You are on page 1of 51

Parallel Inverter System

Model CVT

User Manual
Version: V1.2

The drawings and photographs in this manual are to be considered as


general guidelines, a specific system may vary in layout or component
positioning.
Please refer to the documents provided with your system for
photographs, connection and information specific to that system.

Cavio Technologies Co., Ltd.


Building 6, SME Center, Jiu Tong Road, Dongxihu District,
Wuhan, Hubei, P.R. China
Tel: +86 27 83391680
WWW.CAVIOTECH.COM

i
1. DECLARATION

Without prior written authorization from Cavio any information, diagrams and
drawings contained in this manual cannot be copied for manufacture and/or sales by
any company and/or individual.

1.1 Scope of the Manual

The following information, diagrams and drawings provide the information


required for equipment installation, commissioning, operation, fault diagnosis and
maintenance.

We reserve the right to make modifications to the products described in this


manual without notification. For any enquiry regarding up to date product
information please contact Cavio directly or our local representative.

i
TABLE OF CONTENTS

1. DECLARATION ........................................................................................... i
1.1 Scope of the Manual ............................................................................ i
2.SAFETY PRECAUTION ................................................................................1
2.1 Magnetic Field .....................................................................................1
2.2 Grounding ........................................................................................... 1
2.3 Flammable Gas ................................................................................... 1
2.4 General Operation ...............................................................................1
2.5 Service ................................................................................................ 1
2.6 General Maintenance .......................................................................... 1
2.7 Safety Marking ....................................................................................1
3. INTRODUCTION ....................................................................................... 3
3.1 Product Overview .............................................................................3
3.2 Outline Diagram ..................................................................................4
3.2.1 380Vac/50 or 60Hz system outline ...............................................4
3.2.2 208Vac/50 or 60Hz system outline ...............................................5
3.3 Product Model Number .................................................................. 6
4. INSTALLATION INSTRUCTION ...........................................................8
4.1 Preparation ...................................................................................... 8
4.1.1 Site Location ................................................................................. 8
4.1.2 Tools Required .............................................................................. 9
4.1.3 Cable Selection ..............................................................................9
4.2 Unpacking Inspection .................................................................... 10
4.2.1 Product Unpacking ......................................................................10
4.2.2 Check for damage ....................................................................... 10
4.3 System Installation ...........................................................................11
4.3.1 Single Phase Inverter System ..................................................... 11
4.4 Module Installation ...........................................................................13
4.4.1 Controller Module and Static Switch Module Installation .......... 13
4.4.2 Inverter Module Installation .......................................................14
4.4.3 Backplane ....................................................................................15
5. OPERATION INSTRUCTIONS ................................................................16
5.1 System Check ................................................................................. 17
5.1.1 Controller and Static Switch Check .............................................17
5.1.2 Inverter module quantity configuration ..................................... 18
5.1.3 Inverter Check ............................................................................ 18
5.1.4 System transfer test ....................................................................19
5.1.5 System Check with Dummy Load (if available) .......................... 19
5.2 System Start-Up .................................................................................20
5.3 Parameter Setting ..............................................................................20
5.4 UIB Test ............................................................................................... 31

ii
5.5 Communication Test ............................................................................ 32
5.5.1. Ethernet outline ......................................................................... 32
5.5.2. Website setting .......................................................................... 32
5.5.3. Web Service ............................................................................... 33
5.5.4. SNMP Application .......................................................................34
5.5.5. RS232 / RS485 ...........................................................................35
5.5.6. USB .............................................................................................35
5.6 System Operation .................................................................................37
5.7 Maintenance Switch Instructions ........................................................ 38
5.7.1 Replacement Controller and Static Switch process .................... 38
5.7.2 The use of maintenance switch ...................................................38
5.8 System Shut Down ............................................................................... 39
6. DEFAULT VALUE ..................................................................................... 39
7. REPLACEMENT and MAINTENANCE ..................................................... 40
7.1 Inverter Module Replacement .......................................................... 40
7.2 Controller Replacement .................................................................... 41
7.3 Static Switch Replacement ............................................................... 41
7.4 General Maintenance ........................................................................ 41
7.4.1 Daily Maintenance .......................................................................41
7.4.2 Battery Maintenance ...................................................................41
8. TROUBLESHOOTING ...............................................................................42
9.TECHNICAL DATA .................................................................................... 43
Appendix 1 CVT system Diagram ........................................................... 46
Appendix 2 CVT System Test sheet ........................................................ 47

iii
2.SAFETY PRECAUTION
The safety instructions described in this chapter are applicable to operation and
maintenance personnel. The instructions may not include some special warnings that
may be mentioned in related chapters. This equipment functions with high internal
voltages which may cause personal injury and/or equipment damage.
We do not accept any responsibility for any misuse in regards to design,
manufacture and operation and cannot be held liable for indirect or consequential
damages.

2.1 Magnetic Field


The high currents in the equipment produce magnetic fields which may be
hazardous to the human body and sensitive electronic devices.

2.2 Grounding
The neutral and ground cables must be securely terminated to earth to ensure
correct equipment operation.
If the neutral and ground cables are not correctly terminated then faulty
equipment function and possible failure will result.
We take no responsibility for failures due to incorrect termination of neutral and
ground cables.

2.3 Flammable Gas


To avoid risk of explosion or fire do not operate the equipment in flammable gas
environments.

2.4 General Operation


There are hazardous high voltages inside this equipment and general operation
should be undertaken only by a qualified operator.

2.5 Service
If it is necessary to remove the external covers for service or component
replacement, ensure that all power sources are off and discharge procedures are
followed correctly, note that discharge may take several minutes.

2.6 General Maintenance


General maintenance ought not be conducted alone, please ensure that
assistance or first aid is immediately available.

2.7 Safety Marking


The safety markings described in this manual and shown in Table 2-1 are provided
for qualified operators for installation, operation and maintenance.

Table 2-1 Safety Markings and Explanation

1
Safety Marking Explanation

Safety Indication

Electric Shock

The safety indication is divided to 3 grades: Danger, Warning and Caution.

Danger

Warning

Caution

Ignoring any of the above safety instrucions may result in personal injury and/or
equipment damage

2
3. INTRODUCTION

3.1 Product Overview


The CVT parallel inverter power system is an integrated power system consisting
of between 3 to 63 parallel inverter modules, CVC01 controller module, static switch
module and AC/DC PDU’s.
The inverter module inverts the DC input to high quality AC sine wave output
using high frequency technology. Between 2 and 63 inverter modules may be
connected in parallel to form n+1…n+m redundant system to deliver AC power to a
load and provide a nominal output power rating based on configuration.
In case of system overload or failure the load is switched to an AC bypass line by
the static switch module without power interruption. The switch will return the load to
the system output upon restoration of the AC system output or the overload is
removed.
This system supplies uninterrupted, efficient, quality and reliable AC power and
includes system control, alarms, communications and protection. It is ideally suited for
power equipment such as computer networks, telecommunications, finance, electric
utilities, transportation, military, universities, research institutes as well as many other
applications.

Control Unit RS232/SNMP/Ethernet Port

DC Input AC Output AC Output


DC PDU Inverter Static Switch Transfer Switch
PDU

AC Input
AC Input PDU

Figure 3-1 CVT single line diagram of power system


The system features include:
 High quality low distortion sine wave output.
 Parallel redundant inverter modules providing a maximum output of up to
126kVA three phase.
 The inverter modules automatically share the load current.
 The inverter modules are hot swappable.
 The controller is hot swappable.
 The static switch module is hot swappable.
 The static switch modules can be configured in parallel.
 Intelligent controller design with RS232/USB/SNMP communication port.
 High power density, compact construction and light weight.
 Records up to 500 events in history.
 The controller display supports: Chinese, English, Spanish and Portuguese
languages.

