Professional Documents
Culture Documents
T1-L1
400
Current, A(rms)
Grid T1-L2
T1-L3
300 T2-L1
20 kV T2-L2
T2-L3
200
1600 kVA 240A
1600 kVA
u =6% 468A
u =6% k 100
k
15:30
16:50
18:10
19:30
20:50
22:10
23:30
0:50
2:10
3:30
4:50
6:10
7:30
8:50
10:10
11:30
12:50
14:10
Neutral conductor
2 Hour of day from 30/01/2004-31/01/2004
Five J1VV-U 300mm made up of
cables per phase three J1VV-U 300mm2
15 cables in total cables
Fig. 3. Measured currents of the 1st set of cables
Fig. 4. Measured currents of the 2nd set of cables
12345 12345
800
Circuit Breaker
2500A 700
Main Busbars 0.4 kV PE
L1,L2,L3 600
N T1-L1
Current, A(rms)
Ground T1-L2
Fig. 1. Substasion sinlge-line diagramm 500
T1-L3
100
0
14:50
16:10
17:30
18:50
20:10
21:30
22:50
0:10
1:30
2:50
4:10
5:30
6:50
8:10
9:30
10:50
12:10
13:30
Hour of day from 30/01/2004-31/01/2004
450
400
350 T1-L1
Current, A(rms)
T1-L2
300
T1-L3
250 T2-L1
T2-L2
200
T2-L3
150 240A
100 468A
Fig. 2. Cables laid out in open trays 50
0
11:10
12:30
13:50
15:10
16:30
17:50
19:10
20:30
21:50
23:10
0:30
1:50
3:10
4:30
5:50
7:10
8:30
9:50
T1-L2
each cable would carry in case of symmetry, assuming that T1-L3
300 T2-L1
the total phase current is 1200 A. The dashed line is the T2-L2
T2-L3
permitted cable ampacity. The ampacity-according to DIN 200
240A
VDE 0298 [1]- is 468 A for J1VV-U 300 mm2 cables, 100
468A
It is evident from Figs. 3-7 that there is large asymmetry Hour of day from 03/02/2004-04/02/2004
in the distribution of current. This asymmetry causes some Fig. 6. Measured currents of the 4th set
simulation results. Obviously, the effective inductance of
Fig. 7. Measured currents of the 5th set of cables
these cables is smaller than by the rest of them.
600
500
B. Other Cable Arrangements
T1-L1 After the simulation of the existing cable arrangement
400
illustrated in Fig 8, two more arrangements were
Current, A(rms)
T1-L2
T1-L3
300 T2-L1 simulated using the same simulation model at EMTP. The
T2-L2
T2-L3 two cable arrangements are illustrated in Fig 10.
200
240A
468A
100
0
11:50
13:10
14:30
15:50
17:10
18:30
19:50
21:10
22:30
23:50
1:10
2:30
3:50
5:10
6:30
7:50
9:10
10:30
Hour of day from 04/02/2004-05/02/2004
IV. SIMULATION
The first cable arrangement simulated was the one used at 200
the substation and is shown in Figure 8.
100
0
Cable 1 Cable 2 Cable 3 Cable 4 Cable 5 Cable 1 Cable 2 Cable 3 Cable 4 Cable 5 Cable 1 Cable 2 Cable 3 Cable 4 Cable 5
Fig. 8. Real-Case cables’ arrangement Fig. 11. All three simulation results (Real Case and two
new arrangements)
The load at the busbars was simulated as a simple R-L
branch in such a way that the total current per phase is It is evident, from the results illustrated in Fig 11 that
equal to the measured one. The simulation results the current unbalance is minimized when either of the two
compared with the measurements are shown in Fig 9. new arrangements is applied. Although the cables are not
transposed the current distribution is almost symmetrical
600
Fig. 9: Simulation and Measurement Results. in these cases. Furthermore the current distribution is
Measurement almost the same when either one of the two new
Simulation
500 arrangements is applied. Cable arrangements No1 or No2
400
have a significant advantage over cable transposition: they
are much simpler to implement and can be done also in
300 retrofit.
200
V. PROBLEMS ANALYSIS
100
A. Over-temperature
0
Cable 1 Cable 2 Cable 3 Cable 4 Cable 5 Cable 1 Cable 2 Cable 3 Cable 4 Cable 5 Cable 1 Cable 2 Cable 3 Cable 4 Cable 5 Overloading leads to over-temperature. The temperature
Phase A Phase B Phase C
rise of a cable relative to the maximum temperature rise is
given by
Fig 9. Measurement and Simulation results
∆ϑ I2 (1)
= 2
It appears from Fig. 9 that the simulation results are ∆ϑmax I n
relatively accurate when compared to the measurements. where I, is the rms value of current the cable is loaded
Another conclusion deriving from Fig 9 is the fact that the with, and In is the cable’s rated current (in this case
current unbalance seems to follow a general pattern. In=468A).
