CYMCAP Version 8.1 Revision 2


Study: Ampacity Calculation
Execution: Ampacity Calculation for Case # 05
Date: 9/6/2023 2:52:01 PM

General Simulation Data


Steady State Option
Consider Electrical interaction between circuits

Induced currents in metallic layers as a fraction of conductor current (applied to all single phase circuits) :

Conductor Resistances Computation Option:

Standard Settings Options


General guidance
Factor on RAC due to magnetic armour
Factor on RAC due to magnetic duct
Factor on ƛ₁ due to magnetic armour
Factor on ƛ₁ due to magnetic duct
Factor on ƛ₂ due to ƛ'₁
ƛ''₁ computation
ƛ₂pipe computation
Wd computation
T₂ computation
T₄ computation

Installation Type:Multiple Ductbanks/Backfills


Ambient Soil Temperature at Installation Depth
Native Soil Thermal Resistivity
Consider Non-Isothermal Earth Surface

Layer Name X [m] Y [m] Width [m]

Backfill 0.0 0.7 2.5


Results Summary
Cable No. Cable ID Circuit No. Feeder ID Cable Phase

1 1200-132KV-SEC-OPTIMIZED 1 A
2 1200-132KV-SEC-OPTIMIZED 1 B
3 1200-132KV-SEC-OPTIMIZED 1 C
4 1200-132KV-SEC-OPTIMIZED 2 A
5 1200-132KV-SEC-OPTIMIZED 2 B
6 1200-132KV-SEC-OPTIMIZED 2 C
Study Summary

Equally Loaded
No

circuits) : 0.0

IEC-228

Custom
CIGREGuidance
CIGREGuidance
CYMCAPGuidance
CIGREGuidance
CYMCAPGuidance
CIGREGuidance
CYMCAPGuidance
CIGREGuidance
CIGREGuidance
CYMCAPGuidance

[°C] 40.0
[K.m/W] 2.79
No

Thermal Resistivity
Height [m]
[K.m/W]

1.4 1.2
X coordinate Y coordinate Conductor
Cable Frequency Daily Load Factor
[m] [m] temperature [°C]

60.0 1.0 -1.15 1.2 87.9


60.0 1.0 -0.75 1.2 90.0
60.0 1.0 -0.35 1.2 89.6
60.0 1.0 0.35 1.2 89.6
60.0 1.0 0.75 1.2 90.0
60.0 1.0 1.15 1.2 87.8
Equally Loaded
No

0.0

IEC-228

Custom
CIGREGuidance
CIGREGuidance
CYMCAPGuidance
CIGREGuidance
CYMCAPGuidance
CIGREGuidance
CYMCAPGuidance
CIGREGuidance
CIGREGuidance
CYMCAPGuidance

40.0
2.79
No
Ampacity [A]

850.4
850.4
850.4
850.4
850.4
850.4
CYMCAP Version 8.1 Revision 2
Study: Ampacity Calculation
Execution: Ampacity Calculation for Case # 05
Date: 9/6/2023 2:52:01 PM

Simulation Data
Installation type: Multiple Ductbanks
Steady State Option Equally Loaded
Ambient temperature [°C] 40
Native Soil Thermal Resistivity [K.m/W] 2.79
Consider Non-Isothermal Earth Surface No
Consider effect of soil dry out No
Consider Electrical interaction between circuits No
Induced current in metallic layers as a fraction of conductor current (applied to all single phase
0
circuits)

Variable Description Unit


Cable No. Cable Index Number
General Input Data
Cable ID Cable Equipment ID
Circuit No. Circuit No.
Phase Cable Phase
Fq Operating Frequency [Hz]
x X coordinate [m]
y Y coordinate [m]
DLF Daily Load Factor [p.u.]
Bonding Type
Ampacity
I Steady State Ampacity [A]
Temperatures
θc Conductor temperature [°C]
θs Sheath/Shield temperature [°C]
θa Armour temperature [°C]
θsurf Cable surface temperature [°C]
θduct Duct surface temperature [°C]
Resistances
R₀ DC Resistance of the conductor at 20°C [Ω/km]
R AC Resistance of the Conductor at Operating Temperature [Ω/km]
ys Skin Effect Factor
yp Proximity Effect Factor
Losses
Wc Conductor Losses [W/m]
Wd Dielectric Losses [W/m]
Ws Metallic Screen Losses [W/m]
Wa Armor/Pipe Losses [W/m]
Wt Total Losses [W/m]
ƛ₁ Screen Loss Factor
ƛ₂ Armour Loss Factor + Pipe Loss Factor
Thermal resistances
T1 Thermal resistance of insulation [K.m/W]
T2 Thermal resistance of bedding/medium inside pipe-type [K.m/W]
T3 Thermal resistance of outer covering [K.m/W]
T4 External thermal resistance [K.m/W]
Others
Δθint Temperature rise due to surrounding heat sources [°C]
Induced Voltage (standing) on Concentric Wires [V/km]
Induced current on Metallic Screen [A]
Steady State Summary