3
3.2 Outline Diagram

3.2.1 380Vac/50 or 60Hz system outline

CVT9K-48/380-RT CVT18K-48/380-RT CVT18K-48/380-1M


9kVA From 9 to 18kVA From 9 to 18kVA

CVT36K-48/380-2M CVT72K-48/380-2M CVT126K-48/380-2M


From 9 to 36kVA From 9 to 72kVA From 9 to 126kVA

4
CVT153K-48/380-2M CVT189K-48/380-2M
From 9 to 153kVA From 9 to 189kVA

Figure 3-2 380Vac system outline

3.2.2 208Vac/50 or 60Hz system outline

CVT9K-48/208-RT CVT18K-48/208-RT CVT18K-48/208-1M


9kVA From 9 to 18kVA From 9 to 18kVA

5
CVT36K-48/208-2M CVT72K-48/208-2M CVT126K-48/208-2M
From 9kVA to 36kVA From 9 to 72kVA From 9 to 126kVA
Figure 3-3 208Vac system outline

3.3 Product Model Number


Each system includes cabinet, controller, static and manual switches and inverter
modules with standard rack dimensions of;

2m rack Dimension (mm): 600W × 600D × 2000H

Table 3-1 System configurations

Output Capacity Model Number Remark


Voltage

1 x 2m rack, 1 x static switch,


36kVA CVT36K-A/B
1 x controller and max 12 x inverter

1 x 2m rack, 1 x static switch,


380Vac 63kVA CVT63K-A/B
1 x controller and max 21 x inverter

2 x 2m rack, 1 x static switch,


126kVA CVT126K-A/B
1 x controller and max 42 x inverter

6
1 x 2m rack, 1 x static switch,
36kVA CVT36K-A/B
1 x controller and max 12 x inverter
208Vac
1 x 2m rack, 1 x static switch,
63kVA CVT63K-A/B
1 x controller and max 21 x inverter

See separate chart for static switch ratings.

Model number definition;

CVT: Three phase

A: System DC input voltage: 48, 110 or 220Vdc;


B: System AC output voltage: 110, 115, 120, 127, 208, 220, 230 or 240Vac.

Examples: CVT63K-48/380
System rating is three phase 63kVA with battery voltage of 48Vdc, output voltage of
380Vac(phase to phase) and frequency of 50 or 60Hz.

Caution:
System frequency: 50 or 60Hz, the system can be self-adaptive mains frequency.

Table 3-2 Controller model number

Model Remark
CVC01 Dimension: 482.6W× 150D ×88Hmm Weight: 2.3kg

Table 3-3 Static switch model number

Capacity Model Remark

100A×3 CST63K-48/380 Dimension: 482.6W×340D ×132Hmm Weight:13kg

100A×3 CST40K-48/208 Dimension: 482.6W×340D ×132Hmm Weight:13kg

200A×3 CST126K-48/380 Dimension: 482.6W×340D ×266Hmm Weight:16kg

7
200A×3 CST63K-48/208 Dimension: 482.6W×340D ×266Hmm Weight:16kg

Table 3-4 Parallel Inverter model number

Type Model Remark


Parallel Inverter CPI3K-A/B Dimension: 221W×355D×88Hmm Weight:5.2 kg

Caution:

Definition;
A: DC input voltage: 48, 110 or 220Vdc;
B: AC output voltage: 125Vac (suitable for 110, 115, 120 and 127Vac) or
220Vac (suitable for 208, 220, 230 and 240Vac).

Example: CPI3K-48/220

The inverter is single phase 3kVA with battery voltage of 48Vdc and output
voltage of 220Vac, suits for 50 and 60Hz.

Ensure that the product complies with the specific power requirements applicable
to your country.

4. INSTALLATION INSTRUCTION
This chapter outlines the tools required, cable selection, unpacking inspection and
system installation essential for correct system operation.

4.1 Preparation

4.1.1 Site Location


To ensure correct operation, please install system in an environmentally controlled
location. To avoid system over temperature please ensure unobstructed smooth airflow
for cooling and allow service access at the rear of the enclosures.
The equipment is best located as follows,

 As near as practicable to the power sources and loads for ease of cabling
 In a clean and dust free environment
 At altitude of not more than 1000m
 Preferably at a temperature of 20C. Note that the maximum system operating
environment is between -5 to 50C with relative humidity not more than 90%.
 Away from corrosive, explosive and/or destructive gas and conductive dust
 Away from any heat source
8
 In a vibration free location and with a vertical tilt of not more than 5%

Warning

A controlled temperature environment and clear airflow are very important for
system operation particularly during any overload conditions.

4.1.2 Tools Required

Various tools are essential for product installation, a guide;

 Head screwdrivers: 5, 7 and 10mm


 Slot head screwdrivers: 5, 7 and 10mm
 Wrenches: 6, 8mm and 14mm
 Pliers: 150mm
 Pincers
 Digital multi-meter
 wire cutter and stripper
 Crimping tool, large gauge wire
 Scissors

4.1.3 Cable Selection


The required cable size needs to be calculated according to the input/output
current and the current capability of the local electric power system.

The formula is shown below:

DC Current Max = VA ×0.8 ÷ 0.90 ÷ Minimum input DC voltage


AC Current Max = VA ÷AC voltage

 In the case of copper core cable we recommend a current density of 5A/ mm2
for AC and 2.5A/ mm2 for DC cable.
 The maximum cable thickness required is relative to cable length especially
with high DC currents. If the inverter is located far from the DC power the
cable thickness must be increased. A maximum voltage drop from DC source
to system input of not more that 1Vdc is recommended.
 Maximum ambient temperature must also be taken into consideration. If the
ambient temperature is high then the cable size must be increased

9
Max. DC
Min. DC cable Max. AC output Min. AC
Model input
(mm ) 2
current (A) cable(mm2)
current(A)

CVT36K-48/380 800 320 55×3 11×3

CVT63K-48/380 1400 560 95×3 19×3

CVT126K-48/380 2800 1120 191×3 38×3

Table 4-1 A guide to cable selection.

4.2 Unpacking Inspection

4.2.1 Product Unpacking


Each module is packed separately in rugged, double walled cardboard boxes with
solid inserts and shipped on stock to ease loading and minimize shock during ocean or
air transportation.
Upon receipt of the shipment, and prior to unpacking, check for any exterior
damage to the shipping packaging. If any packaging damage is observed contact the
carrier or supplier immediately.

4.2.2 Check for damage


Proceed with unpacking and inspect the equipment exterior for damage. If there is
any damage save the original shipping package. If any damage is observed, continue
the inspection for any internal damage as described in Chapter 7 headed
“REPLACEMENT AND MAINTENANCE”.
In the unlikely event of internal damage do not connect the product to the power
source but immediately contact supplier for advice. If the product needs to be returned
for service it should be packed in its original shipping package.
Verify that all necessary parts as per the packing list are supplied.

Caution

If the product needs to be returned for service, it should be returned in its original
packaging. If the original packaging is unavailable or severly damaged then make sure
the product is packed safely and correctly to prevent shipping damage. We are not
responsible for any damage caused by the improper packing of a returned product.

10
4.3 System Installation

AC Input I Rectifier System Inverter System AC Output


AC PDU DC Distribution AC Output PDU

AC Input II

Battery

Figure 4-1 Standard system single line diagram

Prior to system installation, check that the installation site is suitable for size,
space and weight and then follow the installation procedures.

