PROJECT OASIS

ALILA SALALAH RESORT


PUMP HEAD CALCULATIONS REPORT

For

P-G-007- COWBP01
COOLED WATER SUPPLY BOOSTER PUMPS
Table of Contents
Contents Page

1.0 CALCULATION DESCRIPTION & METHODOLOGY ............................................................................. 3


2.0 CALCULATION METHODOLOGY........................................................................................................... 4
3.0 HYDRAULIC CALCULATION RESULT................................................................................................... 7
4.0 APPENDICES ........................................................................................................................................... 8
4.1 AFC Drawing & Documents Appendix – 01 ......................................................................... 8
4.2 Pump Head Calculation Appendix - 02 ................................................................................ 8
4.3 Friction Loss Coefficient Appendix – 03 ............................................................................. 8
4.4 References Appendix – 04 ................................................................................................... 8

PUMP HEAD CALCULATIONS REPORT


For
P-G-007- COWBP01
COOLED WATER SUPPLY BOOSTER PUMPS
1.0 CALCULATION DESCRIPTION & METHODOLOGY

1. Calculation Input Parameters

The following listed factors were input in the computer simulation model for system head loss
Calculations:

1. Calculation Methodology = Darcy Weisbach


2. Pipe Materials = All hot and cold water pipes located inside the major
buildings (Main Building, Beach grille, Spa, Pool Villas and
Retreat units) shall be Copper tube and to be manufactured to
British Standard BS 2871 Part 1: 1971 Table "X"
= All underground / buried External Distribution pipes – All
External hot and cold water pipes from individual pump rooms
to the buidings shall be PPR pipes to DIN 8078.
3. Fluid = Water
4. Fluid Temperature = 20°C
5. Fluid Specific Gravity =1
6. Roughness Number = Not Known
7. Pipe Fittings Loss Coefficient = Crane Physical properties of Fluids & Flow Characteristics of
Valves, Fittings and Pipe (Pipe Flow Expert Defaults)
8. Pipe Length and Fittings = as per AFC Drawing Provided by DAWOOD
10. Pipe Size and Valves = as per AFC Drawing Provided by DAWOOD
11. Cold Water Booster pump Rates = as per AFC Drawing Provided by DAWOOD
12. Pumps Specified Capacity from AFC Drawings
a. Cold Water Supply Booster pumps
3.5 L/s each Duplex Set with VFD (2 Duty/1 Standby)
Head: 20m Head
UV = 2-3 psi

2. Documents and Information Used in the Booster Pump Calculations

Refer to Appendix A for all the drawing information used in the calculations. All Drawings and Schedule
are provided by DAWOOD

3. Software

Pipe Flow Expert is a software application that runs on the Microsoft Windows operating system. It
used by engineers in over 75 countries worldwide, to model pipe systems where the flow rates,
PUMP HEAD CALCULATIONS REPORT
For
P-G-007- COWBP01
COOLED WATER SUPPLY BOOSTER PUMPS
pressure losses, and pumping requirements of the system need to be calculated. The Pipe Flow
Expert software has an intuitive interface that makes it easy for users to start working on their pipe
designs, which can be drawn out on a 2D or 3D isometric grid.

The software is backed up by an unrivalled support service that provides help to users when they
need it. Pipe Flow Expert is designed to help today’s engineers analyze and solve a wide range of
hydraulic problems where the flow rates, pressure losses and pumping requirements throughout a
pipe network must be determined.
The Pipe Flow Expert software will allow you to easily draw out a pipeline system and analyze the
performance of the system when flow is occurring. Pipe Flow Expert calculates the balanced steady
flow and pressure conditions of the system. The software will allow you to perform analysis of
alternate systems under various operating conditions.
The reported results include:
o Flow rates for each pipe
o Fluid velocities for each pipe
o Reynolds numbers
o Friction factors
o Friction pressure losses
o Fitting pressures losses
o Component pressure losses
o Pressures at each node
o Hgl (hydraulic grade line) values
o Pump operating points
o Npsha at pump inlet

The input and display of system information on the Pipe Flow Expert drawing and in the results tables
can be shown in metric or imperial units to suit your preference and specific units for each item (such
as flow rate) can also be configured and set on an individual basis as required.