n
n for Case # 05
M

ultiple Ductbanks
ually Loaded

79
o
o
o

Cables
1 2 3

1200-132KV-SEC-OPTIMIZED 1200-132KV-SEC-OPTIMIZED 1200-132KV-SEC-OPTIMIZED


1 1 1
A B C
60.0 60.0 60.0
-1.15 -0.75 -0.35
1.2 1.2 1.2
1.0 1.0 1.0
1 Conductor Crossbonded Flat 1 Conductor Crossbonded Flat 1 Conductor Crossbonded Flat

850.4 850.4 850.4

87.9 90.0 89.6


81.6 83.7 83.3
n/a n/a n/a
80.7 82.8 82.4
n/a n/a n/a

0.0151 0.0151 0.0151


0.02256 0.02267 0.02265
0.1777 0.17572 0.17611
0.0019 0.00188 0.00189
16.3167 16.39591 16.3801
0.52954 0.52954 0.52954
0.23265 0.18672 0.1824
0.0 0.0 0.0
17.07889 17.11217 17.09205
0.01426 0.01139 0.01114
0.0 0.0 0.0

0.37705 0.37705 0.37705


0.0 0.0 0.0
0.0533 0.0533 0.0533
2.38426 2.50154 2.48024

23.2 27.2 27.3


0.0 0.0 0.0
52.2 46.6 46.1
Summary

Cables
4 5 6

1200-132KV-SEC-OPTIMIZED 1200-132KV-SEC-OPTIMIZED 1200-132KV-SEC-OPTIMIZED


2 2 2
A B C
60.0 60.0 60.0
0.35 0.75 1.15
1.2 1.2 1.2
1.0 1.0 1.0
1 Conductor Crossbonded Flat 1 Conductor Crossbonded Flat 1 Conductor Crossbonded Flat

850.4 850.4 850.4

89.6 90.0 87.8


83.3 83.7 81.6
n/a n/a n/a
82.4 82.8 80.7
n/a n/a n/a

0.0151 0.0151 0.0151


0.02265 0.02267 0.02256
0.17609 0.17573 0.17778
0.00189 0.00188 0.0019
16.38107 16.3956 16.31384
0.52954 0.52954 0.52954
0.23358 0.18672 0.1818
0.0 0.0 0.0
17.14419 17.11185 17.02517
0.01426 0.01139 0.01114
0.0 0.0 0.0

0.37705 0.37705 0.37705


0.0 0.0 0.0
0.0533 0.0533 0.0533
2.47401 2.50119 2.38777

27.3 27.1 23.2


0.0 0.0 0.0
52.2 46.6 46.2
Electrical
CYMCAP Version 8.1 Revision 2
Study: Ampacity Calculation
Execution: Ampacity Calculation for Case # 05
Date: 9/6/2023 2:52:01 PM

