Professional Documents
Culture Documents
Model CVT
User Manual
Version: V1.2
i
1. DECLARATION
Without prior written authorization from Cavio any information, diagrams and
drawings contained in this manual cannot be copied for manufacture and/or sales by
any company and/or individual.
i
TABLE OF CONTENTS
1. DECLARATION ........................................................................................... i
1.1 Scope of the Manual ............................................................................ i
2.SAFETY PRECAUTION ................................................................................1
2.1 Magnetic Field .....................................................................................1
2.2 Grounding ........................................................................................... 1
2.3 Flammable Gas ................................................................................... 1
2.4 General Operation ...............................................................................1
2.5 Service ................................................................................................ 1
2.6 General Maintenance .......................................................................... 1
2.7 Safety Marking ....................................................................................1
3. INTRODUCTION ....................................................................................... 3
3.1 Product Overview .............................................................................3
3.2 Outline Diagram ..................................................................................4
3.2.1 380Vac/50 or 60Hz system outline ...............................................4
3.2.2 208Vac/50 or 60Hz system outline ...............................................5
3.3 Product Model Number .................................................................. 6
4. INSTALLATION INSTRUCTION ...........................................................8
4.1 Preparation ...................................................................................... 8
4.1.1 Site Location ................................................................................. 8
4.1.2 Tools Required .............................................................................. 9
4.1.3 Cable Selection ..............................................................................9
4.2 Unpacking Inspection .................................................................... 10
4.2.1 Product Unpacking ......................................................................10
4.2.2 Check for damage ....................................................................... 10
4.3 System Installation ...........................................................................11
4.3.1 Single Phase Inverter System ..................................................... 11
4.4 Module Installation ...........................................................................13
4.4.1 Controller Module and Static Switch Module Installation .......... 13
4.4.2 Inverter Module Installation .......................................................14
4.4.3 Backplane ....................................................................................15
5. OPERATION INSTRUCTIONS ................................................................16
5.1 System Check ................................................................................. 17
5.1.1 Controller and Static Switch Check .............................................17
5.1.2 Inverter module quantity configuration ..................................... 18
5.1.3 Inverter Check ............................................................................ 18
5.1.4 System transfer test ....................................................................19
5.1.5 System Check with Dummy Load (if available) .......................... 19
5.2 System Start-Up .................................................................................20
5.3 Parameter Setting ..............................................................................20
5.4 UIB Test ............................................................................................... 31
ii
5.5 Communication Test ............................................................................ 32
5.5.1. Ethernet outline ......................................................................... 32
5.5.2. Website setting .......................................................................... 32
5.5.3. Web Service ............................................................................... 33
5.5.4. SNMP Application .......................................................................34
5.5.5. RS232 / RS485 ...........................................................................35
5.5.6. USB .............................................................................................35
5.6 System Operation .................................................................................37
5.7 Maintenance Switch Instructions ........................................................ 38
5.7.1 Replacement Controller and Static Switch process .................... 38
5.7.2 The use of maintenance switch ...................................................38
5.8 System Shut Down ............................................................................... 39
6. DEFAULT VALUE ..................................................................................... 39
7. REPLACEMENT and MAINTENANCE ..................................................... 40
7.1 Inverter Module Replacement .......................................................... 40
7.2 Controller Replacement .................................................................... 41
7.3 Static Switch Replacement ............................................................... 41
7.4 General Maintenance ........................................................................ 41
7.4.1 Daily Maintenance .......................................................................41
7.4.2 Battery Maintenance ...................................................................41
8. TROUBLESHOOTING ...............................................................................42
9.TECHNICAL DATA .................................................................................... 43
Appendix 1 CVT system Diagram ........................................................... 46
Appendix 2 CVT System Test sheet ........................................................ 47
iii
2.SAFETY PRECAUTION
The safety instructions described in this chapter are applicable to operation and
maintenance personnel. The instructions may not include some special warnings that
may be mentioned in related chapters. This equipment functions with high internal
voltages which may cause personal injury and/or equipment damage.
We do not accept any responsibility for any misuse in regards to design,
manufacture and operation and cannot be held liable for indirect or consequential
damages.
2.2 Grounding
The neutral and ground cables must be securely terminated to earth to ensure
correct equipment operation.