4.3.1 Single Phase Inverter System

1. Unpack rack and open back door shown in Figure 4-2;

Figure 4-2 Opening rear door latches

2. Fix the rack via the mounting points with expansion bolts M10 × 30 shown in
Figure 4-3;

11
Figure 4-3 mounting points Figure 4-4 open front door

3.Ensure that both the DC and AC inputs are disconnected. Open front door as
shown in Figure 4-4 (the front door key is put in the back of front door). Ensure that all
switches are in the “Off” position, assistant switch in “NORMAL” position and transfer
switch in “Normal Operation” position. AC and DC PDUs are shown in Figure 4-5.

1: Panel Screw; 2: Inverter DC Input Switch; 3: AC Output Breaker; 4: AC Output Branch


5: Bypass Input Breaker; 6: Security Switch; 7: Maintenance Bypass Switch
Figure 4-5 AC and DC PDU in single phase system

4.Prepare DC and AC input cables according to the calculations provided. Connect


the system and DC/AC distribution separately as shown in Figure 4-6 and Table 4-1.

5.Connect AC output cable as required, as shown in Figure 4-6 and Table 4-1.
In single phase system, if it is low load, connect L to “Output L Branches”, N to “N” and
Ground to “PE”, shown as Figure 4-6; if it is high load, connect L to “AC Output L”, N to
“N” and Ground to “PE”, shown as Figure 4-6. Three phase system is analogous to
single phase.

12
1. AC Output L; 2. AC Output Branch L; 3. DC Input Negative; 4. DC Input Positive; 5. N; 6.
PE; 7. Bypass Input L Bus
Figure 4-6 Cable position in single phase system

Danger:

 Prior to connection, make sure that all DC and AC fuses or switches are in the
“Off” position. Use a voltmeter to ensure that voltages are not present and fix
a safety marking stating “Switch ON Forbidden”.
 Remove all metallic jewelry, watches, rings and/or metal necklaces.
 Connect DC input cable and ensure correct polarity.

4.4 Module Installation

4.4.1 Controller Module and Static Switch Module Installation

Install the controller and static switch modules as shown in the figures above and
install and fix the front panel with screws.CVC01 is shown in figure 4-7.

13
Figure 4-7 CVC01 Controller

The static switch is an important part in inverter system. Its main functions includes:
Implement synchronization between inverter and bypass; Control system’s work mode
and status; Finish un-interruption transfer between inverter and bypass; Overload and
short circuit protection etc.
It realizes the load safety transfer by high reliability component, the transfer time
between inverter and bypass is typically less than 4ms.

Figure 4-8 Static Switch Module

Table 4-2 Static Switch Module Indication Definition

Indication Definitions
MAINS Light on when mains is normal
INVERTER Light on when system output is in inverter mode
BYPASS Light on when system output is in bypass mode
MBS Maintenance switch is in “maintenance bypass” position
ALARM Inverter output is either over or under voltage and frequency is out of
range; Mains is over or under voltage and frequency is out of range;
Out-of-step; Overload; Temperature is over high; Fan fault; Battery
voltage is out of range; Internal communication is abnormal
FAULT Light on during system failure

4.4.2 Inverter Module Installation


The inverter module is hot swappable.
Remove the module from the package and insert it into the magazine ensuring
good connections with the back terminals then lock the lock-screw of the front panel.

14
Figure 4-9 CPI Parallel Inverter

The definition of inverter indication:


 Green light: Normal
 Green light flicker: Communication is abnormal
 Yellow light flicker: Inverter voltage is abnormal, inverter frequency is out
of range, Heat sink is over temperature, fan fault,
overload.
 Red light flicker: Address is abnormal or internal fault
 Red light: No output

4.4.3 Backplane

1. Inverter output L 2. Inverter output N 3. DC input +ve 4.DC input –ve


5. Parallel communication port 6. DIP switch 7. Inverter PE
Figure 4-10 Backplane
Module Address (DIP switches):

Item Position1 Position2 Position3 Position4 Position5 Position6 Position7 Position8


1 ON OFF OFF OFF OFF OFF OFF OFF
2 OFF ON OFF OFF OFF OFF OFF OFF
3 ON ON OFF OFF OFF OFF OFF OFF
4 OFF OFF ON OFF OFF OFF OFF OFF
5 ON OFF ON OFF OFF OFF OFF OFF
6 OFF ON ON OFF OFF OFF OFF OFF
7 ON ON ON OFF OFF OFF OFF OFF
8 OFF OFF OFF ON OFF OFF OFF OFF
15
9 ON OFF OFF ON OFF OFF OFF OFF
10 OFF ON OFF ON OFF OFF OFF OFF
11 ON ON OFF ON OFF OFF OFF OFF
12 OFF OFF ON ON OFF OFF OFF OFF
13 ON OFF ON ON OFF OFF OFF OFF
14 OFF ON ON ON OFF OFF OFF OFF
15 ON ON ON ON OFF OFF OFF OFF
16 OFF OFF OFF OFF ON OFF OFF OFF
17 ON OFF OFF OFF ON OFF OFF OFF
18 OFF ON OFF OFF ON OFF OFF OFF
19 ON ON OFF OFF ON OFF OFF OFF
20 OFF OFF ON OFF ON OFF OFF OFF
21 ON OFF ON OFF ON OFF OFF OFF
22 OFF ON ON OFF ON OFF OFF OFF
23 ON ON ON OFF ON OFF OFF OFF
24 OFF OFF OFF ON ON OFF OFF OFF
25 ON OFF OFF ON ON OFF OFF OFF
26 OFF ON OFF ON ON OFF OFF OFF
27 ON ON OFF ON ON OFF OFF OFF
28 OFF OFF ON ON ON OFF OFF OFF
29 ON OFF ON ON ON OFF OFF OFF
30 OFF ON ON ON ON OFF OFF OFF
31 ON ON ON ON ON OFF OFF OFF
32 OFF OFF OFF OFF OFF ON OFF OFF
33 ON OFF OFF OFF OFF ON OFF OFF
34 OFF ON OFF OFF OFF ON OFF OFF
35 ON ON OFF OFF OFF ON OFF OFF
36 OFF OFF ON OFF OFF ON OFF OFF
37 ON OFF ON OFF OFF ON OFF OFF
38 OFF ON ON OFF OFF ON OFF OFF
39 ON ON ON OFF OFF ON OFF OFF
40 OFF OFF OFF ON OFF ON OFF OFF
41 ON OFF OFF ON OFF ON OFF OFF
42 OFF ON OFF ON OFF ON OFF OFF

Caution:

 Eusure the appearance is good and no noise while shaking the module before
installation.

 Insert module and ensure good connection with backplane.

 Ensure the relevant MCB is OFF before module replacement.

5. OPERATION INSTRUCTIONS
16
5.1 System Check

 Ensure inverter system cabling is properly connected and screws are firmly
fastened.
 Check for correct DC input polarity and ensure that the input voltage is within
operating range.
 Check AC input L/N/PE and ensure that the input voltage is within operating
range.
 Ensure ground cabling is properly connected to system.
 Ensure all inverter modules have been properly installed and that the self-lock
screw is in the lock position.
 Ensure all system switches are in the “OFF” position.
 Ensure Security switch is in the “Normal” position, the Maintenance switch is
in “Normal Operation” position.