The Pipe Flow Expert software has been designed for the professional engineer who needs a
powerful tool that has a class leading, easy to use and robust interface that makes it simple to design
and analyze pipe networks. The Software uses Crane Technical Paper 410 as a standard procedure of
calculation and methodology.

2.0 CALCULATION METHODOLOGY

Pipe Flow Expert 2017 7.30 was used to generate the results. The following procedure was used to
prepare the calculations:
1. The entire system was modeled in Pipe Flow Expert 2017 7.30, with all the inputs based on the

provided AFC drawings by DAWOOD for PROJECT OASIS project .

PUMP HEAD CALCULATIONS REPORT


For
P-G-007- COWBP01
COOLED WATER SUPPLY BOOSTER PUMPS
2. Pipe vertical lengths were based on floor to floor elevation based on the elevation details from the

provided AFC Drawings.

3. All nodes elevation was taken from the elevation drawings and AFC drawings.

4. Fittings for the pipe e.g. elbows & bends, are given 10% assumptions for each pipe routing from the

provided Schematic Drawing.

5. For Booster pumps calculation, all Fixtures units are combined in one Flowrate for the ease of

understanding and calculations,

6. Calculation of Fixtures is based on the below reference, and as per ASPE references, refer to Annexure

4.

7. CALCULATION OF FIXTURES/ per room

CALCULATION OF FIXTURES/ per room


EQUIV
Balancing Tank

Cofee Machine
Wash basin 1
Wash basin 2

Kitchen Sink/
Hand Spray
Equipment

3 door U/C

Provision/

Generator
ALENT
Bin Marie

Bath Tub
Ablution

machine
Ice cube

Bib tap
Kitchen

Shower
Chiller

Steam
Urinal

Spare
S/ SERVIN FLOWR

sink
ROOM
N G ATE,

TOTAL
F.U. TO
L/S
(ASPE
F.U. 2 2 2 2 3 2 1 1 1 1 2 2 2 2 1 2 2 Refere
nce)
MAIN
DISPLAY
1 VILLA - - - - - 3 2 - - - - - - 2 - - - - 7 0.38
BAR
GF
MAIN
ALL DAY 1
2 VILLA - - - - 2 - - - 1 - - - - 6 - - 2 - 0.53
DINING 1
GF
MALE MAIN
1
3 TOILET & VILLA - - - - - - - 3 2 1 - - - - 6 - - - 0.57
2
M.ACC TOI GF
FEMALE MAIN
5 TOILET& VILLA - - - - - - - 4 3 1 - - - - - - - - 8 0.44
M.ACC TOI GF
HOT &
MAIN
COLD
6 VILLA - - - - - - - - - - - - - 2 - 1 - - 3 0.19
BEVERAGE
GF
COUNTER
MAIN
7 PANTRY VILLA - - - - - - 4 - 1 - - - - 2 - - - - 7 0.38
GF
MAIN
MALE
8 VILLA - 8 - - - - - - - - - - - - - - - - 8 0.44
ABLUTION
GF
PUMP HEAD CALCULATIONS REPORT
For
P-G-007- COWBP01
COOLED WATER SUPPLY BOOSTER PUMPS
MAIN
FEMALE
9 VILLA - 4 - - - - - - - - - - - - - - - - 4 0.25
ABLUTION
GF
MAIN
1
TOILET VILLA - - - - - - - 1 1 - - - - - - - - - 2 0.16
0
GF
MAIN
1
PANTRY VILLA - - - - - - - - - - - - - 2 - - - - 2 0.16
1
GF
MAIN
1 ACC
VILLA - - - - - - - 1 1 - - - - - - - - - 2 0.16
2 TOILET
GF
MAIN