Neighboring cables that belong to different phases (such Using (1) the relative temperature increase of the seven
as cables 5, 6, 7, 10, 11 from Fig. 8) are overloaded. This overloaded cables, is in the range of 18% - 120%. For
pattern appears both at the measurement and at the PVC-insulated cables the maximum continuous
temperature is 70°C. Assuming an ambient temperature of 15028
30°C, the maximum temperature rise is ∆θmax=40 °C. log e t = − 31.6 (4)
T
Therefore, in the case presented here, we have ∆θ, 47°C where, t, is the life (in hours) of the cable and
to 88 °C, or 7°C to 48 °C above the maximum permissible T=273+ °C, is the core temperature
temperature. For a cable operating at 70°C, the above formula yields,
B. Additional Losses 23 years.
The current asymmetry leads to additional thermal In our case, the age of the overloaded cables ranges
losses when compared to the losses generated from a from 9.5 years (77°C core temperature) to less than 2
symmetrical current distribution. These additional losses months (118°C core temperature).
are due to the fact that the currents loading the single-core Indeed, two of the 15 cables were found to have severe
cables are larger than they would be if the distribution was deterioration in their insulation and were replaced.
symmetrical.
The thermal losses for the fifteen cables examined in VI. CONCLUSIONS
this paper were calculated for two representative Measurements at an industrial substation, have shown
scenarios. Firstly, for the measured asymmetrical current large current asymmetries among parallel connected
distribution and secondly for the new cable arrangement cables on the low voltage side of transformers. Some of
shown in Fig 10a. The losses were calculated according to the cables are shown to be overloaded, while the
15 15 employed overload protection devices do not detect it.
P = ∑ I i2 R = R ∑ I i2 (2) Overloading leads to additional losses and premature
i =1 i =1 ageing.
where Ii, is the rms value of current the cable i is loaded Simulation by EMTP reveals that there are simple and
with, and R is the cable’s resistance (in this case R=0.5836 practical ways for cable layout, so that the multiple
x 10-4 Ohm/m and is assumed equal for each cable parallel cables are evenly loaded. These cable
although it will be larger in the overloaded cables). arrangements can be easily implemented even in retrofit,
When the current is distributed symmetrically among while cable transposition cannot.
the five cables per each phase, the losses can be calculated
using the following simplified expression of (2) REFERENCES
Ia Ib Ic [1] DIN VDE 0298-4 “Verwendung von Kabeln und
P = 5( ) R + 5(
2
) R + 5(
2
) R=
2
5 5 5 (3) isolierten Leitungen für Starkstromanlagen. Teil 4:
= ( R )( I a2 + I b2 + I c2 ) Empfohlene Werte für die Strombelastbarkeit von Kabeln
5 und Leitungen für feste Verlegung in und an Gebäuden
The thermal losses calculations are und von flexiblen Leitungen“
[2] IEC 943: Guide for the specification of permissible
TABLE 1: THERMAL LOSSES CALCULATIONS.
temperature and temperature rise for parts of electrical
P Losses equipment, on particular for terminals
W/m W / 30m
Symmetrical Current (Theoretical) 46,08 1382,5 Kostas Gouramanis (M’ 2002) was born in Athens, Greece,
Real Case 66,49 1994,8 on September 22, 1979. He received his diploma in Electrical
Engineering from the Department of Electrical and Computer
New Arrangement (Fig 10a) 47,36 1420,7 Engineering at the Aristotle University of Thessaloniki, Greece
in 2003. Since 2003 he is a Ph.D. student at the same University.
The thermal losses calculations for the symmetrical His research interests are in the fields of power electronics,
current correspond to a theoretical case were the current power system harmonics and power quality.
distribution is completely symmetrical. As illustrated in Mr. Gouramanis is a member of the Society of Professional
Table 1 the thermal losses with the asymmetrical current Engineers of Greece.
distribution (real case) are about 50% bigger then the
Charis Demoulias (M’1995) was born in Katerini, Greece, on
thermal losses in the symmetrical case. On the other hand,
July 23, 1961. He received his Diploma in Electrical Engineering
the losses for the cable arrangement shown in Fig 10a are from the Aristotle University of Thessaloniki, Thessaloniki,
almost the same as the ones corresponding to the Greece, in 1984 and his Ph.D., degree from the same university
symmetrical distribution. in 1991.
He worked as a consultant in the areas of industrial electrical
C. Cable Ageing
installations, electrical energy saving, and renewable energy
Probably the most important effect of the high current sources. He is currently lecturer with the Electrical Machines
asymmetries analyzed in this paper is the rapid ageing of Laboratory, Department of Electrical and Computer Engineering
the cables due to the deterioration of their insulation. This in the Aristotle University of Thessaloniki. His research interests
deterioration occurs because of the over-temperature are in the fields of power electronics, harmonics, electric motion
mentioned earlier. systems and renewable energy sources.
For PVC insulated cables, the equation for ageing [2], is