5.1.1 Controller and Static Switch Check

5.1.1.1 Normal mains input

Close AC input switch in distribution panel, close “Mains” breaker in inverter system.
The controller and STS (static switch) modules will start to work.
First STS starts frequency check for 5 seconds, all LED light up. The controller displays
system information, such as system model etc.
5 seconds later, “MBS” LED will be flash and controller highlights the frequency which
be sampled by STS. Please check the frequency is same as local mains frequency or not.
If no, use “Increase”, “Decrease” keys to select frequency again. If STS sampling
frequency is different with controller default setting value, STS will use the sampling one
and send “Sys Para Err” alarm to controller.
Several seconds later, ”MAINS” and “BYPASS” light up, “Alarm” flash. Then close DC
switch in distribution panel, test DC voltage, mains voltage and system output voltage
by voltmeter. Check the tolerance between controller and voltmeter display, DC voltage
error is less than ±0.5V, AC voltage error is less than ±3V.
Check below LED status: Red LED on cabinet front door flickers, controller red LED
flickers. STS “MAINS”, “BYPASS” light up, “Alarm” flickers.
Open AC input switch “MAINS” after above check finished.
5.1.1.2 No mains input
Close DC breaker or Fuse in distribution panel, the controller and STS (static switch)
modules will start to work.
First STS starts self-check for 5 seconds, all LED light up. The controller displays
system information, such as system model etc.
5 seconds later, “MBS” LED will be flash and controller highlights the frequency which
STS has been used last time. Please check the frequency is same as local mains frequency

17
or not. If no, use “Increase”, “Decrease” keys to select frequency again. STS will use the
controller setting frequency to work.
“FAULT” LED lights up, test DC voltage by voltmeter. Check the tolerance between
controller and voltmeter display is less than ±0.5V.
Check below LED status: Red LED on cabinet front door light up, controller red LED
and STS red LED light up too.
Next to check “inverter module quantity configuration” below after finish above check.

5.1.2 Inverter module quantity configuration


According to real quantity of inverter modules to modify ”Inverter System”-“Inverter
Parameters” – “Quantity”.

5.1.3 Inverter Check

5.1.3.1 Parallel working for two inverter modules

First switch on DC input switch of a inverter module, yellow LED lights up for 1 second,
green LED lights up, wait for about 10 seconds, this module will output AC voltage, the
inverter’s information, such as voltage, current, serial number and alarm will be displayed
on controller menu “Inverter System” – “Inverter Status”.
Wait for 1 minutes, STS changes to inverter output and “INVERTER” lights up, “ALARM”
flickers. Test inverter voltage by voltmeter, compare it with controller display, the difference
is no more than ±3V.
Switch on the second inverter module’s DC input switch and do the same work as
above. The two inverter module will be parallel working after 10 seconds.
Open first module’s DC input switch, wait for inverter red LED becomes off. Turn on
the third inverter module. Watch the two inverter module’s parallel working.
Let each inverter module work with another module in parallel, observe the test result,
record inverter module’s serial number, output voltage’s display value and test value.

5.1.3.2 Parallel working for all inverter modules


Close all DC input switches to let all inverter modules start to work in parallel. All
inverter module green LED are on. STS “INVERTER” is on, ”ALARM” flickers. Controller
yellow LED flickers. Green LED on front door of inverter system flickers. Observe all LED’s
status are same as above description.

Caution:

 If turn on inverter and find unusual noise shut down the inverter immediately
and remove it from rack. Do not try to power on it again but return it for
service.

18
5.1.4 System transfer test

5.1.4.1 Online mode(No need test it without mains input)

1.Close “MAINS” breaker, 2 seconds later the system has no alarm. “INVERTER” LED
is on. Change the menu “Inverter System” – “STS Test” to “ON”, STS will transfer to mains
output, “INVERTER” LED is off, “BYPASS’ is on, the menu “STS Test” return to “OFF”
automatically and STS will transfer to inverter output after 10 seconds, “INVERTER” is on,
“BYPASS” becomes off.
2. Change the menu “Inverter System” – “STS Parameters” – “Mode” to “OFFLINE”,
STS transfer to mains output, “BYPASS’ is on, “INVERTER” LED becomes off. Change back
“Mode” to “ONLINE” again, STS will transfer to inverter output, “INVERTER” is on, “BYPASS”
becomes off.
3.Slide upward maintenance protection cover, move Security switch to “BYPASS”, STS
“MBS” indicator will be on, 2 seconds later, STS transfer to bypass and “BYPASS” LED is on,
continuous slide upward maintenance protection cover and twist “Maintenance bypass
switch” to “Maintenance Bypass” position quickly, the system output don’t interrupt, STS
“ALARM” flickers, controller display “In service” alarm. Slide down maintenance protection
cover, move Security switch to “NORMAL” position, 5 seconds later, “MBS” becomes off,
STS will change to inverter output status, “INVERTER” LED will be on.

5.1.4.2 Offline mode


1 . Close “MAINS” breaker, 2 seconds later the system has no alarm. Wait for 10
seconds again, the system output mains and “BYPASS” LED is on. Change controller menu
“Inverter System” – “STS Parameters” – “STS Test” to “ON”, STS transfer to inverter output
and “INVERTER” lights us. The menu “STS Test” return to “OFF” automatically and STS will
transfer to bypass output after 10 seconds, “BYPASS” is on.
2.Change the menu “Inverter System” – “STS Parameters” – “Mode” to “ONLINE”, STS
transfer to inverter output, “INVERTER’ is on, “BYPASS” LED becomes off. Change back
“Mode” to “OFFLINE” again, STS will transfer to mains output, “BYPASS” is on, “INVERTER”
becomes off.
3.Slide upward maintenance protection cover, move Security switch to “BYPASS”, STS
“MBS” indicator will be on, STS output mains and “BYPASS” LED is on, continuous slide
upward maintenance protection cover and twist “Maintenance bypass switch” to
“Maintenance Bypass” position quickly, the system output don’t interrupt, STS “ALARM”
flickers, controller display “In service” alarm. Slide down maintenance protection cover,
move Security switch to “NORMAL” position, 5 seconds later, “MBS” becomes off, STS will
hold mains output status, “BYPASS” is on, “INVERTER” LED becomes off. Observe above
LED indicators are same as the descriptions when conversion happened.

5.1.5 System Check with Dummy Load (if available)


Open bypass input “MAINS” breaker and all DC input switches.

19
Connect a dummy load (30% of full load) to the system output.
Close “MAINS” breaker and all DC input switches, wait for the system normal working,
change controller menu “Inverter System” – “STS Parameters” – “Mode” to “ONLINE”, the
system transfer to inverter output.
Close load switch and check each inverter module’s output current is normal or not.
Turn off the dummy load switch, turn off inverter system, move the dummy load after
finish test.

5.2 System Start-Up


After system check is completed, the system may now be started,
1.Ensure all switches are off.
2.Switch on AC input breaker on AC distribution and DC input breaker or fuse on
DC distribution. Controller and static switch start to operate. The “BYPASS” LED
indicator will light up in 30 seconds. STS change to bypass output status.
3. Close all DC input MCB’s, inverter will work normally, static switch “INVERTER”
lights up and STS transfer to inverter output.
System start up is completed

4. Check each menu in controller and see the setting parameters.


5. Clear alarm loges: Set menu “Alarm” – “Delete Log” to “ON”.
Finish the system start-up.

5.3 Parameter Setting


After the system start-up is completed and functions correctly some system
parameters need to be set. Prior to parameter setting read setting instructions
carefully.

Caution:

 After start password protection will indicate password protection when


entering again. If input shows “user” password, you will have user permission.
If the input shows “Admin” password, you will have the “Admin” permission.
“User” can check parameter settings of the system, but can’t modify
parameters. “Admin” can do both parameter setting and modification.

 In the parameter setting menu, you can choose password to set ON/OFF,
choosing ”ON”, the LCD appears black or click ”user log-off”, password
protection will initiate.

The controller menu: Under the touch screen there are four keys of

indicates “increase”, ”decrease”, ”enter” and “Esc”.