1 FEMALE
VILLA - - - - - - - 4 4 - - - - - - - - - 8 0.44
3 TOILET
GF
MAIN
1 MALE
VILLA - - - - - - - 4 4 - 1 - - - - - - - 9 0.69
4 TOILET
GF
MAIN
1 ACC
VILLA - - - - - - - 1 1 - - - - - - - - - 2 0.16
5 TOILET
GF
SWIMMIN
MAIN
1 G POOL
VILLA - - - 2 - - - - - - - - - - - - - - 2 0.16
6 BALANCIN
GF
G TANK
MALE MAIN
1 1
CHANGIN VILLA - - - - - - - 3 3 - - 4 - - - - - - 0.5
7 0
G GF
FEMALE MAIN
1 1
CHANGIN VILLA - - - - - - - 3 3 - - 4 - - - - - - 0.5
8 0
G GF
MAIN
1 POOL
VILLA - - - - - - - - - - - 4 - - - - - - 4 0.25
9 SHOWER
GF
MAIN
2 FEMALE
VILLA - - - - - - - 3 2 - - - - - - - - - 5 0.28
0 TOILET
GF
MAIN
2 MALE
VILLA - - - - - - - 3 2 - - - - - - - - - 5 0.28
1 TOILET
GF
MAIN
2 COLD
VILLA - - - - - - - - 1 - - - - 2 - - - - 3 0.19
2 KITCHEN
GF
MAIN
2 FUNCTION
VILLA - - 6 - - - - - - - - - - - - - - - 6 0.32
2 & SERVICE
GF
MAIN
2 MAIN 1 1
VILLA - - - - - - - - - - - - - - - - - 0.525
3 KITCHEN 4 4
GF
2 DISPENSE MAIN
- 8 - - - - - - - - - - - - - - - 8 0.44
4 BAR VILLA -
PUMP HEAD CALCULATIONS REPORT
For
P-G-007- COWBP01
COOLED WATER SUPPLY BOOSTER PUMPS
GF
MAIN
2 MAIN 2 2
VILLA - - - - - - - - - - - - - - - - - 1.07
5 KITCHEN 4 4
GF
MAIN
2 BAKERY/
VILLA - - 7 - - - - - - - - - - - - - - - 7 0.38
6 PASTRY
GF
MAIN
2 ROOM
VILLA - - 4 - - - - - - - - - - - - - - - 4 0.25
7 SERVICE
GF
MAIN
2 MEAT/VE 1 1
VILLA - - - - - - - - - - - - - - - - - 0.85
8 GETABLE 9 9
GF
MAIN
2 GOOD
VILLA - - 2 - - - - - - - - - - - - - - - 2 0.16
9 LOBBY
GF
VEGETABL MAIN
3 1 1
E ROUGH VILLA - - - - - - - - - - - - - - - - - 0.5
0 0 0
PREP GF
8.

3.0 HYDRAULIC CALCULATION RESULT

Specified Calculated Cooled Water


Equipment Booster pump Head
Capacity (IFC) Recommended Pump
Equipment Tag Pump Head Velocity

Calculated Pump TDH (m) (m/s)


Capacity Calculated
TDH (m) TDH (m) @ 10 %
(l/s) Pump TDH (m)
F.O.S

P-G-007-
3.5 20 28.515 31.366 32 1.067
COWBP01 (Duty)
P-G-007-
3.5 20 28.526 31.3786 32 1.067
COWBP01 (Duty)
P-G-007-
COWBP01 3.5 20 28.526 31.3786 32 1.067
(Standby)

Note:

1. For Detailed Calculation Report, Refer to Attached Pipe Flow PROJECT OASIS Pump Head
Calculations (Appendix 2).

PUMP HEAD CALCULATIONS REPORT


For
P-G-007- COWBP01
COOLED WATER SUPPLY BOOSTER PUMPS
2. For Calculated TDH value, refer to Pump data on the generated Pipe flow 2017 7.30 report (Appendix
2).
3. For Data references and Technical Details Refer to Attached References (Appendix 5).

4.0 APPENDICES

4.1 AFC Drawing & Documents Appendix – 01

4.2 Pump Head Calculation Appendix - 02

4.3 Friction Loss Coefficient Appendix – 03

4.4 References Appendix – 04

PUMP HEAD CALCULATIONS REPORT


For
P-G-007- COWBP01
COOLED WATER SUPPLY BOOSTER PUMPS