If the neutral and ground cables are not correctly terminated then faulty
equipment function and possible failure will result.
We take no responsibility for failures due to incorrect termination of neutral and
ground cables.
2.5 Service
If it is necessary to remove the external covers for service or component
replacement, ensure that all power sources are off and discharge procedures are
followed correctly, note that discharge may take several minutes.
1
Safety Marking Explanation
Safety Indication
Electric Shock
Danger
Warning
Caution
Ignoring any of the above safety instrucions may result in personal injury and/or
equipment damage
2
3. INTRODUCTION
AC Input
AC Input PDU
3
3.2 Outline Diagram
4
CVT153K-48/380-2M CVT189K-48/380-2M
From 9 to 153kVA From 9 to 189kVA
5
CVT36K-48/208-2M CVT72K-48/208-2M CVT126K-48/208-2M
From 9kVA to 36kVA From 9 to 72kVA From 9 to 126kVA
Figure 3-3 208Vac system outline
6
1 x 2m rack, 1 x static switch,
36kVA CVT36K-A/B
1 x controller and max 12 x inverter
208Vac
1 x 2m rack, 1 x static switch,
63kVA CVT63K-A/B
1 x controller and max 21 x inverter
Examples: CVT63K-48/380
System rating is three phase 63kVA with battery voltage of 48Vdc, output voltage of
380Vac(phase to phase) and frequency of 50 or 60Hz.
Caution:
System frequency: 50 or 60Hz, the system can be self-adaptive mains frequency.
Model Remark
CVC01 Dimension: 482.6W× 150D ×88Hmm Weight: 2.3kg
7
200A×3 CST63K-48/208 Dimension: 482.6W×340D ×266Hmm Weight:16kg
Caution:
Definition;
A: DC input voltage: 48, 110 or 220Vdc;
B: AC output voltage: 125Vac (suitable for 110, 115, 120 and 127Vac) or
220Vac (suitable for 208, 220, 230 and 240Vac).
Example: CPI3K-48/220
The inverter is single phase 3kVA with battery voltage of 48Vdc and output
voltage of 220Vac, suits for 50 and 60Hz.
Ensure that the product complies with the specific power requirements applicable
to your country.
4. INSTALLATION INSTRUCTION
This chapter outlines the tools required, cable selection, unpacking inspection and
system installation essential for correct system operation.
4.1 Preparation
As near as practicable to the power sources and loads for ease of cabling
In a clean and dust free environment
At altitude of not more than 1000m
Preferably at a temperature of 20C. Note that the maximum system operating
environment is between -5 to 50C with relative humidity not more than 90%.
Away from corrosive, explosive and/or destructive gas and conductive dust
Away from any heat source
8
In a vibration free location and with a vertical tilt of not more than 5%
Warning
A controlled temperature environment and clear airflow are very important for
system operation particularly during any overload conditions.
In the case of copper core cable we recommend a current density of 5A/ mm2
for AC and 2.5A/ mm2 for DC cable.
The maximum cable thickness required is relative to cable length especially
with high DC currents. If the inverter is located far from the DC power the
cable thickness must be increased. A maximum voltage drop from DC source
to system input of not more that 1Vdc is recommended.
Maximum ambient temperature must also be taken into consideration. If the
ambient temperature is high then the cable size must be increased
9
Max. DC
Min. DC cable Max. AC output Min. AC
Model input
(mm ) 2
current (A) cable(mm2)
current(A)
Caution
If the product needs to be returned for service, it should be returned in its original
packaging. If the original packaging is unavailable or severly damaged then make sure
the product is packed safely and correctly to prevent shipping damage. We are not
responsible for any damage caused by the improper packing of a returned product.
10
4.3 System Installation
AC Input II
Battery
Prior to system installation, check that the installation site is suitable for size,
space and weight and then follow the installation procedures.
2. Fix the rack via the mounting points with expansion bolts M10 × 30 shown in
Figure 4-3;
11
Figure 4-3 mounting points Figure 4-4 open front door
3.Ensure that both the DC and AC inputs are disconnected. Open front door as
shown in Figure 4-4 (the front door key is put in the back of front door). Ensure that all
switches are in the “Off” position, assistant switch in “NORMAL” position and transfer
switch in “Normal Operation” position. AC and DC PDUs are shown in Figure 4-5.