20
Select system frequency when system start-up
Set Frequency 50 Hz
Set Frequency 60 Hz
Remaining Time: 5S

↑ ↓ ← Esc

The menu will be selected automatically and highlight the selected menu or select
it manually.
Home Page

SYSTEM OUTPUT DATA 1/4

Vout AC 220V 221V 220V

Iout AC 20A 18A 20A

Frequency 50.0Hz

Mode: ONLINE 0

↑ ↓ ← Esc

SYSTEM INPUT DATA 2/4

Vmains 225V 225V 224V

Frequency 50.0Hz

VinDC 48.8V

IinDC 60.0A

↑ ↓ ← Esc

INVERTER DATA 3/4

Vinv AC 221V 222V 221V

Frequency 50.0Hz

TIME (H:M D- M-Y)

23:59 31-01-2011

21
↑ ↓ ← Esc

OUTPUT POWER 4/4

P 18kW 16kW 18kW

S 21kVA 19kVA 21kVA

↑ ↓ ← Esc

The first page indicates: Voltage, current, frequency present, system mode
(online or offline) and alarms.
The second page indicates: AC voltage, frequency; DC voltage current;
The third home indicates: Inverter voltage, frequency and time.
The fourth home indicates: Active power, apparent power.

Click Esc to enter into main menu.

Inverter System

Alarm

System Setting

↑ ↓ ← Esc

Enter “inverter system” submenu, indications;

Inverter Status

Inverter Parameters

STS Parameters

UIB Parameters

Other Information

↑ ↓ ← Esc
22
“Inverter status” menu;

Inverter Status

NO. 01 -R SN: AC0001

Vout AC 220V

Iout AC 0A

Alarm: No Alarm

↑ ↓ ← Esc

Indicates the relevant status of module, phase sequence, serial number, output
voltage, current and alarm.
Click ESC to quit this page and return to inverter system menu.
“Inverter parameters” menu

Quantity 10

Hi V alm 270Vac

Lo V alm 170Vac

Hi F alm 53.0Hz

Lo F alm 47.0Hz

Bat HV Shut 58.0V

Bat LV Shut 44.0V

Bat Threshold 50.0V

↑ ↓ ← Esc

Quantity: Individual inverter numbers in system.


Hi V alm: While the output voltage is higher than the set value
the inverter will alarm.
Lo V alm: When the output voltage is lower than the set value the
inverter will alarm.
Hi F alm: When the output frequency is higher than the set value
the inverter will alarm.
Lo F alm: While the output frequency is lower than the value,
inverter will alarm.
Bat Vol Hi: When the DC voltage is higher than the set value the
inverter will shut down
23
Bat Vol Lo: When the DC voltage is lower than the set value the
inverter will shut down
Bat Threshold: When the voltage is below this setting the inverter is
shut down, if the battery voltage higher than this value,
the inverter module will restart again.
“STS parameters” menu

Mode: Online

Inv Hi V 270Vac

Inv Lo V 160Vac

Inv Hi F 53.0Hz

Inv Lo F 47.0Hz

Mains Hi V 270Vac

Mains Lo V 160Vac

Mains Hi F 53.0Hz

Mains Lo F 47.0Hz

Set Over Load Auto

Over LoadA 100A

Over LoadB 100A

Over LoadC 100A

Switch Delay 5mS

STS Test OFF

Phase failure ON

↑ ↓ ← Esc

Mode: Online or off line


Inv Hi V: If the inverter voltage is higher than this value, STS alarms and transfer
to AC mains.
Inv Lo V: If the inverter voltage is lower than this value, STS alarms and transfer to
AC mains.
Inv Hi F: If the inverter frequency is higher than this value, STS alarms and
transfer to AC mains.
Inv Lo F: If the inverter voltage is lower than this value, STS alarms and transfer to
AC mains.
Mains Hi V: If the mains voltage is higher than this value, STS alarms and transfer to

24
Inverter output.
Mains Lo V: If the mains voltage is lower than this value, STS alarms and transfer to
Inverter output.
Mains Hi F: If the mains frequency is higher than this value, STS alarms and transfer
to Inverter output.
Mains Lo F: If the mains voltage is lower than this value, STS alarms and transfer to
Inverter output;

Set over Load: Set overload current manually or automatically.


Over LoadX: If the output current is higher than this value, STS will alarm.
Switch Delay: The inverter output delay time is not synchronized with the AC
mains.
STS Test: STS transfer test for 10 seconds.
Phase Failure: If the value is “ON”, the STS alarms while any phase failure.

“UIB Parameters” Menu

Output Relay Def

Digital Input Def

↑ ↓ ← Esc

Output Relay Def: Define voltage free contacts


Digital Input Def: Definitions of digital input alarms

“Output Relay Def”Menu

Any Alm Spare

Inverter Fault Spare

Mains Alarm Spare

Over Load Spare

INV Output Spare

Byp Output Spare

System Fault Spare

DC V Fault Spare

↑ ↓ ← Esc

25
If the value set to “USED”, the relevant alarm has occurred and the relevant relay will
trip.

“Digital Input Def” Menu

Output Switch 1 0

Output Switch 2 0

Input Alm 3 0

Input Alm 4 0

Input Alm 5 0

Input Alm 6 0

Input Alm 7 0

Input Alm 8 0

↑ ↓ ← Esc

Input Alm X: 0 figures low voltage alarm; Short circuit the two pins of the terminal will
send the low voltage alarm.

“Oter Information” Menu

STS VER 2010AA

UIB VER 2030AB

SCU VER 2031AA

Batt Temp 23℃

Amb Temp 20℃

↑ ↓ ← Esc

STS VER: STS software version


UIB VER: UIB software version
CVC VER: CVC software version
Batt Temp: Battery Temperature
Amb Temp: Ambient Temperature

“Alarm” Menu

26
Alarm Log

Delete Log: OFF

↑ ↓ ← Esc

Delete Log: The report will be deleted permanently.

“System Setting” Menu

Controller Setting

User Logout

Time

Net Parameters

↑ ↓ ← Esc

User Logout: After password setting, click logout, Esc immediately and need password.

“Controller setting” Menu


System Addr 1
Three Phase ON
Mute OFF
Backlight 0M
Security OFF
Admin Password
User Password
Language En

↑ ↓ ← Esc

System Addr: System address, it is used in multi-system communication


Three Phase: For three system, it is “ON”
Mute: To mute the audible alarm when select ”ON”
Backlight: Back light will be shut down after the setting time, the unit is minute
Security: Use password protection please set it to “ON”. Only the screen becomes black or
menu “User Logout” is confirmed, the password protection starts to work.
Admin Password: Administrator password, default password: 2222.

27
User Password: User password, default password: 1111.
Language: The menu language

“Time and date” Menu


Year: 2011
Month: 1
Date: 1
Hour: 0
Minute: 0

↑ ↓ ← ESC

“Net parameters” Menu


IP: 192.168.1.123
Mask: 255.255.255.0
Gate: 192.168.1.1
Trap1: 192.168.1.124
Trap2: 192.168.1.125

↑ ↓ ← Esc

Sheet 5-1 Controller Alarm Report

Alarm Description Status


InvM Alarm Inverter alarms A/R
INV Comm Fail Inverter and CVC01 communication failed A/R
Maintenance System is in maintenance A
UIB Comm Fail UIB and CVC01 communication failed R
STS Comm Fail STS and CVC01 communication failed R
INV Phase F Inverter voltage lack one or two phases R
INV Fail Three phases have no voltage R
Mains Phase F Mains voltage lacks one or two phase R
Mains Fail Three phases have no voltage R
VInv High Inverter voltage is higher than set value A
VInv Low Inverter voltage is lower than set value A
FInv High Inverter frequency is higher than set value A
FInv Low Inverter frequency is lower than set value A
Vmains High Mains voltage is higher than set value A
Vmains Low Mains voltage is lower than set value A
28
Fmain High Mains frequency is higher than set value A
Fmain Low Mains frequency is lower than set value A
Syn Alarm Mains and inverter voltage not synchronization A
Over Load System current is higher than set value R
Temp High STS is over Temperature R
Short Circuit System output short circuit R
Fan Fail STS fans alarm A
Vbat High Battery voltage is higher than set value R
Vbat Low Battery voltage is lower than set value R
Sys Para Err System parameter error A

Caution

A: System non-urgent alarm


R: System urgent alarm
A/R: Fault or disconnection more than two times, it’s an urgent alarm or it’s
non-urgent alarm.