No. Description Unit Cable No.1


1 Cable Equipment ID 1200-132KV-SEC-OPTIMIZED
Resistances
DC Resistance of the conductor at 20°C

2 [Ω/km] 0.0151

DC Resistance of Conductor at Operating Temperature

3 [Ω/km] 0.01913

4 AC Resistance of Conductor at 20°C [Ω/km] 0.01912


AC Resistance of Conductor at Operating Temperature

5 [Ω/km] 0.02256

6 DC Resistance of Concentric Wires at 20°C [Ω/km] 0.06868


DC Resistance of Concentric Wires at Operating Temperature

7 [Ω/km] 0.08532

Losses
Conductor Losses

8 [W/m] 16.3167

Dielectric Losses

9 [W/m] 0.52954

Metallic Screen Losses

10 [W/m] 0.23265
10 [W/m] 0.23265

Armor/Pipe Losses

11 [W/m] 0.0

Total Losses

12 [W/m] 17.07889

Capacitance, Inductance, Impedance


Capacitance

13 [µF/km] 0.242

Inductance of Conductor

14 [mH/km] 0.63283

Reactance of Conductor

15 [Ω/km] 0.23857

Inductance of Metallic Sheath

16 [mH/km] 0.44255

Reactance of Metallic Sheath

17 [Ω/km] 0.16684

Positive Sequence Impedance

0.022564 +
18 [Ω/km]
j0.238571
Negative Sequence Impedance

0.022564 +
19 [Ω/km]
j0.238571

Zero Sequence Impedance

0.086463 +
20 [Ω/km]
j0.166837

Surge Impedance

21 [Ω] 51.15335

Others
Dielectric Stress at Insulation Inner Surface

22 [kV/mm] 5.72001

23 Dielectric Stress at Insulation Outer Surface [kV/mm] 3.22098


Insulation Resistance at 60°F (15.8°C)

24 [㏁.km] 1520.39871

Reduction Factor (2pt bonded & single metallic screen)

25 n/a

Charging Current for One Cable (Phase)

26 [A/km] 6.94838

Charging Capacity of three phase system at Uo

27 [kvar/km] 1588.61355

Voltage drop for Three Phase System

28 [V/A/km] 0.03908
28 [V/A/km] 0.03908

29 Induced Voltage (standing) on Concentric Wires [V/km] 0.0


Induced current on Metallic Screen

30 [A] 52.2
Electrical Parameters

Cable No.2 Cable No.3 Cable No.4 Cable No.5 Cable No.6
1200-132KV-SEC-OPTIMIZED
1200-132KV-SEC-OPTIMIZED
1200-132KV-SEC-OPTIMIZED
1200-132KV-SEC-OPTIMIZED
1200-132KV-SEC-OPTIMIZED

0.0151 0.0151 0.0151 0.0151 0.0151

0.01925 0.01923 0.01923 0.01925 0.01912

0.01912 0.01912 0.01912 0.01912 0.01912

0.02267 0.02265 0.02265 0.02267 0.02256

0.06868 0.06868 0.06868 0.06868 0.06868

0.08588 0.08577 0.08577 0.08588 0.0853

16.39591 16.3801 16.38107 16.3956 16.31384

0.52954 0.52954 0.52954 0.52954 0.52954

0.18672 0.1824 0.23358 0.18672 0.1818


0.18672 0.1824 0.23358 0.18672 0.1818

0.0 0.0 0.0 0.0 0.0

17.11217 17.09205 17.14419 17.11185 17.02517

0.242 0.242 0.242 0.242 0.242

0.63283 0.63283 0.63283 0.63283 0.63283

0.23857 0.23857 0.23857 0.23857 0.23857

0.44255 0.44255 0.44255 0.44255 0.44255

0.16684 0.16684 0.16684 0.16684 0.16684

0.022674 + 0.022652 + 0.022653 + 0.022673 + 0.022560 +


j0.238571 j0.238571 j0.238571 j0.238571 j0.238571
0.022674 + 0.022652 + 0.022653 + 0.022673 + 0.022560 +
j0.238571 j0.238571 j0.238571 j0.238571 j0.238571

0.086433 + 0.086439 + 0.086438 + 0.086433 + 0.086464 +


j0.166837 j0.166837 j0.166837 j0.166837 j0.166837

51.15335 51.15335 51.15335 51.15335 51.15335

5.72001 5.72001 5.72001 5.72001 5.72001

3.22098 3.22098 3.22098 3.22098 3.22098

1520.39871 1520.39871 1520.39871 1520.39871 1520.39871

n/a n/a n/a n/a n/a

6.94838 6.94838 6.94838 6.94838 6.94838

1588.61355 1588.61355 1588.61355 1588.61355 1588.61355

0.03927 0.03923 0.03924 0.03927 0.03908


0.03927 0.03923 0.03924 0.03927 0.03908

0.0 0.0 0.0 0.0 0.0

46.6 46.1 52.2 46.6 46.2


CYMCAP Version
Study:
Execution:
Date:

