This is to inform you that test certificates for protective relays and measuring and
metering Instruments should be submitted from EETC Central Protection Sector.
(G-2):
in (G-2) for Metering instruments and Protection System you didn’t Fill-in the Data for
(Name of Manufacturer, Place of Manufacturer, Place of Testing, Standard), please Fill-in the
Guarantee Schedules (G-2) and send it for evaluation .
Incoming Feeders:
2- Please confirm to provide the number of (DO) to be (16) instead of (10) as per
EETC Guarantee Schedules (G-7a) ,item (1.1.11).
3- Please confirm that Original Software and firmware for the relay should be
provided in all relays.
Outgoing Feeders:
1- This is to inform you that the relay type (REF 611) is not accepted as it doesn’t
complete the field test period according to the (table-item 5) as per EETC specs,
Section (3), item (3.7.1), Page (6/8).
3- Please confirm to provide the number of (DI) to be (16) instead of (4) as per
EETC Guarantee Schedules (G-7a), item (2.1.12).
4- Please confirm to provide the number of (DO) to be (16) instead of (6) as per
EETC Guarantee Schedules (G-7a), item (2.1.13).
6- Please confirm that Original Software and firmware for the relay should be
provided in all relays.
Bus-Ties:
1- Please confirm that Original Software and firmware for the relay should be
provided in all relays.
Load Shedding:
Page 1
EETC Comments for Protection Project Sector on ABB offer for the 11 KV Distribution Feeders
2- Please Follow EETC Guarantee Schedules (G-7a) Specs For the Following:
Operating Time.
Temperature.
Humidity.
Operating frequency.
3- Please confirm that Original Software and firmware for the relay should be
provided in all relays.
Please submit the EETC Central Protection Sector- ROD EL-FARAG- test certificates
for the measuring and metering instruments (MICROSTAR-bluestar, type-A2000) for
evaluation or it will be omitted from your offer.