5.Connect AC output cable as required, as shown in Figure 4-6 and Table 4-1.
In single phase system, if it is low load, connect L to “Output L Branches”, N to “N” and
Ground to “PE”, shown as Figure 4-6; if it is high load, connect L to “AC Output L”, N to
“N” and Ground to “PE”, shown as Figure 4-6. Three phase system is analogous to
single phase.
12
1. AC Output L; 2. AC Output Branch L; 3. DC Input Negative; 4. DC Input Positive; 5. N; 6.
PE; 7. Bypass Input L Bus
Figure 4-6 Cable position in single phase system
Danger:
Prior to connection, make sure that all DC and AC fuses or switches are in the
“Off” position. Use a voltmeter to ensure that voltages are not present and fix
a safety marking stating “Switch ON Forbidden”.
Remove all metallic jewelry, watches, rings and/or metal necklaces.
Connect DC input cable and ensure correct polarity.
Install the controller and static switch modules as shown in the figures above and
install and fix the front panel with screws.CVC01 is shown in figure 4-7.
13
Figure 4-7 CVC01 Controller
The static switch is an important part in inverter system. Its main functions includes:
Implement synchronization between inverter and bypass; Control system’s work mode
and status; Finish un-interruption transfer between inverter and bypass; Overload and
short circuit protection etc.
It realizes the load safety transfer by high reliability component, the transfer time
between inverter and bypass is typically less than 4ms.
Indication Definitions
MAINS Light on when mains is normal
INVERTER Light on when system output is in inverter mode
BYPASS Light on when system output is in bypass mode
MBS Maintenance switch is in “maintenance bypass” position
ALARM Inverter output is either over or under voltage and frequency is out of
range; Mains is over or under voltage and frequency is out of range;
Out-of-step; Overload; Temperature is over high; Fan fault; Battery
voltage is out of range; Internal communication is abnormal
FAULT Light on during system failure
14
Figure 4-9 CPI Parallel Inverter
4.4.3 Backplane
Caution:
Eusure the appearance is good and no noise while shaking the module before
installation.
5. OPERATION INSTRUCTIONS
16
5.1 System Check
Ensure inverter system cabling is properly connected and screws are firmly
fastened.
Check for correct DC input polarity and ensure that the input voltage is within
operating range.
Check AC input L/N/PE and ensure that the input voltage is within operating
range.
Ensure ground cabling is properly connected to system.
Ensure all inverter modules have been properly installed and that the self-lock
screw is in the lock position.
Ensure all system switches are in the “OFF” position.
Ensure Security switch is in the “Normal” position, the Maintenance switch is
in “Normal Operation” position.
Close AC input switch in distribution panel, close “Mains” breaker in inverter system.
The controller and STS (static switch) modules will start to work.
First STS starts frequency check for 5 seconds, all LED light up. The controller displays
system information, such as system model etc.
5 seconds later, “MBS” LED will be flash and controller highlights the frequency which
be sampled by STS. Please check the frequency is same as local mains frequency or not.
If no, use “Increase”, “Decrease” keys to select frequency again. If STS sampling
frequency is different with controller default setting value, STS will use the sampling one
and send “Sys Para Err” alarm to controller.
Several seconds later, ”MAINS” and “BYPASS” light up, “Alarm” flash. Then close DC
switch in distribution panel, test DC voltage, mains voltage and system output voltage
by voltmeter. Check the tolerance between controller and voltmeter display, DC voltage
error is less than ±0.5V, AC voltage error is less than ±3V.
Check below LED status: Red LED on cabinet front door flickers, controller red LED
flickers. STS “MAINS”, “BYPASS” light up, “Alarm” flickers.
Open AC input switch “MAINS” after above check finished.
5.1.1.2 No mains input
Close DC breaker or Fuse in distribution panel, the controller and STS (static switch)
modules will start to work.
First STS starts self-check for 5 seconds, all LED light up. The controller displays
system information, such as system model etc.
5 seconds later, “MBS” LED will be flash and controller highlights the frequency which
STS has been used last time. Please check the frequency is same as local mains frequency
17
or not. If no, use “Increase”, “Decrease” keys to select frequency again. STS will use the
controller setting frequency to work.