When system is in normal operation, the green light on door of the system is alight;
when system is in non-urgent alarm the green light will flicker (on/off each second);
when system is in urgent alarm, the light on door will flicker red (on/off each second);
when there is in fault without output, the red light will light up constantly.

The definition of module alarm


Vs Hi System voltage is high
Vs Lo System voltage is low
Soff Respond to controller to close inverter module
Vba F Battery voltage high or low alarm
Vbu F Bus voltage high or low alarm
Disp Inverter module leave its position
Add F Address test failure
No Ze No 0 phase signal
OvL1 Overload 100—125%
OvL2 Overload 125—150%
OvL3 Overload above 150%
Vin H Inverter voltage is high Alarm
Vin L Inverter voltage is low Alarm
Fin H Inverter frequency high
Fin L Inverter frequency low

29
Te1 H Heat sink 1 temperature is high
Te2 H Hear sink 2 temperature is high
Fan F Fan alarms

Caution

1. The upper limit of output current can be set according to total amount of
inverters connected in parallel. Caution: When actual output current exceeds
the upper limit value the system will be switched to AC bypass. Only when the
current is lower than 85% of output current will the system switch to inverter.

2. The definition of lower limit of battery voltage is: If DC input voltage (sensed
via the controller) is lower than the lower limit setting of battery voltage then
the inverter will be shut down. If DC input voltage recovers and rises up to the
value, the inverter will restart.
3. The old alarms will be displayed in alarm history. The first alarm after title is
the last alarm in system. A maximum of 500 alarms is stored in alarm history.
If there are more than 500 alarms the first alarms will be dropped.
4. If short circuit occurs in inverter mode, the system won’t be switched to AC
bypass. When the short circuit is removed, the system will be recovered.
5. The system is designed to have different audible alarms for different alarms.
Mains failure: A short tone will sound every 3 seconds.
System overload:A short tone will sound every 1 second.
DC under voltage: A short tone will sound every 1 second. (The sound will
alarm before 2 volts difference, for example, we set the
voltage to 44V, but the sound will alarm when DC
voltage decrease to 46V)
System failure: A long tone will sound.
6. All audible alarms can be set to mute in menu until new audible alarm occurs.
7. When the system is overloaded, it will transfer to the bypass line after 10
minutes
8. Refer to overload point setting in N+M redundant system, which is essential to
system reliability. The following formula is provided for reference.
I limit=N × k × I rated
I limit: Overload point in parallel redundant system
I rated: Rated output current for parallel inverter
N: (N+M) total amount of inverters designed to work in parallel
redundant system
M: (N+M) total amount of redundant inverters designed to work in
parallel redundant system
K: Parallel redundant coefficient, K equals 0.9.

30
Warning:

 System set “default parameter” when being out of factory, the details are
seen in chapters blow.

 Default “Set Over Load” setting is “Auto”, the system will set the overload
threshold automatically, if select “Manual”, please modify “Over Load”
accoring to the module numbers and capacity.

 Modify the present time to record history time.

5.4 UIB Test


UIB is installed on the front door of system, including eight digital signals input,
two analog variable inputs, two temperature probes, eight node signals.

Figure 5-1 UIB port

Digital input:
The user may input external alarm voltage-free contacts to controller through
digital input terminals.
Analog inputs:
From left to right, pin 1 for 12V, pin 2 for analog 1 input, pin 3 for analog 2 inputs,
and pin 4 for signal ground

TB: Battery temperature input, pin 1 for temperature transducer AD592+; pin 2
for temperature transducer AD592-, temperature sensor is optional.
TE:Ambient temperature input, pin 1 for temperature transducer AD592+; pin 2
for temperature transducer AD592-, temperature sensor is optional.

Voltage-free contacts output:


From left to right; Pin 1 is NO, pin 2 is COM, pin 3 is NC, the total relay quantity is
8 and ratings are 1A/30Vdc or 1A/125Vac.
While connect digital signal input terminals with short circuit the relevant alarm

31
signal could display in controller.
Voltage-free contacts test: Choose the relevant relay menu in “UIB setting” when
alarms occur the relay will close.

5.5 Communication Test

5.5.1. Ethernet outline

The system can be viewed via Ethernet which supports TCP/IP, UDP, SNMP or
HTTP. The users can access to the system through SNMP software or web browser.

5.5.2. Website setting

Figure 5-2 Connection figure


Setting steps (Windows XP operation system):
a. Click start on Windows and click setting, website connection and then local
connection;
b. Choose (TCP/IP) of Internet, click attribution;
c. The network parameters of CVC01 are as follows;

IP: 192.168.1.123
Mask: 255.255.255.0
Gate: 192.168.1.1
Trap1: 192.168.1.213
Trap2: 192.168.1.125

Set IP address, subnet mask code, default gateway and trap address on your PC to
match the network setting, please see above box. The computer’s network parameters
may be set as figure 5-3.

32
Figure 5-3

Caution

1. IP address of PC must be different with that of CVC01, but they can


connect only in same address district;
2. IP address of PC must be the same as at least one trap of CVC01, otherwise
it can’t work correctly.

5.5.3. Web Service

a. Input address 192.168.1.123 into explorer could display “identification


check” (User name: admin Password: admin)

Figure 5-4
b. When input correctly then the page display system status like the follows;

33
Figure 5-5

c. Click Sys Parameter to system parameter page;


d. Click Net Config to system parameter setting page, which can set new user
name, password, IP address, mask code, gateway, and trap of CVC01.

5.5.4. SNMP Application

a. Read the voltage-free contact


Open SNMP software and load the file of MIB (Supported by Nentron), it will
display CVC01 voltage-free contacts under PRIVATE, the CVC01 will connect the
relevant PCS system, click the right key and connection, then “Get”, the relevant
voltage-free contact will be read.
b. Trap Receive
When CVC01 occurs any alarm setting on CVC01.PCS, it could send one trap
message to the relevant IP address, if the trap address of CVC01 is right, PC will be in
trap.

34
Figure 5-6 SNMP node description

5.5.5. RS232 / RS485

Computer connects to RS232 or RS485 of inverter system, operate the controller


software and choose the relevant to connect.

5.5.6. USB

a. When CVC01 is operating correctly (home page displays), insert USB


communication cable, PC will indicate new hardware and to install drive program;

35
Figure 5-7

b. Click “Next” to install drive program, choose the access under CVC01 Software
Driver and click NEXT (as per figure below)

Figure 5-8
c. After installation, CVC01 will be reflected as a common port, users can use USB as
a common communication port, and other steps are the same as RS232.

36
Figure 5-9
5.6 System Operation

After parameter setting is completed, check following parameter again.


 Overload current value
 Operating mode
 Time and date
If the parameter setting above is correctly completed the load may be applied to
the system. The installation and commissioning is completed.

Caution

The inrush current is high or non-linear load.

 To avoid high inrush current caused by load the load should be applied in system
gradually.

 To avoid unnecessary transfer to bypass caused by inrush current the current


indicated on controller shouldn’t exceed 80% of setting value.
37
 Store user manual carefully, lock door and store keys securely.

5.7 Maintenance Switch Instructions

The inverter system is equipped with maintenance or manual bypass switch.


