm voltages, compared to the non cross-bonded case, especially at
or 2 Ohm have been examined, since such low grounding the cable terminals. These are the points with the higher risk
resistances are common in substations. For higher values of for human safety, since they are accessible by the technical
grounding resistances the voltage at the cable ends can reach personnel.
very high values. Furthermore, when cable sheaths are
4
Fig. 9. Induced voltage at sheaths. Cable sheaths are grounded at both ends
using different grounding resistances and sheaths are cross-bonded at five
points (every 3060 m). Fig. 11. Induced voltage at the sheaths when the cable sheaths are grounded
at both ends with 2 Ohm grounding resistances, for cable systems consisting
of 3, 6 and 9 cables.
Fig. 10 illustrates the voltage profiles at the cable sheaths,
when sheaths are grounded at both ends with a 2 Ohm
grounding resistance and also at 12 equidistant points along
IV. SHORT CIRCUIT CALCULATIONS
the cable length (every 1530 m), using different grounding
resistances. It is shown that unless a very low grounding The cable model is also used in order to calculate the cable
resistance, for example 2 Ohm or less, is achieved at all sheath voltages during 3-phase and single phase short-circuits
intermediate grounding points the sheath voltage is high. (SC). As the worst case scenario, a 3-phase or single phase to
However, to attain such values for the grounding resistances ground fault in the PPC or the wind park busbars has been
along the cable routing is not at all easy. Furthermore, this considered. The SC currents in the cable cores have been
arrangement also causes higher sheath currents in respect to simulated using proper current sources equal to the expected
the cross-bonding case, due to the high number of internal SC current, as calculated according to the IEC 60909 [13]. A
loops formed by the numerous grounding points. The sheath 3-phase SC at the grid side is simulated using a current source
current has been calculated equal to 35 A for the case of representing the total fault current at the wind farm busbar,
2 Ohm grounding resistances. connected at the wind farm side of the cable and all phases
short circuited at the grid side cable end. For the simulation of
a single-phase short circuit, a current source is connected at
the faulted cable phase. In this case, the other two phases are
assumed to be open-circuited at both ends. The simulation
model used is illustrated in Fig. 12.
Fig. 10. Induced voltage at sheaths. Cable sheaths are grounded at both ends
using grounding resistances equal to 2 Ohm and at 12 points along the cable
with varying grounding resistances.
Fig. 15. Induced voltage at sheaths for a 3-phase short circuit when sheath
cross-bonding and SVLs are used.