“FAULT” LED lights up, test DC voltage by voltmeter. Check the tolerance between
controller and voltmeter display is less than ±0.5V.
Check below LED status: Red LED on cabinet front door light up, controller red LED
and STS red LED light up too.
Next to check “inverter module quantity configuration” below after finish above check.
First switch on DC input switch of a inverter module, yellow LED lights up for 1 second,
green LED lights up, wait for about 10 seconds, this module will output AC voltage, the
inverter’s information, such as voltage, current, serial number and alarm will be displayed
on controller menu “Inverter System” – “Inverter Status”.
Wait for 1 minutes, STS changes to inverter output and “INVERTER” lights up, “ALARM”
flickers. Test inverter voltage by voltmeter, compare it with controller display, the difference
is no more than ±3V.
Switch on the second inverter module’s DC input switch and do the same work as
above. The two inverter module will be parallel working after 10 seconds.
Open first module’s DC input switch, wait for inverter red LED becomes off. Turn on
the third inverter module. Watch the two inverter module’s parallel working.
Let each inverter module work with another module in parallel, observe the test result,
record inverter module’s serial number, output voltage’s display value and test value.
Caution:
If turn on inverter and find unusual noise shut down the inverter immediately
and remove it from rack. Do not try to power on it again but return it for
service.
18
5.1.4 System transfer test
1.Close “MAINS” breaker, 2 seconds later the system has no alarm. “INVERTER” LED
is on. Change the menu “Inverter System” – “STS Test” to “ON”, STS will transfer to mains
output, “INVERTER” LED is off, “BYPASS’ is on, the menu “STS Test” return to “OFF”
automatically and STS will transfer to inverter output after 10 seconds, “INVERTER” is on,
“BYPASS” becomes off.
2. Change the menu “Inverter System” – “STS Parameters” – “Mode” to “OFFLINE”,
STS transfer to mains output, “BYPASS’ is on, “INVERTER” LED becomes off. Change back
“Mode” to “ONLINE” again, STS will transfer to inverter output, “INVERTER” is on, “BYPASS”
becomes off.
3.Slide upward maintenance protection cover, move Security switch to “BYPASS”, STS
“MBS” indicator will be on, 2 seconds later, STS transfer to bypass and “BYPASS” LED is on,
continuous slide upward maintenance protection cover and twist “Maintenance bypass
switch” to “Maintenance Bypass” position quickly, the system output don’t interrupt, STS
“ALARM” flickers, controller display “In service” alarm. Slide down maintenance protection
cover, move Security switch to “NORMAL” position, 5 seconds later, “MBS” becomes off,
STS will change to inverter output status, “INVERTER” LED will be on.
19
Connect a dummy load (30% of full load) to the system output.
Close “MAINS” breaker and all DC input switches, wait for the system normal working,
change controller menu “Inverter System” – “STS Parameters” – “Mode” to “ONLINE”, the
system transfer to inverter output.
Close load switch and check each inverter module’s output current is normal or not.
Turn off the dummy load switch, turn off inverter system, move the dummy load after
finish test.
Caution:
In the parameter setting menu, you can choose password to set ON/OFF,
choosing ”ON”, the LCD appears black or click ”user log-off”, password
protection will initiate.
The controller menu: Under the touch screen there are four keys of
20
Select system frequency when system start-up
Set Frequency 50 Hz
Set Frequency 60 Hz
Remaining Time: 5S
↑ ↓ ← Esc
The menu will be selected automatically and highlight the selected menu or select
it manually.
Home Page
Frequency 50.0Hz
Mode: ONLINE 0
↑ ↓ ← Esc
Frequency 50.0Hz
VinDC 48.8V
IinDC 60.0A
↑ ↓ ← Esc
Frequency 50.0Hz
23:59 31-01-2011
21
↑ ↓ ← Esc
↑ ↓ ← Esc
The first page indicates: Voltage, current, frequency present, system mode
(online or offline) and alarms.
The second page indicates: AC voltage, frequency; DC voltage current;
The third home indicates: Inverter voltage, frequency and time.
The fourth home indicates: Active power, apparent power.