The operation of maintenance switch should be done as per procedure and by
qualified personnel otherwise serious damage may be caused by improper operation.

5.7.1 Replacement Controller and Static Switch process


1. Write down load data and parameter setting, when everything is functioning
properly in system;
2. Insert finger into the hole in the access panel of maintenance bypass switch
and push the panel up, the panel travel will be blocked by the travel switch
(part 6 in figure 4-5), push travel switch from NORMAL to BYPASS and push
up the panel completely, the STS will transfer to bypass after 1 seconds, The
BYPASS and MBS on STS light.
3. Turn transfer switch as shown in Figures 4-5 to “bypass maintenance” ;
4. The output current will indicate 0A on the controller and load is applied to
converter switch from inverter.
5. Power off all inverters;
6. Remove the controller and/or STS carefully;
7. Complete controller and/or static switch upgrade or replacement.
8. Controller and STS will start to operate then fasten with screw.
9. Controller starts to indicate AC voltage/frequency, bypass light open after
several seconds;
10. Restart all inverter modules and wait for normal operation of every module;
11. Turn transfer switch as shown in Figures 4-5 to “normal operation” from
“bypass maintenance”. The output current will be indicated on controller and
the system is working in bypass mode.
12. Check all the parameters, lower the panel to original position and return the
travel switch to NORMAL position, STS will transfer to inverter after two
seconds.
In this way, controller and static switch upgrading or replacement is completed
without cutting power to system.

5.7.2 The use of maintenance switch


Under the condition of system fault, please maintain and recover as follow steps:
1.When power is cut off by a system failure already, power off all inverters and
turn transfer switch as shown in Figures 4-5 to “bypass maintenance” from
“normal operation” immediately. The load recover to supply power;
2.Write down parameter setting on controller;
3.Follow steps from 5.7.1 then replace inverter, controller or static switch
according to inspection result.
38
Danger:

 It is hazardous during operation described above. The operation should be done


only by trained and qualified maintenance personnel.

 Ensure good insulation between human body and hand tools.

5.8 System Shut Down

1. Backup all data in computer;


2. Remove all loads gradually;
3. Turn off all switches in inverter system;
4. Turn off bypass input breakers and DC input breakers;
5. Test inverter system with voltmeter and no voltage.
The system shut down is completed.

6. DEFAULT VALUE

System parameter setting

NO Description Setting Remark


1 Start 3 phase mains User requirement
2 alarm Open
3 Return to default page 2m
4 Password setting Off
5 Administrator password 0000
7 User password 0000
8 Language User requirement
9 Time The present time

Website parameter setting

NO Description Setting Remark


1 IP 192.128.1.123
2 Mask code 255.255.255.0
3 Gateway 192.128.1.1
4 Trap 1 192.128.1.124
5 Trap 2 192.128.1.125

39
UIB parameter setting

NO Description Setting Remark


1 Any alarm Spare
2 Inverter fails Spare
3 Mains alarm Spare
4 Overload Spare
5 Inverter output Spare
6 Mains output Spare
7 Output fails Spare
8 Battery voltage alarm Spare

CST Parameter setting


NO Description Setting Remark
1 Inverter mode User requirement
2 Upper limit of inverter voltage 270V
3 Lower limit of inverter voltage 160V
4 Upper limit of inverter frequency 52.5Hz
5 lower limit of inverter frequency 47.5Hz
6 Upper limit of mains voltage 270V
7 Lower limit of mains voltage 160V
8 Upper limit of mains frequency 51Hz
9 Lower limit of mains frequency 49Hz
10 Set overload current Automatic
11 Overload current Automatic
12 Transfer delay 0
13 SSMS Test Off

Inverter parameter setting


NO Description Setting Remark
1 Setting system
2 Inverter voltage over high 270V
3 Inverter voltage over low 160V
4 Inverter frequency over high 52.5Hz
5 Inverter frequency over low 47.5Hz
6 Upper limit of battery voltage 58.0V
7 Lower limit of battery voltage 44.0V
8 Battery low recovery 50.0V

7. REPLACEMENT and MAINTENANCE

7.1 Inverter Module Replacement

40
1. Write down inverter failure information;
2. Remove screws that secure front panel of inverter;
3. Turn off inverter switch on front panel and corresponding DC input switch inside
rack;
4. Gently slide inverter out of rack;
5. Insert new inverter ensuring connection to rear terminal and fix with screws;
6. Turn on DC input switch and inverter switch on front panel. The new inverter
starts to work in few seconds;
7. Pack the failed inverter in original shipping package and return for service
(attach failure information).
The inverter replacement is completed.

7.2 Controller Replacement


1. Record failure information and controller parameters;
2. Remove the fix screw on controller;
3. Fasten handle and put the module out lightly;
4. Insert the new controller module tightly and fasten screws.
5. Enter into each menu and check that the parameters are correct.
6. Pack the faulty module into original crate and return to test.
7. Replacement is over

7.3 Static Switch Replacement


The static switch replacement is done using the maintenance switch. See 5.7
Maintenance Switch Instructions.

7.4 General Maintenance


Since the system is used to power critical equipment general maintenance is
essential for system reliability.

7.4.1 Daily Maintenance


Check and analysis alarm history for potential risks:
Check for unusual fluctuations in load and analysis reasons;
Check for load current. If it exceeds 80% of upper limit of output current, consider
inverter addition or reduce loads;
Check battery status and ensure that the battery is in good condition;
Check for alarms such as “low inverter voltage”, “low DC voltage” and “load short
circuit”. If there is an alarm like that, inspect carefully and contact our technical staff
for advice if necessary;
Check that the rectifier system meets power requirements of the inverter system
and battery.

7.4.2 Battery Maintenance


The battery is an important power source in system particularly during mains

41
failed condition and its status may have direct influence on power quality. Therefore,
battery maintenance including battery discharge test should be performed every 6
months.

8. TROUBLESHOOTING

If system fails to operate properly after installation and a thorough re-examination


shows the system to be correct, use following troubleshooting table to determine
probable causes and solutions to resolve error conditions.

Sheet 8-1 Troubleshooting for Inverter System

Error Condition Problem Cause Recommendation

Green light flick Communication is not normal Check cable connection

Yellow light flicker Alarm Check alarm through CVC01

Check address setting of


Red light flicker quickly Module address in abnormal
inverter module’s rear panel

Red light in long time Fault Check the reason of shut down

Remove the controller and


Controller Screen halted Immunity of LED
insert again after 3 seconds.

The short circuit is The impulse current of


indicated on controller. nonlinear load is too high,
Avoid impulse current one time
No short circuit is in which caused short circuit
system. protection.

The mains failure. The battery


discharge voltage is low. The Avoid high inrush current at the
The DC voltage low is voltage falls sharply when same time.
indicated on controller battery has impact load. The Check whether rectifier system
power capacity of rectifier and battery is working properly.
system is not enough.

Controller parameter Parameter password


Contact operator
can’t be modified protection

42
9.TECHNICAL DATA

Technical data is shown in table 9-1 to table 9-3.