No. Symbol
1
Normal Operation IEC 60287-1-1
Conductor AC Resistance

2 R₀

3 R'

4 dc
5 s
6 ks
7 kp

8 Xs²

9 Xp²

10 ys

11 yp
11 yp

12 R

Dielectric Losses
13 tanδ
14 ε

15 C

16 U₀

17 Wd

Circulating Loss Factor


18 Rs
19 d

20 X

21 Xm

22 P

23 Q
23 Q

24 Fspacing

25 ƛ'₁

Eddy Loss Factor

26 ƛ''₁

Metallic Screen Loss factor

27 ƛ₁

Armour and Pipe Loss Factor

28 ƛ₂a

29 ƛ₂pipe
29 ƛ₂pipe

30 ƛ₂

Normal Operation IEC 60287-2-1

32 T₁

33 t₁
34 ρTi

35 T₃

36 t₃
37 ρTJ
38

39 T
Conductor
Shield
40
41
42
43

44
T
Insulation

45
46
47
48

T
Insulation
Screen
49 T
Insulation
Screen
50
51
52
53

54
T
Concentric wires

55
56
57
58

59
T
Jacket

60
61
62
Thermal resistance of the external medium
63 L
64 De

65 u

66 ρTs

67 T₄'''self

68 T₄'''mutual
68 T₄'''mutual

69 Δθint

70 T₄'''

Thermal Capacitance IEC 853-2


71

72 Q
Conductor

73
74
75

76 Q
Conductor
Shield
77
78
79
80

81
Q1
Insulation
82
83
84
85

86
Q2
Insulation
87
Q2
Insulation

88
89
90

91 Q
Insulation
Screen
92
93
94
95

96

97 Q
98 Concentric wires
99
100
101
102

103
Q
Jacket

104
105
106
Ampacity

107 T₄

108 I
8.1 Revision 2
Ampacity Calculation
Ampacity Calculation for Case # 05
9/6/2023 2:52:01 PM

Description
Cable Equipment ID
ion IEC 60287-1-1
Resistance
DC Resistance of the conductor at 20°C

DC Resistance of Conductor at Operating Temperature

Conductor Diameter
Distance Between Conductor Axes
Factor Used for xs Calculation (Skin Effect)
Factor Used for xp Calculation (Proximity Effect)
Component of Ys Calculation (Skin Effect)

Component of Yp Calculation (Proximity Effect)

Skin Effect Factor

Proximity Effect Factor


AC Resistance of Conductor at Operating Temperature

s
Dielectric Loss Factor
Insulation Relative Permitivity
Cable Capacitance

Voltage
Cable Dielectric Losses Per Phase

s Factor
AC Resistance used for Circulating Loss Factor computation
Mean diameter used for Circulating Loss Factor computation
Reactance used for Circulating Loss Factor computation

Mutual Reactance

Component for Circulating Loss Factor Formula (Clause 2.3.3)

Component for Circulating Loss Factor Formula (Clause 2.3.3)


Spacing Factor (applied when spacing between cable uneven or non-equal minor section length)

Screen Loss Factor Caused by Circulating Current

or
Screen Loss Factor Caused by Eddy Current

Loss factor
Screen Loss Factor

pe Loss Factor
Armour Loss Factor

Pipe Loss Factor


Armour Loss Factor + Pipe Loss Factor

ion IEC 60287-2-1


Thermal Resistance Between Conductor and Screen

Insulation Thickness Between Conductor and Screen


Thermal Resistivity of Insulation
Thermal Resistance of Jacket/Pipe Coating

Thickness of Jacket/Pipe Coating


Thermal Resistivity of Jacket/Pipe Coating
Thermal resistance

Thermal resistance equation

Thermal resistivity
Layer thickness
Internal diameter
Thermal resistance

Thermal resistance equation

Thermal resistivity
Layer thickness
Internal diameter
Thermal resistance
Thermal resistance equation

Thermal resistivity
Layer thickness
Internal diameter
Thermal resistance

Thermal resistance equation

Thermal resistivity
Layer thickness
Internal diameter
Thermal resistance

Thermal resistance equation

Thermal resistivity
Layer thickness
Internal diameter
nce of the external medium
Depth of cable/conduit axis
External diameter of the cable conduit
Geometric factor as per IEC60287-2-1 clause 4.2.2

Thermal resistivity of the soil


Thermal resistance of the cable isolated

Thermal resistance associated to the temperature rise due to surrounding heat sources
Temperature rise due to surrounding heat sources

Thermal resistance of the external medium

itance IEC 853-2


Thermal capacitance

Thermal capacitance equation

Material surface
Volumetric specific heat of the material
Thermal capacitance

Thermal capacitance equation

External diameter
Internal diameter
Volumetric specific heat of the material
Thermal capacitance

Thermal capacitance equation

External diameter
Internal diameter
Volumetric specific heat of the material
Thermal capacitance

Thermal capacitance equation

External diameter
Internal diameter
Volumetric specific heat of the material
Thermal capacitance

Thermal capacitance equation

External diameter
Internal diameter
Volumetric specific heat of the material
Thermal capacitance