Inverter System
Alarm
System Setting
↑ ↓ ← Esc
Inverter Status
Inverter Parameters
STS Parameters
UIB Parameters
Other Information
↑ ↓ ← Esc
22
“Inverter status” menu;
Inverter Status
Vout AC 220V
Iout AC 0A
Alarm: No Alarm
↑ ↓ ← Esc
Indicates the relevant status of module, phase sequence, serial number, output
voltage, current and alarm.
Click ESC to quit this page and return to inverter system menu.
“Inverter parameters” menu
Quantity 10
Hi V alm 270Vac
Lo V alm 170Vac
Hi F alm 53.0Hz
Lo F alm 47.0Hz
↑ ↓ ← Esc
Mode: Online
Inv Hi V 270Vac
Inv Lo V 160Vac
Inv Hi F 53.0Hz
Inv Lo F 47.0Hz
Mains Hi V 270Vac
Mains Lo V 160Vac
Mains Hi F 53.0Hz
Mains Lo F 47.0Hz
Phase failure ON
↑ ↓ ← Esc
24
Inverter output.
Mains Lo V: If the mains voltage is lower than this value, STS alarms and transfer to
Inverter output.
Mains Hi F: If the mains frequency is higher than this value, STS alarms and transfer
to Inverter output.
Mains Lo F: If the mains voltage is lower than this value, STS alarms and transfer to
Inverter output;
↑ ↓ ← Esc
DC V Fault Spare
↑ ↓ ← Esc
25
If the value set to “USED”, the relevant alarm has occurred and the relevant relay will
trip.
Output Switch 1 0
Output Switch 2 0
Input Alm 3 0
Input Alm 4 0
Input Alm 5 0
Input Alm 6 0
Input Alm 7 0
Input Alm 8 0
↑ ↓ ← Esc
Input Alm X: 0 figures low voltage alarm; Short circuit the two pins of the terminal will
send the low voltage alarm.
↑ ↓ ← Esc
“Alarm” Menu
26
Alarm Log
↑ ↓ ← Esc
Controller Setting
User Logout
Time
Net Parameters
↑ ↓ ← Esc
User Logout: After password setting, click logout, Esc immediately and need password.
↑ ↓ ← Esc
27
User Password: User password, default password: 1111.
Language: The menu language
↑ ↓ ← ESC
↑ ↓ ← Esc
Caution
When system is in normal operation, the green light on door of the system is alight;
when system is in non-urgent alarm the green light will flicker (on/off each second);
when system is in urgent alarm, the light on door will flicker red (on/off each second);
when there is in fault without output, the red light will light up constantly.
29
Te1 H Heat sink 1 temperature is high
Te2 H Hear sink 2 temperature is high
Fan F Fan alarms
Caution
1. The upper limit of output current can be set according to total amount of
inverters connected in parallel. Caution: When actual output current exceeds
the upper limit value the system will be switched to AC bypass. Only when the
current is lower than 85% of output current will the system switch to inverter.
2. The definition of lower limit of battery voltage is: If DC input voltage (sensed
via the controller) is lower than the lower limit setting of battery voltage then
the inverter will be shut down. If DC input voltage recovers and rises up to the
value, the inverter will restart.
3. The old alarms will be displayed in alarm history. The first alarm after title is
the last alarm in system. A maximum of 500 alarms is stored in alarm history.
If there are more than 500 alarms the first alarms will be dropped.
4. If short circuit occurs in inverter mode, the system won’t be switched to AC
bypass. When the short circuit is removed, the system will be recovered.
5. The system is designed to have different audible alarms for different alarms.
Mains failure: A short tone will sound every 3 seconds.
System overload:A short tone will sound every 1 second.
DC under voltage: A short tone will sound every 1 second. (The sound will
alarm before 2 volts difference, for example, we set the
voltage to 44V, but the sound will alarm when DC
voltage decrease to 46V)
System failure: A long tone will sound.
6. All audible alarms can be set to mute in menu until new audible alarm occurs.
7. When the system is overloaded, it will transfer to the bypass line after 10
minutes
8. Refer to overload point setting in N+M redundant system, which is essential to
system reliability. The following formula is provided for reference.
I limit=N × k × I rated
I limit: Overload point in parallel redundant system
I rated: Rated output current for parallel inverter
N: (N+M) total amount of inverters designed to work in parallel
redundant system
M: (N+M) total amount of redundant inverters designed to work in
parallel redundant system
K: Parallel redundant coefficient, K equals 0.9.