Table 9-1 Inverter Module Technical Data

Model Number CPI3K


Nominal Capacity 3000VA/3000W
DC Input Voltage -48Vdc(40 to 60Vdc), 110Vdc(90 to
140Vdc) or 220Vdc(180 to 280Vdc)
Reflected relative
psophometric noise ≤1%
Current
Reflected Relative Wide ≤10%
Band Noise Current
AC Output Voltage 120/220Vac ±2%
120Vac suits 110, 115, 120 and 127Vac
220Vac suits 208, 220, 230 and 240Vac
Frequency 50Hz ±0.03%
Waveform Pure sine wave
Nominal Output Current 13.5A/13.5A
Total Harmonic Distortion 2%(resistive load)
Transient Response ≤4ms
Efficiency ≥90%
Crest Factor 3:1
Parallel Total Amount Max 42pcs
ability Current Unbalance ≤±5%
Audible Noise ≤55dB(A)

43
Protection  Input: high/low voltage shut down;
reserve polarity protection.
 Short circuit: current limitation
automatically and recover after
resolution.
 Overload: 100 to 125% overload
supports 10 minutes, 126 to 150%
overload supports 10 seconds, 150%
above overload supports 2 seconds.
 Over Temperature:
When inverter internal temperature rises
over 90C it will be disconnected from the
system. When temperature returns to
normal the inverter will reconnect to the
system.
 Intelligent fan speed control
Panel indication LED indicate inverter status
Safe standard IEC60950
EMC CISPR22 classB
Humidity IEC61000
Environment Temperature -5 to 50C
Humidity <90%, non-condensing
Dimension(mm) 221W×355D×88H
Weight(kg) 5.2

Table 9-2 Static Switch Technical Data

Model CST63K
Nominal Capacity 100A×3
Operating voltage 40 to 60Vdc
Or 90 to 300Vac
Transfer Time Controlled transfer 0 ms
abnormal transfer 4 ms
Noise ≤50(dBA)

44
Protection  Input protection of reverse
connection
 Overload: 100 to 125% overload
supports 10 minutes , 126 to 150%
overload supports 10 seconds ,
150% above overload supports 2
seconds.
 Over Temperature: The temperature
of heat sink is over 90C, alarm will
appear.
 Intelligent fan speed control
Panel indication LED indicate work status
Safe standard IEC60950
EMC CISPR22 classB
Immunity IEC61000
Environment Temperature -5 to 50℃
Humidity <90%, non condensing
Dimension(mm) 482.6W×340D×132H
Weight(kg) 13

Table 9-3 CVC01 Controller Technical Data

DC Input Voltage -48V (40 to 60Vdc)


Alarm history 500 Items
Menu Chinese/English/Spanish/Portuguese
Communication Port RS232/USB /SNMP/HTTP
Temperature -5 to 50C
Environment
Humidity <90%,non-condensing
Dimension(mm) 482.6W×150D×88H
Weight(kg) 2.3

45
1 2 3 4 5 6 7 8

9 10
5 6
1 2
1@MAINS 27@STS POWER CON 5@OUT SW
1 2 BYP LC 2@MBS11 12 1 2
P7 BPYC OUTC P9
3 4 BYP LB 7 8 3 4
P4 BPYB OUTB P6
5 6 BYP LA 3 4 5 6
P1 BPYA OUTA P3
D D
P2 P5 P8 13 14 1 2 43@LOCK SW 1 2
22@BYP PE 9@INV PE INVA INVB INVC 6@OUT PE
PE
Appendix 1

1 2

23@BYP N 10@INV N 7@OUT N 1 2


N
N
3 1 2

MO C
WO DN IW
MO C
4 8 V+

NO IT AT S W S
1
40@AUX POWERX 7 2
To S TS B PA X 6 G ND B X3 L
2 1

1
2
2
1
1 2
X5 X2 X4
4 8 V+
1

1
2
1
2
1
2
To S CU BP AX 5 G ND B X8 X5
2 X1
1 2
X4 CAN B YP L
5 X7 M-S FA U LT
1
L X2 N
4
X1 2
11@DC+ X7 DC+ 3
3
C OM
B AT + 24@CT 2

8@INVLA
BAT+

41@INVLB
42@INVLC
28@1#CPI3K N X1 1
CT 1 2
X6 DC-
38@DC- PE X3 26@STS BPA
B AT - 1 2 3 4 12@1#SW X5 CAN
BAT- GND B S -MFA U LT
1 1
48 + X9 X2 C OM
2 2
To A U X PO W E R
X4 CAN X2
C X4 C
X14 X1 L X2
GND B
1 1
+1 2V X7 DC+
-12V
2 2 29@2#CPI3K N X1
48 + IOU T X6 X3
CVT system Diagram

3 3
GND 1 2
4 X6 DC-
X3
PE X3
B AT + 13@2#SW X5 CAN X3
1 48 5A
1
2 X2 48 5B
B AT - X2 2
3 X29
1
X4 CAN
48 + X 0 48 V+
3@UIB 2 L X2 X1 X5
1
3 X7 DC+ 2 To A U X PO W E R X 1

46
GND B
GND 3
1 30@3#CPI3K N X1
IO1 X1
2 X9
1 2
39@DOOR-LED X6 DC- 25@CVC01 BPA
X10 14@3#SW PE X3 1 X4
X11
X5 CAN 2
X12 + Amb ien t 3 X1 WEB
8 I/O 1
X13 X5 - Temperature 4
2
X16 5
X17 6
X6 1
+ B attery 15@4#SW 31@4#CPI3K 7
CVC01
-
GND
1
X19 2 Temperature 16@5#SW 32@5#CPI3K 8
IO8 9
2 17@6#SW 33@6#CPI3K 10
18@7#SW 34@7#CPI3K C N4
USB
NO X6
B
C OM
1 19@8#SW 35@8#CPI3K B
2 1
NC
3
20@9#SW 36@9#CPI3K 2
X21
3

Three phase CVT system diagram


4
X24 X7
X25
X4 CAN
1
2
3
4

X20
X26 L X2
X27 X7 DC+
NO
1
C OM
2
X28 37@10#CPI3KN X1
NC 1 2
3 X6 DC-
1
2
3
4

C N1
PE X3
21@10#SW X5 CAN
C N2 R S23 2 OR RS 485
44@RS232
X4 CAN
L X2
X7 DC+
47@11#CPI3K N X1
1 2
X6 DC-
45@11#SW PE X3
X5 CAN

X4 CAN
A L X2 A
X7 DC+
48@12#CPI3K N X1 Title
1 2
X6 DC- CVT Sy stem Diagram
46@12#SW PE X3
X5 CAN Size N u mb er R ev is io n
A2 V1.0
D ate: 1 7 -F eb -2 0 1 2 Sh eet o f
File: E:\Diag ram\C V M (T ) D iag ram. Dd b D raw n B y :

1 2 3 4 5 6 7 8
Appendix 2 CVT System Test sheet
CVT System Test Sheet
Serial No: Date:
Test Result: Inspector:
Test
Item Requirement
Result
Structure

Product Marking
No visual color difference, stain,
Exterior Galvanization
scratch and/or abrasion
Painting

AC Input/ Output to Shelf


Insulation
DC Input to Shelf >2 MΩ
Resistance
AC Input to AC Output
Signal Control Circuit to 1min, no cut through
710Vdc
Shelf and electric arc,
Insulation
AC Input/ Output to Shelf 2200Vdc leakage current
Intensity
DC Input to AC Input/ ≤20mA
2200Vdc
Output
Nominal Voltage 220(380)±3Vac
AC Output
Voltage Regulation ≤±2%

AC Output Voltage Relative Harmonic ≤3%

Frequency Variation 50/60 ±0.3Hz


Electric
Perform Start Performance 5 continuous normal starts
ance Overload Capability and Over Current 1.25×I nom > 10minutes and
Protection protection
Audible and light alarms Displays and sounds
Load Sharing ≤±5%
Remote measure AC output voltage,
Remote Measure and Communication current, frequency, DC input voltage and
system status
Exceeds setting of output voltage
Output Over Voltage Protection
and protection
Protection in real time and recovery
Short Circuit Protection
after short circuit is removed
100% unbalance load for three phase
Normal working
system
Maintenance bypass test Transfer to bypass to maintain
Battery Under Voltage Test Inverter shut down and recovers

47

You might also like