Thermal capacitance equation

Number of armour wires


Mean diameter of armour wire
Length of lay
Mean diameter of armour
Wire Shape is half-circle
Thermal capacitance

Thermal capacitance equation

External diameter
Internal diameter
Volumetric specific heat of the material

Total external thermal resistance

Cable core ampacity


Cable Parameters under Norm

Unit Cable No.1


1200-132KV-SEC-OPTIMIZED

[Ω/km] 0.0151

[Ω/km] 0.01913

[mm] 43.4
[mm] 400.0
0.8
0.37

6.30663

2.91682

0.1777

0.0019
0.0019

[Ω/km] 0.02256

0.001
2.5

[µF/km] 0.242

[kV] 76.21024

[W/m] 0.52954

[Ω/km] 0.08532
[mm] 87.52

[Ω/km] 0.16684

[Ω/km] 0.05226

[Ω/km] 0.2191

[Ω/km] 0.14942
[Ω/km] 0.14942

0.004

0.01426

0.0

0.01426

0.0

0.0
0.0

0.0

[K.m/W] 0.37705

[mm] 21.0
[K.m/W] 3.5

[K.m/W] 0.0533

[mm] 4.5
[K.m/W] 3.5
[K.m/W] 0.03723

[K.m/W] 3.5
[mm] 1.5
[mm] 43.4
[K.m/W] 0.3199

[K.m/W] 3.5
[mm] 18.0
[mm] 46.4
[K.m/W] 0.01992
[K.m/W] 3.5
[mm] 1.5
[mm] 82.4
[K.m/W] 0.0