30
Warning:
System set “default parameter” when being out of factory, the details are
seen in chapters blow.
Default “Set Over Load” setting is “Auto”, the system will set the overload
threshold automatically, if select “Manual”, please modify “Over Load”
accoring to the module numbers and capacity.
Digital input:
The user may input external alarm voltage-free contacts to controller through
digital input terminals.
Analog inputs:
From left to right, pin 1 for 12V, pin 2 for analog 1 input, pin 3 for analog 2 inputs,
and pin 4 for signal ground
TB: Battery temperature input, pin 1 for temperature transducer AD592+; pin 2
for temperature transducer AD592-, temperature sensor is optional.
TE:Ambient temperature input, pin 1 for temperature transducer AD592+; pin 2
for temperature transducer AD592-, temperature sensor is optional.
31
signal could display in controller.
Voltage-free contacts test: Choose the relevant relay menu in “UIB setting” when
alarms occur the relay will close.
The system can be viewed via Ethernet which supports TCP/IP, UDP, SNMP or
HTTP. The users can access to the system through SNMP software or web browser.
IP: 192.168.1.123
Mask: 255.255.255.0
Gate: 192.168.1.1
Trap1: 192.168.1.213
Trap2: 192.168.1.125
Set IP address, subnet mask code, default gateway and trap address on your PC to
match the network setting, please see above box. The computer’s network parameters
may be set as figure 5-3.
32
Figure 5-3
Caution
Figure 5-4
b. When input correctly then the page display system status like the follows;
33
Figure 5-5
34
Figure 5-6 SNMP node description
5.5.6. USB
35
Figure 5-7
b. Click “Next” to install drive program, choose the access under CVC01 Software
Driver and click NEXT (as per figure below)
Figure 5-8
c. After installation, CVC01 will be reflected as a common port, users can use USB as
a common communication port, and other steps are the same as RS232.
36
Figure 5-9
5.6 System Operation
Caution
To avoid high inrush current caused by load the load should be applied in system
gradually.
6. DEFAULT VALUE
39
UIB parameter setting
40
1. Write down inverter failure information;
2. Remove screws that secure front panel of inverter;
3. Turn off inverter switch on front panel and corresponding DC input switch inside
rack;
4. Gently slide inverter out of rack;
5. Insert new inverter ensuring connection to rear terminal and fix with screws;
6. Turn on DC input switch and inverter switch on front panel. The new inverter
starts to work in few seconds;
7. Pack the failed inverter in original shipping package and return for service
(attach failure information).
The inverter replacement is completed.
41
failed condition and its status may have direct influence on power quality. Therefore,
battery maintenance including battery discharge test should be performed every 6
months.
8. TROUBLESHOOTING
Red light in long time Fault Check the reason of shut down
42
9.TECHNICAL DATA
43
Protection Input: high/low voltage shut down;
reserve polarity protection.
Short circuit: current limitation
automatically and recover after
resolution.
Overload: 100 to 125% overload
supports 10 minutes, 126 to 150%
overload supports 10 seconds, 150%
above overload supports 2 seconds.
Over Temperature:
When inverter internal temperature rises
over 90C it will be disconnected from the
system. When temperature returns to
normal the inverter will reconnect to the
system.
Intelligent fan speed control
Panel indication LED indicate inverter status
Safe standard IEC60950
EMC CISPR22 classB
Humidity IEC61000
Environment Temperature -5 to 50C
Humidity <90%, non-condensing
Dimension(mm) 221W×355D×88H
Weight(kg) 5.2
Model CST63K
Nominal Capacity 100A×3
Operating voltage 40 to 60Vdc
Or 90 to 300Vac
Transfer Time Controlled transfer 0 ms
abnormal transfer 4 ms
Noise ≤50(dBA)
44
Protection Input protection of reverse
connection
Overload: 100 to 125% overload
supports 10 minutes , 126 to 150%
overload supports 10 seconds ,
150% above overload supports 2
seconds.
Over Temperature: The temperature
of heat sink is over 90C, alarm will
appear.