[K.m/W] 0.0
[mm] 2.12
[mm] 85.4
[K.m/W] 0.0533

[K.m/W] 3.5
[mm] 4.5
[mm] 89.64

[m] 1.2
[m] 0.09864

24.3309

[K.m/W] 1.66184

[K.m/W] 1.0274

[K.m/W] 1.35686
[K.m/W] 1.35686

[°C] 23.17361

[K.m/W] 2.38426

[J/m.K] 4140.0

[mm²] 1200.0
[J/(K*m³)] 3450000.0
[J/m.K] 507.80693

[mm] 46.4
[mm] 43.4
[J/(K*m³)] 2400000.0
[J/m.K] 3148.62983

[mm] 82.4
[mm] 46.4
[J/(K*m³)] 2400000.0
[J/m.K] 5591.53236

[mm] 82.4
[mm] 46.4
[J/(K*m³)] 2400000.0
[J/m.K] 948.88665

[mm] 85.4
[mm] 82.4
[J/(K*m³)] 2400000.0
[J/m.K] 260.67223

74.0
[mm] 2.12
[mm] 956.0
[mm] 87.52
0.0
[J/m.K] 3194.0953

[mm] 98.64
[mm] 89.64
[J/(K*m³)] 2400000.0

[K.m/W] 2.38426

[A] 850.36557
Cable Parameters under Normal Operation

Cable No.2 Cable No.3


1200-132KV-SEC-OPTIMIZED 1200-132KV-SEC-OPTIMIZED

0.0151 0.0151

0.01925 0.01923

43.4 43.4
400.0 400.0
0.8 0.8
0.37 0.37

6.26548 6.27365

2.89779 2.90156

0.17572 0.17611

0.00188 0.00189
0.00188 0.00189

0.02267 0.02265

0.001 0.001
2.5 2.5

0.242 0.242

76.21024 76.21024

0.52954 0.52954

0.08588 0.08577
87.52 87.52

0.16684 0.16684

0.05226 0.05226

0.2191 0.2191

0.14942 0.14942
0.14942 0.14942

0.004 0.004

0.01139 0.01114

0.0 0.0

0.01139 0.01114

0.0 0.0

0.0 0.0
0.0 0.0

0.0 0.0

0.37705 0.37705

21.0 21.0
3.5 3.5

0.0533 0.0533

4.5 4.5
3.5 3.5
0.03723 0.03723

3.5 3.5
1.5 1.5
43.4 43.4
0.3199 0.3199

3.5 3.5
18.0 18.0
46.4 46.4
0.01992 0.01992
3.5 3.5
1.5 1.5
82.4 82.4
0.0 0.0

0.0 0.0
2.12 2.12
85.4 85.4
0.0533 0.0533

3.5 3.5
4.5 4.5
89.64 89.64

1.2 1.2
0.09864 0.09864

24.3309 24.3309

1.47935 1.4268

0.91459 0.88209

1.58696 1.59815
1.58696 1.59815

27.15626 27.31564

2.50154 2.48024

4140.0 4140.0

1200.0 1200.0
3450000.0 3450000.0
507.80693 507.80693

46.4 46.4
43.4 43.4
2400000.0 2400000.0
3148.62983 3148.62983

82.4 82.4
46.4 46.4
2400000.0 2400000.0
5591.53236 5591.53236

82.4 82.4
46.4 46.4
2400000.0 2400000.0
948.88665 948.88665

85.4 85.4
82.4 82.4
2400000.0 2400000.0
260.67223 260.67223

74.0 74.0
2.12 2.12
956.0 956.0
87.52 87.52
0.0 0.0
3194.0953 3194.0953

98.64 98.64
89.64 89.64
2400000.0 2400000.0

2.50154 2.48024

850.36557 850.36557
Cable No.4 Cable No.5
1200-132KV-SEC-OPTIMIZED 1200-132KV-SEC-OPTIMIZED

0.0151 0.0151

0.01923 0.01925

43.4 43.4
400.0 400.0
0.8 0.8
0.37 0.37

6.27315 6.26565

2.90133 2.89786

0.17609 0.17573

0.00189 0.00188
0.00189 0.00188

0.02265 0.02267

0.001 0.001
2.5 2.5

0.242 0.242

76.21024 76.21024

0.52954 0.52954

0.08577 0.08588
87.52 87.52

0.16684 0.16684

0.05226 0.05226

0.2191 0.2191

0.14942 0.14942
0.14942 0.14942

0.004 0.004

0.01426 0.01139

0.0 0.0

0.01426 0.01139

0.0 0.0

0.0 0.0
0.0 0.0

0.0 0.0

0.37705 0.37705

21.0 21.0
3.5 3.5

0.0533 0.0533

4.5 4.5
3.5 3.5
0.03723 0.03723

3.5 3.5
1.5 1.5
43.4 43.4
0.3199 0.3199

3.5 3.5
18.0 18.0
46.4 46.4
0.01992 0.01992
3.5 3.5
1.5 1.5
82.4 82.4
0.0 0.0

0.0 0.0
2.12 2.12
85.4 85.4
0.0533 0.0533

3.5 3.5
4.5 4.5
89.64 89.64

1.2 1.2
0.09864 0.09864

24.3309 24.3309

1.427 1.47979

0.88222 0.91485

1.59178 1.58634
1.59178 1.58634

27.28985 27.14522

2.47401 2.50119

4140.0 4140.0

1200.0 1200.0
3450000.0 3450000.0
507.80693 507.80693

46.4 46.4
43.4 43.4
2400000.0 2400000.0
3148.62983 3148.62983

82.4 82.4
46.4 46.4
2400000.0 2400000.0
5591.53236 5591.53236

82.4 82.4
46.4 46.4
2400000.0 2400000.0
948.88665 948.88665

85.4 85.4
82.4 82.4
2400000.0 2400000.0
260.67223 260.67223

74.0 74.0
2.12 2.12
956.0 956.0
87.52 87.52
0.0 0.0
3194.0953 3194.0953

98.64 98.64
89.64 89.64
2400000.0 2400000.0

2.47401 2.50119

850.36557 850.36557
Cable No.6
1200-132KV-SEC-OPTIMIZED

0.0151

0.01912

43.4
400.0
0.8
0.37

6.30813

2.91751

0.17778

0.0019
0.0019

0.02256

0.001
2.5

0.242

76.21024

0.52954

0.0853
87.52

0.16684

0.05226

0.2191

0.14942
0.14942

0.004

0.01114

0.0

0.01114

0.0

0.0
0.0

0.0

0.37705

21.0
3.5

0.0533

4.5
3.5
0.03723

3.5
1.5
43.4
0.3199

3.5
18.0
46.4
0.01992
3.5
1.5
82.4
0.0

0.0
2.12
85.4
0.0533

3.5
4.5
89.64

1.2
0.09864

24.3309

1.65959

1.02601

1.36175
1.36175

23.18409

2.38777

4140.0

1200.0
3450000.0
507.80693

46.4
43.4
2400000.0
3148.62983

82.4
46.4
2400000.0
5591.53236

82.4
46.4
2400000.0
948.88665

85.4
82.4
2400000.0
260.67223

74.0
2.12
956.0
87.52
0.0
3194.0953

98.64
89.64
2400000.0

2.38777

850.36557