Intelligent fan speed control
Panel indication LED indicate work status
Safe standard IEC60950
EMC CISPR22 classB
Immunity IEC61000
Environment Temperature -5 to 50℃
Humidity <90%, non condensing
Dimension(mm) 482.6W×340D×132H
Weight(kg) 13
45
1 2 3 4 5 6 7 8
9 10
5 6
1 2
1@MAINS 27@STS POWER CON 5@OUT SW
1 2 BYP LC 2@MBS11 12 1 2
P7 BPYC OUTC P9
3 4 BYP LB 7 8 3 4
P4 BPYB OUTB P6
5 6 BYP LA 3 4 5 6
P1 BPYA OUTA P3
D D
P2 P5 P8 13 14 1 2 43@LOCK SW 1 2
22@BYP PE 9@INV PE INVA INVB INVC 6@OUT PE
PE
Appendix 1
1 2
MO C
WO DN IW
MO C
4 8 V+
NO IT AT S W S
1
40@AUX POWERX 7 2
To S TS B PA X 6 G ND B X3 L
2 1
1
2
2
1
1 2
X5 X2 X4
4 8 V+
1
1
2
1
2
1
2
To S CU BP AX 5 G ND B X8 X5
2 X1
1 2
X4 CAN B YP L
5 X7 M-S FA U LT
1
L X2 N
4
X1 2
11@DC+ X7 DC+ 3
3
C OM
B AT + 24@CT 2
8@INVLA
BAT+
41@INVLB
42@INVLC
28@1#CPI3K N X1 1
CT 1 2
X6 DC-
38@DC- PE X3 26@STS BPA
B AT - 1 2 3 4 12@1#SW X5 CAN
BAT- GND B S -MFA U LT
1 1
48 + X9 X2 C OM
2 2
To A U X PO W E R
X4 CAN X2
C X4 C
X14 X1 L X2
GND B
1 1
+1 2V X7 DC+
-12V
2 2 29@2#CPI3K N X1
48 + IOU T X6 X3
CVT system Diagram
3 3
GND 1 2
4 X6 DC-
X3
PE X3
B AT + 13@2#SW X5 CAN X3
1 48 5A
1
2 X2 48 5B
B AT - X2 2
3 X29
1
X4 CAN
48 + X 0 48 V+
3@UIB 2 L X2 X1 X5
1
3 X7 DC+ 2 To A U X PO W E R X 1
46
GND B
GND 3
1 30@3#CPI3K N X1
IO1 X1
2 X9
1 2
39@DOOR-LED X6 DC- 25@CVC01 BPA
X10 14@3#SW PE X3 1 X4
X11
X5 CAN 2
X12 + Amb ien t 3 X1 WEB
8 I/O 1
X13 X5 - Temperature 4
2
X16 5
X17 6
X6 1
+ B attery 15@4#SW 31@4#CPI3K 7
CVC01
-
GND
1
X19 2 Temperature 16@5#SW 32@5#CPI3K 8
IO8 9
2 17@6#SW 33@6#CPI3K 10
18@7#SW 34@7#CPI3K C N4
USB
NO X6
B
C OM
1 19@8#SW 35@8#CPI3K B
2 1
NC
3
20@9#SW 36@9#CPI3K 2
X21
3
X20
X26 L X2
X27 X7 DC+
NO
1
C OM
2
X28 37@10#CPI3KN X1
NC 1 2
3 X6 DC-
1
2
3
4
C N1
PE X3
21@10#SW X5 CAN
C N2 R S23 2 OR RS 485
44@RS232
X4 CAN
L X2
X7 DC+
47@11#CPI3K N X1
1 2
X6 DC-
45@11#SW PE X3
X5 CAN
X4 CAN
A L X2 A
X7 DC+
48@12#CPI3K N X1 Title
1 2
X6 DC- CVT Sy stem Diagram
46@12#SW PE X3
X5 CAN Size N u mb er R ev is io n
A2 V1.0
D ate: 1 7 -F eb -2 0 1 2 Sh eet o f
File: E:\Diag ram\C V M (T ) D iag ram. Dd b D raw n B y :
1 2 3 4 5 6 7 8
Appendix 2 CVT System Test sheet
CVT System Test Sheet
Serial No: Date:
Test Result: Inspector:
Test
Item Requirement
Result
Structure
Product Marking
No visual color difference, stain,
Exterior Galvanization
scratch and/or abrasion
Painting
47